UPS Operating Instructions
6-12
Eaton 9E UPS (20–30 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000301—Rev 1
www.eaton.com/powerquality
17. If requested, enter the Level 1 password. Default password is 1111.
The rectifier and inverter turn on. The inverter continues to ramp up to full voltage.
Once the inverter reaches full voltage, the UPS inverter switchgear closes and the static switch turns off.
Power is now supplied to the critical load in HE Normal mode. It takes approximately one minute for the
UPS to achieve HE Normal mode.
The Normal status indicator is illuminated.
18. If an ITC with an input and output transformer is installed, close the output breaker.
6.3.2
Starting the UPS in Bypass Mode
If the inverter output of the UPS is not available and the critical load needs to be energized:
CAUTION
In Bypass mode, the critical load is not protected from commercial power interruptions and
abnormalities.
1.
Unfasten the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open (Figure 6-1).
2.
Verify that the input breaker is open.
3.
If the UPS is EBC capable, verify that the UPS battery breaker is open.
4.
Close the UPS input feeder circuit breaker.
5.
If an ITC with an input transformer is installed, close the input and UPS input breakers.
6.
If an ITC with an input and output transformer is installed, close the input, UPS input, and UPS output
breakers.
7.
If the UPS is dual-feed, close the bypass input feeder circuit breaker.
8.
Close the input breaker.
9.
If the UPS is EBC capable, close the UPS battery breaker.
10. Close the door and secure the latch.
11. If EBCs are installed, close the EBC battery breakers.
12. Observe the UPS control panel display becoming active, indicating logic power.
13. Verify no alarms are active.
14. Select the
CONTROLS
symbol on the main menu bar. The System Control screen is displayed.
15. If not already selected, select UPS on the System Control screen.
16. On the UPS System Control screen, select the
LOAD OFF
BYPASS
command, then press the
RETURN
pushbutton.
The critical load is immediately supplied by the bypass source, in Bypass mode.
The
BYPASS
status indicator is illuminated.
17. If an ITC with an input and output transformer is installed, close the output breaker.
The critical load is immediately supplied by the bypass source, in Bypass mode.
NOTE
If two EBCs are installed, EBC 1 must be closed to supply DC input to the UPS. EBC
2 may be left open, but battery runtime will be reduced.
Summary of Contents for 9E
Page 1: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Page 2: ......
Page 3: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Page 21: ...Section 1 Installation ...
Page 22: ......
Page 65: ...Section 2 Operation ...
Page 66: ......
Page 113: ......
Page 114: ... P 164000301 1 P 164000301 1 ...