Page 14

8-11kVA EU_EN

2. Presentation

Submenu

Available settings

Default settings

In/Out settings

Interrupt time

If Bypass transfer is enabled, 

Interrupt time: [10ms] [20ms]

Define break duration when transfer 

on Bypass

[10ms]

Overload  

prealarm

[10%] … [102%]

Load % when overload alarm occurs

[102%]

Redundancy 

mode

[Unitary UPS] [Hot Standby]

Force slew rate value to 0.5Hz/s

Unitary UPS

On/Off settings

Cold start

[Enabled] [Disabled]

Authorize the product to start on  

battery power.

[Enabled]

Forced reboot

[Enabled] [Disabled]

If mains recover during a shutdown 

sequence:

If set to Enabled, shutdown sequence 

will complete and wait 10 seconds 

prior to restart,

If set to Disabled, shutdown 

sequence will not complete and 

restart will occur immediately.

[Enabled]

Auto restart

[Enabled] [Disabled]

Authorize the product to restart  

automatically when mains recovers 

after a complete battery discharge.

[Enabled]

Auto start

[Enabled] [Disabled]

The UPS automatically starts up as 

soon as mains power is available  
(no need topress the 

 button).

[Disabled]

Energy saving

[Disabled] [100W] … [1000W] 

If Enabled, UPS will shutdown after  

5 min. of back-up time, if load is less 

than threshold.

[Disabled]

Sleep mode

[Enabled] [Disabled]

If Disabled, LCD and communication 

will turn OFF immediately after UPS 

is OFF. 

If Enabled, LCD and communication 

stays ON 1h30 min after UPS is OFF.

[Enabled]

Remote command

[Enabled] [Disabled]

If Enabled, shutdown or restart  

commands from software are  

authorized.

[Enabled]

Bypass standby

[Enabled] [Disabled]

Define if output is powered from 

Bypass in Standby mode.

[Enabled] 

Battery settings

Automatic battery 

test

In constant charge mode:

[No test] [Every day] [Every week] 

[Every month] 

In ABM cycling mode :

[No test] [Every ABM cycle]

[Every ABM cycle]

Low battery  

warning

[0%] ... [100%] 

The alarm triggers when the set  

percentage of battery capacity is 

reached during back-up time.

[20%]

Restart bat. level

[0%] ... [100%] 

If set, automatic restart will occur 

only when percentage of battery 

charge is reached.

[0%]

Battery charge 

mode

[ABM cycling] [Constant charge]

[ABM cycling]

External battery

[Auto detection]

[Manual EBM set.]

[Manual battery set.]

[No battery]

[Auto detection]

Using standard EBM, UPS 

detects automatically the  

number of EBM connected

Deep Disch.  

protect.

[Yes] [No]  

If set to Yes, the UPS automatically 

prevents battery from deep discharge 

by adapting end of back-up time  

voltage threshold. 

Warranty void if set to No.

[Yes]

Summary of Contents for 9PX EBM 240V

Page 1: ...9SX 8000 9SX 11000 9PX 8000 9PX 11000 9SX EBM 240V 9PX EBM 240V Installation and user manual Copyright 2012 EATON All rights reserved Service and support Call your local service representative 8 11kV...

Page 2: ...Page 2 8 11kVA EU_EN...

Page 3: ...Certification standards Safety IEC EN 62040 1 Ed 1 2008 p UL 1778 4th edition EMC IEC EN 62040 2 Ed 2 2006 p FCC part 15 Class A Performance IEC EN 62040 3 Ed 2 0 2011 p IEC 61000 4 2 ESD level 3 p IE...

Page 4: ...h the National Electric Code ANSI NFPA 70 US installations only The upstream circuit breaker must be easily accessible The unit can be disconnected from AC power source by opening this circuit breaker...

Page 5: ...sources connection 24 4 3 Separate input source connection 25 4 4 Frequency converter connection 25 5 Operation 26 5 1 UPS startup and shutdown 26 5 2 Operating modes 27 5 3 Transferring the UPS betw...

Page 6: ...se comprises over 50 of recycled cardboard p Sacks and bags are made of polyethylene p Packing materials are recyclable and bear the appropriate identification symbol p 01 PET Materials Abbreviations...

Page 7: ...f your equipment Providing outstanding performance and reliability the Eaton 9SX and 9PX s unique benefits include True online double conversion technology with high power density utility frequency in...

Page 8: ...kg Dimensions inch mm D x W x H 9SX 8000 Power Module 42 19 27 6 x 17 3 x 5 1 700 x 440 x 130 9SX 11000 Power Module 46 21 27 6 x 17 3 x 5 1 700 x 440 x 130 9PX 8000 Power Module 42 19 27 6 x 17 3 x...

Page 9: ...ion port 4 Connector for ROO Remote On Off control 5 Connectors for automatic recognition of battery module 6 Connector for Parallel operation for 9PX only 7 Connector for RPO Remote Power Off control...

Page 10: ...1Ki 8 2 6 4 3 5 1 7 1 Input Output terminal blocks 2 Input Output cables for connection to the UPS 3 Bypass terminal blocks for connection to the UPS 4 Normal AC source switch 5 Bypass AC source switc...

Page 11: ...BM 50 5 0kW 5 5kVA Efficiency 95 Escape Up Down Enter On Off button Battery mode indicator orange Bypass mode indicator orange The following table shows the indicator status and description Indicator...

Page 12: ...operating normally The UPS is powering and protecting the equipment Battery mode 1 beep every 10 seconds A utility failure has occured and the UPS is on Battery mode The UPS is powering the equipment...

Page 13: ...ults stored Reset fault list Clears faults Identification Product type model Part Serial number UPS NMC firmware Com card IPv4 Com card IPv6 Com card MAC Detected accessories Register product Links to...

Page 14: ...after 5 min of back up time if load is less than threshold Disabled Sleep mode Enabled Disabled If Disabled LCD and communication will turn OFF immediately after UPS is OFF If Enabled LCD and communi...

Page 15: ...king the cabinet Unpacking the cabinet in a low temperature environment may cause condensation to occur z in and on the cabinet Do not install the cabinet until the inside and outside of the cabinet a...

Page 16: ...nstructions 9 Software CD ROM If you ordered an optional Extended Battery Module EBM verify that the following additional items are included z with the EBM 3 4 2 1 1 Battery power cable attached with...

Page 17: ...nd firmly 1 Plug the EBM power cable s into the battery connector s Up to 12 EBMs may be connected to the UPS 2 Verify that the EBM connections are tight and that adequate bend radius and strain relie...

Page 18: ...the LCD panel p If you ordered other UPS accessories refer to specific user manuals to check the tower installation with the UPS To install the cabinet 1 Place the UPS on a flat stable surface in its...

Page 19: ...move the center cover of the front panel 2 Remove the four screws to open the front panel 3 Remove the three screws to pull out the metal protection cover of the battery 4 Pull out the plastic handle...

Page 20: ...20 8 11kVA EU_EN Rack mounting of UPS EBM and accessory modules p Follow steps 1 to 4 for module mounting on the rails 1 1 3 4 4 3 2 The rails and necessary hardware are supplied by EATON 3 Installat...

Page 21: ...ker 8000VA D curve 50A 11000VA D curve 63A 2 poles circuit breaker G N L2 L1 N L2 L1 to UPS Normal AC source 2 Recommended cable cross sections Terminal position Wire function Terminal wire size ratin...

Page 22: ...d 8 10 11 z UPS with separate Normal and Bypass AC inputs 8 10 11 Bypass AC Normal AC Load Main low voltage switchboard MLVS Isolation transformer Change in SEA between upstream and downstream or galv...

Page 23: ...and downstream or galvanic isolation required 8 10 11 Bypass AC Normal AC Load MLVS1 MLVS2 Isolation transformer z Frequency converter without Bypass AC input Configuration used when the frequency of...

Page 24: ...es Normal AC source and Bypass AC source are open O Off Always connect the ground wire first If you ordered a HotSwap MBP refer to the specific user manual to check the terminal blocks connection of t...

Page 25: ...o the Bypass AC source terminal blocks 6 Insert the Output cable through the cable gland 7 Connect the three cables to the Output terminal blocks 8 Put back and secure the terminal blocks cover with t...

Page 26: ...larms and restart if necessary 7 Verify that the indicator illuminates solid indicating that the UPS is operating normally and powering the output The UPS should be in Online mode The EBM charge to 90...

Page 27: ...mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available and your equipment is not protected however the utility power c...

Page 28: ...ing on output mode If Disabled the UPS output is shutdown Interrupt time This setting is displayed to define the break duration during transfer to Bypass only if transfer out of tolerance is enabled 1...

Page 29: ...ugh the display 1 Press any button to activate the menu options then select Event log 2 Scroll through the listed events 5 8 Retrieving the Fault log To retrieve the Fault log through the display 1 Pr...

Page 30: ...tected Pin 3 not low battery Pin 4 not on Battery Pin 5 user common Pin 6 on Bypass Pin 7 low battery Pin 8 load protected Pin 9 on Battery n o contact normally open n c contact normally closed The re...

Page 31: ...age SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation The RPO must not be connected to any utility connected circuits Reinforced insulation to th...

Page 32: ...avoid accidental load loss z Connectivity Cards Connectivity cards allow the UPS to communicate in a variety of networking environments and with different types of devices The 9SX and 9PX models have...

Page 33: ...wer Software suite Each 9SX and 9PX UPS ships with Eaton Intelligent Power Software suite To begin installing see the instructions accompanying the Software suite CD Eaton Software suite provides up t...

Page 34: ...untimes Replace batteries at least every 4 years to keep units running at peak efficiency 7 2 Storing the equipment If you store the equipment for a long period recharge the battery every 6 months by...

Page 35: ...lacing batteries replace with the same type and number of batteries or battery packs z Contact your service representative to order new batteries Proper disposal of batteries is required Refer to your...

Page 36: ...Plug the EBM cable s into the battery connector s Up to twelve EBMs may be connected to the UPS 4 Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for ea...

Page 37: ...UPS 4 Select Control then Go to Bypass 5 Turn the HotSwap MBP switch to the Normal position the red LED on the HotSwap MBP goes Off indicating that the load is now powered by the UPS Bypass LED shoul...

Page 38: ...utility failure has occurred and the UPS is in Battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery low The UPS is in Battery mode and the bat...

Page 39: ...n to normal operation when the temperature drops 5 C below the warning level If the condition persists shut down the UPS Clear vents and remove any heat sources Allow the UPS to cool Ensure the airflo...

Page 40: ...Model number z Serial number z Firmware version number z Date of failure or problem z Symptoms of failure or problem z Customer return address and contact information z If repair is required you will...

Page 41: ...M 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 9PX11KiPM 700 x 440 x 130 27 6 x 17 3 x 5 1 46 21 Model EBM Dimensions D x W x H mm inch Weight lb kg 9SXEBM240 680 x 440 x 130 26 8 x 17 3 x 5 1 128 58 9PXEB...

Page 42: ...rm 125 150 UPS shuts down after 1 minute 150 UPS shuts down after 1s Voltage waveform Sinewave Harmonic distortion 2 THDV on linear load 5 THDV on non linear load Transfer time Online mode 0 ms no bre...

Page 43: ...r configuration 9SXEBM240 240Vdc 20 x 12V 7Ah 9PXEBM240 240Vdc 20 x 12V 9Ah Fuses 63A for 8kVA models 80A for 11kVA models and EBM Type Sealed maintenance free valve regulated lead acid with minimum 3...

Page 44: ...ttery power Load Devices or equipment connected to the UPS output HE mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user This...

Reviews: