![Eaton AMT Vari-Depth Instruction Leaflet Download Page 5](http://html1.mh-extra.com/html/eaton/amt-vari-depth/amt-vari-depth_instruction-leaflet_526657005.webp)
Instruction Leaflet IL14946I
Effective November 2012
Instructions for Type AMT Vari-Depth
®
Handle
Mechanism for Above Handle (Variable-Width)
eaton Corporation
www.eaton.com
0.250 (6.35) Approximate
Brace Length
Brace will work as furnished at Max. D + 0.125 (3.18) to Max. D - 0.125(3.18).
Table “A” - For Rod and Brace
Breaker
Long Rod and Brace
Short Rod and Brace
Maximum Minimum Maximim Minimum
Box Box
Box Box
Height D Height D Height D Height D
FB, F-Frame Series C© 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5 (165.1)
KB, J-Frame Series C© 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5 (165.1)
JA, KA, LB
K-Frame Series C© 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 8.5
(165.1 - 215.9)
LA
18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 8.5
(165.1 - 215.9)
MA, LCL
18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 7.5
- 8.5
(190.5 - 215.9)
NB
18.5 (469.9) 13.5 (342.9) 14.5 (368.3) 7.5
- 10 .0
(190.5 - 254.0)
FB, TRI-PAC, FCL 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 9.0
(165.1 - 228.6)
LA, TRI-PAC 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 12.0
(165.1 - 304.8)
NB, TRI-PAC 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 7.5
- 13.0
(190.5 - 330.2)
Switch
DS-30, 60, 100 Unfused 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5 (165.1)
DS-30, 60, 100 Fused 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 8.0
(165.1 - 203.2)
DS-200 Unfused) 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5 (165.1)
DS-200 Fused 18.5 (469.9) 12.5 (317.5) 14.5 (368.3) 6.5
- 9.0
(165.1 - 228.6)
Breakers
Dim. Dim. Dim. Dim. Dim. Dim. Dim.
C E F G H J K (Max.)
FB, FB TRI-PAC
F-Frame Series C© 7.875 5.438 - 3.250 3.688 3.969 6.469
(200.03) (138.11) - (82.55) (93.66) (100.81) (164.31)
KB, J-Frame Series C© 7.188 4.750 - 4.625 5.125 5.313 7.813
JA, KA, LB (182.56) (120.65) - (117.48) (130.18) (134.95) (198.44)
K-Frame Series C© 7.188 - 5.625 4.625 5.125 5.313 7.813
(182.56) - (142.88) (117.48) (130.18) (134.95) (198.44)
LA & LA TRI-PAC 7.188 - - 4.625 5.125 5.313 7.813
(182.56) - - (117.48) (130.18) (134.95) (198.44)
MA, LCL 7.188 - - 4.625 5.125 5.313 7.813
(182.56) - - (117.48) (130.18) (134.95) (198.44)
NB & NB TRI-PAC 7.188 - - 4.625 5.125 5.313 7.813
(182.56) - - (117.48) (130.18) (134.95) (198.44)
Switches
DS-30, 60, 100A Unfused 7.875 5.188
- 3.250 3.688 3.969 6.469
(200.03) (131.76) - (82.55) (93.66) (100.81) (164.31)
DS-200A Unfused 7.188 4.750 - 4.625 5.125 5.313 7.813
(182.56) (120.65) - (117.48) (130.18) (134.95) (198.44)
DS-30, 60, 100A Fused 7.875 5.188 - 3.250 3.688 3.969 6.469
(200.03) (131.76) - (82.55) (93.66) (100.81) (164.31)
DS-30, 60, 100A Fused 7.875 5.188
- 3.250 3.688 3.969 6.469
(200.03) (131.76) - (82.55) (93.66) (100.81) (164.31)
DS-200A Fused 7.188 11.000 - 4.625 5.125 5.313 7.813
(182.56) (279.40) - (117.48) (130.18) (134.95) (198.44)
Table “B”
For 250 Volt Class H Fuses. For 600 Volt Class H and J Fuses.
Breaker may be moved 1.250 (31.75) closer to enclosure wall the max. shown.
Breaker must be at max. distance from enclosure wall.