112
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Figure 77. Optional X-Slot Cards
Relay Interface Card
Modbus Card
Industrial Relay Card
Power Xpert Gateway UPS Card
Power Xpert Gateway
PXGX UPS
EMP
Upstream
Downstream
100
100
Act
Act
Setup
Restart
Status
DHCP
Ident
Power
66..66
C
Coonnttrrooll TTeerrm
miinnaallss
Connect the cables to the control terminals with a mating connector. Input and output terminals have a
functional isolation from terminal to terminal. They are connected to the UPS through individual 1 MΩ resistors.
Figure 78. External Control Terminal Connections
+ Polarity
– Polarity
2
1
+ Polarity
– Polarity
2
1
2
1
2
1
Signal Input 1 (programmable)
Signal Input 2 (programmable)
REPO Normally Open
REPO Normally Closed
Normally Open
Normally Closed
1
2
Common
3
Relay Output
UPS
Connectors
(see Figure 73)
+ Polarity
– Polarity
2
1
Redundant Signal Wiring
(For Parallel Use Only)
+ Polarity
– Polarity
2
1
Standalone/Parallel
NOTE
If using a semiconductor switch type, pay attention to the proper polarity. A relay or
other mechanical control is preferred.
66..77
R
Reellaayy O
Ouuttppuutt C
Coonnttaaccttss
The UPS incorporates a programmable relay output with potential free contacts for remote alarm indications
(see
). You can obtain an additional four relay outputs with the X-Slot compatible Relay Interface Card.
CAUTION
The relay output contacts must not be connected to any utility connected circuits; the utility requires reinforced
insulation. The relay output contacts have a maximum rating of 30 Vac/1A and 60 Vdc/2A nominal values.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...