Eaton 9PX Lithium-Ion
P-164001006—Rev 01
31
1.
Select Settings, In/Out settings, and High Efficiency mode.
2.
Select Enabled and Enter to confirm.
3.
The UPS transfers to High Efficiency mode after 5 minutes.
55..77
C
Coonnffiigguurriinngg B
Byyppaassss S
Seettttiinnggss
The following settings are available for configuring Bypass operation.
Changing the settings changes UPS behavior and may result in decreased protection.
Bypass Voltage Low Limit
The default disables a transfer to Bypass if the measured bypass voltage level is below the nominal output
voltage minus 20%. You can configure the setting for another voltage value. This setting can be overruled by
the “Qualify Bypass” setting.
Bypass Voltage High Limit
The default disables a transfer to Bypass if the measured bypass voltage level is above the nominal output
voltage plus 15%. You can configure the setting for another voltage value. This setting can be overruled by the
“Qualify Bypass” setting.
Qualify Bypass
The default setting (“In spec”) allows a transfer to Bypass only when Bypass is within the following
specifications:
•
Bypass voltage is between the “Bypass Voltage Low Limit” and “Bypass Voltage High Limit” settings
•
Bypass frequency is within nominal frequency 5%.
You can prohibit Bypass (”Never”) or always allow Bypass with no specification checking (“Always”). For
“Always on UPS Fault,” transfer to Bypass is always made on UPS fault; otherwise, operation proceeds as
with the default setting.
Synchronization Window
The UPS tries to synchronize with Bypass when the Bypass frequency is less than the value set for the
“Synchronization Window” setting. When the Bypass frequency is more than the set value, the UPS goes to
nominal frequency.
Unsynchronized Transfers
When Qualify Bypass is set to “Always” or “Always on Fault” you can select the interruption time when
transferring to bypass, default setting is “Half Cycle” but can be changed to “Full cycle”.
55..88
C
Coonnffiigguurriinngg B
Baatttteerryy S
Seettttiinnggss
Low battery warning
During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than
the setting capacity threshold (0 % by default). This threshold can be modified.
Restart battery level
This setting is used to define the battery restart level. The battery level must reach this threshold to enable UPS
start.
55..99
R
Reettrriieevviinngg tthhee EEvveenntt LLoogg
To retrieve the Event log through the display:
Summary of Contents for 9PX1000IRTANZ-L
Page 34: ...28 Eaton 9PX Lithium Ion P 164001006 Rev 01 UPS Remote Control Functions...
Page 44: ...38 Eaton 9PX Lithium Ion P 164001006 Rev 01 Recycling The Used Equipment...
Page 48: ...42 Eaton 9PX Lithium Ion P 164001006 Rev 01 CE Compliance Contact...
Page 53: ...Eaton 9PX Lithium Ion P 164001006 Rev 01 47 Model Specifications...
Page 54: ...P 16400100601 P 164001006 01...