Eaton 9PX Lithium-Ion
P-164001006—Rev 01
11
Table 6. User Settings (Continued)
Submenu
Available settings
Default settings
- [Function]: [No] [ROO] [RPO] [Building
alarm] [Forced bypass] [On generator]
[Remote shutdown]
No
- [Delay]: [0s] … [999s]
- [Active]: [Open] [Closed]
[0s]
[Open]
DB9-4 port:
No
- [Function]: [No] [ROO] [RPO] [Building
alarm] [Forced bypass] [On generator]
[Remote shutdown]
- [Delay]: [0s] … [999s]
- [Active]: [High] [Low]
[0s]
[High]
Output signals
[Relay] [DB9-1] [DB9-7] [DB9-8] Sets
events or fault that will actuate Output
signal parameters through external
contact connector or RS232
[Relay]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[Relay] [Bypass]
[DB9-1]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-1] [Low bat]
[DB9-7]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-7] [UPS OK]
[DB9-8]: [On bat] [Low bat] [Bat fault]
[Bypass] [UPS OK] [Load protected]
[Load powered] [General alarm] [Ext.
charger ON] [OVL pre-alarm]
[DB9-8] [On bat]
Remote
command
[Enabled] [Disabled] If Enabled,
shutdown or restart commands from
software are authorized.
[Enabled]
Shutdown
commands
[Send CMD] [Output OFF] [OFF delay]
[restart]
Sets events or fault that will actuate
Output signal parameters through
external contact connector or RS232
port
[Send CMD]: [Yes] [No]
Send CMD: [No]
[Output OFF]: [No] [UPS] [Group 1]
Output OFF: [No]