background image

Eaton 9PX Lithium-Ion

P-164001006—Rev 01

31

1.

Select Settings, In/Out settings, and High Efficiency mode.

2.

Select Enabled and Enter to confirm.

3.

The UPS transfers to High Efficiency mode after 5 minutes.

55..77

C

Coonnffiigguurriinngg B

Byyppaassss S

Seettttiinnggss

The following settings are available for configuring Bypass operation.

Changing the settings changes UPS behavior and may result in decreased protection.

Bypass Voltage Low Limit

The default disables a transfer to Bypass if the measured bypass voltage level is below the nominal output
voltage minus 20%. You can configure the setting for another voltage value. This setting can be overruled by
the “Qualify Bypass” setting.

Bypass Voltage High Limit

The default disables a transfer to Bypass if the measured bypass voltage level is above the nominal output
voltage plus 15%. You can configure the setting for another voltage value. This setting can be overruled by the
“Qualify Bypass” setting.

Qualify Bypass

The default setting (“In spec”) allows a transfer to Bypass only when Bypass is within the following
specifications:

Bypass voltage is between the “Bypass Voltage Low Limit” and “Bypass Voltage High Limit” settings

Bypass frequency is within nominal frequency 5%.

You can prohibit Bypass (”Never”) or always allow Bypass with no specification checking (“Always”). For
“Always on UPS Fault,” transfer to Bypass is always made on UPS fault; otherwise, operation proceeds as
with the default setting.

Synchronization Window

The UPS tries to synchronize with Bypass when the Bypass frequency is less than the value set for the
“Synchronization Window” setting. When the Bypass frequency is more than the set value, the UPS goes to
nominal frequency.

Unsynchronized Transfers

When Qualify Bypass is set to “Always” or “Always on Fault” you can select the interruption time when
transferring to bypass, default setting is “Half Cycle” but can be changed to “Full cycle”.

55..88

C

Coonnffiigguurriinngg B

Baatttteerryy S

Seettttiinnggss

Low battery warning

During discharge, the low battery alarm is activated if the remaining runtime goes below 3 minutes or less than
the setting capacity threshold (0 % by default). This threshold can be modified.

Restart battery level

This setting is used to define the battery restart level. The battery level must reach this threshold to enable UPS
start.

55..99

R

Reettrriieevviinngg tthhee EEvveenntt LLoogg

To retrieve the Event log through the display:

Configuring Bypass Settings

Summary of Contents for 9PX1000IRTANZ-L

Page 1: ...p n P 164001006 Revision 01 Eaton 9PX Lithium Ion Advanced Users Guide 9PX1000IRTANZ L 9PX1500IRTANZ L 9PX2000IRTAU L 9PX3000IRTANZ L 9PXEBM48RT1U L 9PXEBM72RT1U L Eaton 9PX Lithium Ion...

Page 2: ...K OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as importan...

Page 3: ...rical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply...

Page 4: ...less than 25 C This charges the battery thus avoiding possible irreversible damage During the replacement of the Battery Module it is imperative to use the same type and number of element as the origi...

Page 5: ...Connecting the EBM s 18 3 6 Detecting other Accessories 20 3 7 UPS Connection without Hotswap MBP Module 21 3 8 Connection with a Hotswap MBP Module Optional Accessory 22 4 4 C Co om mm mu un niic ca...

Page 6: ...swap MBP 37 6 5 Recycling The Used Equipment 37 7 7 T Tr ro ou ub blle es sh ho oo ot tiin ng g 3 39 9 7 1 Typical Alarms and Faults 39 7 2 Silencing the Alarm 40 7 3 Service and Support 40 7 4 CE Com...

Page 7: ...N has implemented an environmental protection policy Products are developed according to an eco design approach Substances This product does not contain CFCs HCFCs or asbestos Packing To improve waste...

Page 8: ...can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eato...

Page 9: ...Table 2 Weights and Dimensions Model Dimensions D x W x H inch mm Weight lb kg 9PX1000IRTANZ L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 34 3 15 6 9PX1500IRTANZ L 17 7 x 17 3 x 3 4 450 x 440 x 86 5 34 8 15 8...

Page 10: ...ut contact 4 Connector for additional battery module 5 Primary group outlets for connection of critical equipment 6 Group 1 programmable outlets for connection of equipment 7 Group 2 programmable outl...

Page 11: ...3 UPS Accessories Part number Description 9PXEBM48RT1U L 9PXEBM72RT1U L Extended Battery Module Network M2 Network Card INDGW M2 Industrial Gateway Card Modbus TCP RTU Relay MS Relay Card BINTSYS Batt...

Page 12: ...ge Indicator Status Description Green On The UPS is operating normally on Online or on High Efficiency mode Orange On The UPS is on Battery mode Orange On The UPS is on Bypass mode Red On The UPS has...

Page 13: ...n 60mn The alarm triggers when the set percentage of battery capacity or remaining back up time is reached High Efficiency mode The UPS is operating on High Efficiency mode The UPS is powering and pro...

Page 14: ...ent Log Event filter Selects faults alarms and or events to display Event list Displays the events stored Reset fault list Clears events Fault log Fault list Displays the faults stored Reset fault lis...

Page 15: ...BP Inv BP Inv Short circuit Inv Stop Inv BP Inv BP Inv IT Inv BP Inv Inv Stop Input volt hysteresis Sets input voltage hysteresis from 1 to 10V 10V High Efficiency mode Enabled Disabled Power the out...

Page 16: ...the UPS in case of phase vs neutral wires swapping Disabled Power off Alert Enabled Disabled If Enabled activates a confirmation screen that requires user confirmation after pressing the power button...

Page 17: ...l alarm Ext charger ON OVL pre alarm Relay Bypass DB9 1 On bat Low bat Bat fault Bypass UPS OK Load protected Load powered General alarm Ext charger ON OVL pre alarm DB9 1 Low bat DB9 7 On bat Low bat...

Page 18: ...s 99s Sets delay before noticing on battery information to software 0s General alarm On battery Battery fault Internal fault Overload pre alarm Internal fault Ambient temp Fan lock Bypass overload Cur...

Page 19: ...on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your service representative 3 3 2 2 C Ch he ec ck kiin ng g t th he e A Ac cc ce...

Page 20: ...leaflet 22 Safety instructions 23 Quick start 24 Mounting kit for 19 inch enclosures 25 2 supports for tower position Elements supplied depending on the version or optional 26 NMC communication card o...

Page 21: ...pplied depending on the version or optional 26 NMC communication card optional standard on Network Bundle options 27 HotSwap MBPmodule optional 28 Connection cables between Hotswap MBP module and UPS...

Page 22: ...ts 3 3 3 3 T To ow we er r I In ns st ta alllla at tiio on n Tip If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet...

Page 23: ...Rev 01 17 Adjustment of the angle of vision of the LCD panel 3 3 4 4 R Ra ac ck k I In ns st ta alllla at tiio on n Rack mounting of UPS EBM and accessory modules Follow steps 1 to 4 for module mounti...

Page 24: ...he UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly 1 Plug the EBM power cable s into the battery connector s Up to 4 EBMs may be c...

Page 25: ...omm Battery Comm Battery Comm EBM Communications wiring UPS EBM 1 EBM 2 EBM 3 EBM 4 NOTE The EBM communication wiring connections are directional and must be connected in the correct sequence to ensur...

Page 26: ...mmunication wiring connections are directional and must be connected in the correct sequence to ensure proper detection regulation and lifecycle monitoring of the integrated battery management system...

Page 27: ...oads to the outlets marked 5 and the non priority loads to the outlets marked 6 7 that can be programmed For the 9PX 3000RTAU model connect any high power devices to the 16 A outlet To program shutdow...

Page 28: ...is still supplied 2 Set switch 33 back to Normal position The HotSwap MBP module has a rotary switch 33 with two positions Normal the load is supplied by the UPS LED 31 is on Bypass the load is suppl...

Page 29: ...Installation of the communication cards 2 It is not necessary to shutdown the UPS before installing a communication card 1 Remove the slot cover 2 secured by screws 2 Insert the communication card in...

Page 30: ...rameter see Settings Com Settings Shutdown commands on page 16 the unit may startup automatically IMPORTANT Warning Signal inputs have no function by default please choose a function through the LCD S...

Page 31: ...ctor type Terminal 14 AWG maximum wires External breaker specification 60 V DC 30V AC 20mA max RPO 11 ROO Remote Control Connection and Test 1 Check the UPS is shut down and the electrical supply netw...

Page 32: ...alarm Choose events that will trigger this alarm trough the LCD Settings Com settings General alarm for more information on possible events please look at page 16 Ext charger ON Control an optional e...

Page 33: ...te Eaton Intelligent Power Software suite is available from eaton com download Eaton Software suite provides up to date graphics of UPS power and system data and power flow It also gives you a complet...

Page 34: ...28 Eaton 9PX Lithium Ion P 164001006 Rev 01 UPS Remote Control Functions...

Page 35: ...start setting in ON OFF Settings in Table 6 To start the UPS on battery 1 Press the button on the UPS front panel until the UPS front panel display illuminates and shows a status of UPS starting The U...

Page 36: ...d your equipment is not protected however the utility power continues to be passively filtered by the UPS The indicator illuminates Depending on overload conditions the UPS remains in Bypass mode for...

Page 37: ...imit and Bypass Voltage High Limit settings Bypass frequency is within nominal frequency 5 You can prohibit Bypass Never or always allow Bypass with no specification checking Always For Always on UPS...

Page 38: ...ect Event log 2 Scroll through the listed events 5 5 1 10 0 R Re et tr riie ev viin ng g t th he e F Fa au ullt t L Lo og g To retrieve the Fault log through the display 1 Press any button to activate...

Page 39: ...rical shock or burn from high short circuit current Observe the following precautions 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts...

Page 40: ...hands to support the battery pack See Recycling the used equipment on page 38 for proper disposal 7 Verify that the replacement batteries have the same rating as the batteries being replaced 8 Put th...

Page 41: ...gs Reset section before restarting the unit 6 6 3 3 B Ba at tt te er ry y S Se et tt tiin ng gs s R Re es se et t After replacement of the internal UPS batteries and extended battery modules and befor...

Page 42: ...If optional EBMs are installed verify that the EBM are connected to the UPS See section 3 Verify that the UPS power cord is plugged in 4 The UPS front panel display illuminates and shows EATON logo 5...

Page 43: ...cates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local re...

Page 44: ...38 Eaton 9PX Lithium Ion P 164001006 Rev 01 Recycling The Used Equipment...

Page 45: ...To check the Event log or Fault log 1 Press any button on the front panel display to activate the menu options 2 Press the button to select Event log or Fault log 3 Scroll through the listed events or...

Page 46: ...UPS transferred to Bypass mode the UPS will return to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any he...

Page 47: ...k or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units IMPORT...

Page 48: ...42 Eaton 9PX Lithium Ion P 164001006 Rev 01 CE Compliance Contact...

Page 49: ...able 8 Extended Battery Module List Model Configuration Battery Voltage For Power Module 9PXEBM48RT1U L Rack Tower 48Vdc 1000 1500VA 9PXEBM72RT1U L Rack Tower 72Vdc 2200 3000VA Table 9 Weights and Dim...

Page 50: ...IEC C14 IEC10A 9PX1500IRTANZ L 9PX2000IRTAU L IEC C20 IEC16A 9PX3000IRTANZ L Table 12 Electrical Output All Models Normal Mode Battery Mode Voltage Regulation 1 2 Efficiency 98 High Efficiency mode 9...

Page 51: ...ower Factor Up to 0 9 Load Crest Ratio Up to 3 1 Table 13 Electrical Output Connections Model Output Connection Output Cable 9PX1000IRTANZ L 4 IEC10A 2 IEC10A group 1 2 IEC10A group 2 9PX1500IRTANZ L...

Page 52: ...F with batteries 25 to 55 C 13 to 130 F without batteries Transit Temperature 25 to 55 C 13 to 130 F Relative Humidity 0 to 96 no condensing Operating Altitude Up to 3 000 meters 9 843 ft above sea l...

Page 53: ...Eaton 9PX Lithium Ion P 164001006 Rev 01 47 Model Specifications...

Page 54: ...P 16400100601 P 164001006 01...

Reviews: