Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01
9
Table 6. User Settings (Continued)
Submenu
Available Settings
Default settings
High Efficiency
mode
[Enabled] [Disabled] Power the output from Bypass for high efficiency
[Disabled]
Bypass transfer
[Transfer if BP AC NOK]
[Enabled] [Disabled]
Allow transfer on Bypass out of tolerance
[Enabled]
Overload
prealarm
[10%] … [102%]
Load % when overload alarm occurs
[102%]
Redundancy
mode
[Unitary UPS] [Hot Standby]
Force slew rate value to 0.5Hz/s
Unitary UPS
On/Off
Settings
Cold Start
[Enabled] [Disabled]
Authorize the product to start on battery power.
[Enabled]
Forced reboot
[Enabled] [Disabled]
If mains recover during a shutdown sequence:
If set to Enabled, shutdown sequence will complete and wait 10
seconds prior to restart, If set to Disabled, shutdown sequence will
not complete and restart will occur immediately.
[Enabled]
Auto restart
[Enabled] [Disabled]
Authorize the product to restart automatically when mains recovers
after a complete battery discharge.
[Enabled]
Auto start
[Enabled] [Disabled]
The UPS automatically starts up as soon as mains power is available
(no need to press the
button).
[Disabled]
Energy Saving
[Disabled] [100W] … [1000W]
If Enabled, UPS will shutdown after 5 min. of back-up time, if load is
less than threshold.
[Disabled]
Sleep mode
[Enabled] [Disabled]
If Disabled, LCD and communication will turn OFF immediately after
UPS is OFF.
If Enabled, LCD and communication stays ON 1h30 min after UPS is
OFF.
[Enabled]
Remote
Command
[Enabled] [Disabled]
If Enabled, shutdown or restart commands from software are
authorized.
[Enabled]
Bypass standby
[Enabled] [Disabled]
Define if output is powered from Bypass in Standby mode.
[Enabled]
Battery
settings
Low battery
warning
[Capacity] [0%] … [100%]
The alarm triggers when the set percentage of battery capacity or
remaining back-up time is reached.
[20%]
Restart bat.
level
[0%] ... [100%]
If set, automatic restart will occur only when percentage of battery
charge is reached.
[0%]
Summary of Contents for 9PX6KIRTN-L
Page 16: ...10 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 User Settings ...
Page 40: ...34 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Recycling The Used Equipment ...
Page 44: ...38 Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 Compliance Contact ...
Page 49: ...Eaton 9PX Lithium Ion User Guide DPD 9PX2205 Rev 01 43 Model Specifications EMEA ...
Page 50: ...DPD 9PX220501 DPD 9PX2205 01 ...