Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 09
Table 10. External Critical Load Output Power Cable Terminations for the Eaton 93PM IAC-D
Terminal
Function
Breaker
Rating
Terminal
Function
Number and Size
of Pressure
Termination
(AWG or kcmil)
Tightening Torque
Nm (lb in)
Type and
Size Screw
AC Output
from Distribution
Panel
Breakers to Critical
Load
N/A
N
Neutral
64 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
22 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
N/A
G
Ground
32 – #6–#14
#6–#8:
#10–#14:
2.8 (25)
1.7 (15)
Slotted
11 – 1/0
#4–#6:
#8:
#10–#14:
5.0 (45)
4.5 (40)
4.0 (35)
AC Output from
Subfeed
Breaker Terminal
Block
to Critical Load
N/A
A
Phase A
1 – #6–500
20 (177)
1/2” Hex
B
Phase B
1 – #6–500
20 (177)
1/2” Hex
C
Phase C
1 – #6–500
20 (177)
1/2” Hex
N
Neutral
2 – #6–300
31 (275)
5/16” Hex
G
Ground
10 – #14–1/0
5.6 (50)
Slotted
AC Output from
Optional Single
Subfeed Breaker
Terminal Block
to Critical Load
(150 kW and
200 kW only)
N/A
A
Phase A
2 – #6–300
31 (275)
5/16” Hex
B
Phase B
2 – #6–300
31 (275)
5/16” Hex
C
Phase C
2 – #6–300
31 (275)
5/16” Hex
N
Neutral
2 – #6–300
31 (275)
5/16” Hex
G
Ground
2 – #14–1/0
5.6 (50)
Slotted
AC Output
from Output
Breaker
to Critical Load
“K” Frame
175A
(50 kW
IAC-D)
XOB-2
Phase A
1 – #3–350
31 (275)
5/16” Hex
XOB-4
Phase B
1 – #3–350
31 (275)
5/16” Hex
XOB-6
Phase C
1 – #3–350
31 (275)
5/16” Hex
N
Neutral
4 – #6–300
31 (275)
5/16” Hex
“LG” Frame
350A
(100 kW
IAC-D)
XOB-2
Phase A
2 – #2–500
42 (372)
5/16” Hex
XOB-4
Phase B
2 – #2–500
42 (372)
5/16” Hex
XOB-6
Phase C
2 – #2–500
42 (372)
5/16” Hex
N
Neutral
4 – #6–300
31 (275)
5/16” Hex
“LG” Frame
600A
(150 kW
IAC-D)
XOB-A
Phase A
4 – 2 bolt mounting
35 (310)
M12 Hex
XOB-B
Phase B
4 – 2 bolt mounting
35 (310)
M12 Hex
XOB-C
Phase C
4 – 2 bolt mounting
35 (310)
M12 Hex
N
Neutral
4 – 2 bolt mounting
35 (310)
M12 Hex