106
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Table 14. EBM Selection for UPS Configurations (Continued)
UPS + 2 EBMs
2
UPS + 3 EBMs
3
UPS + 4 EBMs
4
1.
Press the
button to save the setting.
2.
Press the
ESC
button until the Start screen appears.
55..1188
C
Coonnffiigguurriinngg TThhee U
UP
PS
S FFoorr C
Cuussttoom
meerr S
Suupppplliieedd EExxtteerrnnaall B
Baatttteerriieess
NOTE
This setting is available only for BladeUPS 12i models.
If you installed a customer-supplied external battery using the External Battery Interconnect accessory, set the
external battery capacity (in Watts per cell) to configure the UPS for the customer-supplied external battery.
The UPS uses the setting to adjust the predicted battery runtime.
CAUTION
Do not attach the External Battery Interconnect to an EBM. Doing so may cause damage to the EBM or the
UPS.
NOTE
To install the External Battery Interconnect accessory, refer to the External Battery
Interconnect User’s Guide.
1.
Press any button on the front panel display to activate the menu options, then select SETTINGS, USER
SETTINGS, BATTERY SETUP, and EXTERNAL BATTERY CAPACITY.
2.
Use the or buttons to select the Watts per cell.
For the correct Watts per cell, see the specifications sheet for the customer-supplied external batteries.
3.
Press the
button to save the setting.
4.
Press the
ESC
button until the Start screen appears.
NOTE
The UPS sets the charge current to the maximum that the UPS charger can supply and
disables the 24-hour recharge battery diagnostic test.
55..1199
S
Seettttiinngg tthhee B
Baatttteerryy LLoow
w LLeevveell A
Allaarrm
m
The default Battery Low Alarm Level setting provides approximately 2.5 minutes of battery warning for a UPS.
Additional EBMs installed in a parallel system can provide a longer warning time.
1.
Press any button on the front panel display to activate the menu options, then select SETTINGS, USER
SETTINGS, BATTERY SETUP, and Battery Low Alarm Level.
2.
Use the or
buttons to select the volts per cell.
To adjust the Battery Low Alarm Level setting to provide different warning times for a parallel system with
additional EBMs installed, see
.
Configuring The UPS For Customer Supplied External Batteries
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...