Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
89
6.
Repeat Steps 3 through 5 to install a CAN Bridge Card in each in each new UPS to be installed
NOTE
The BladeUPS parallel system can automatically assign identities to each UPS in the
system based on the order in which their CAN Bridge Cards are wired in Steps 10 and
11. For more information, see the “Auto identification” Section..
7.
Determine the type of PARALLEL SYSTEM configuration you have by examining the ports on the
EXISTING Powerware Hot Sync CAN Bridge Cards:
•
Legacy configuration requiring modification of the existing UPSs: The first UPS has a black terminating
plug in the CAN IN port. Continue to Step 8.
•
An existing configuration that was installed or modified as a new configuration, requiring no additional
modification of the existing UPSs: The first UPS has a blue terminating plug in the CAN IN port and the
last UPS has a blue terminating plug in the CAN OUT port. Continue to Step 10.
8.
Remove and discard the black terminating plug installed in the CAN IN port of the first UPS.
9.
For each existing UPS, remove and discard the Jumper J7 installed in the Powerware Hot Sync CAN
Bridge Card:
a.
Remove and retain the screws securing the Powerware Hot Sync CAN Bridge Card to the UPS.
b.
Disconnect the CAN Bridge Card Cable from the Powerware Hot Sync CAN Bridge Card.
c.
Remove the Powerware Hot Sync CAN Bridge Card from the UPS.
d.
Remove and discard the Jumper J7 (see
).
Figure 71. Removing the Jumper J7 (Side View)
Jumper J7 - Pins 1 and 2
(First and Last UPS) Shown
e.
Reinstall each Powerware Hot Sync CAN Bridge Card in the open X-Slot communication bay #2 on its
UPS rear panel. Install screws and tighten.
f.
Reconnect the CAN Bridge Card Cable to the Powerware Hot Sync CAN Bridge Card.
Summary of Contents for BladeUPS none
Page 8: ...viii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Table of Contents ...
Page 12: ...xii Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Figures ...
Page 14: ...xiv Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 List of Tables ...
Page 20: ...6 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Introduction ...
Page 134: ...120 Eaton BladeUPS 5 kVA to 60 kVA N 1 User s Guide 164201649 Rev 14 Metering ...
Page 160: ...16420164914 164201649 14 ...