Eaton 93PM Emergency Lighting UPS (50 kW, 480V Three and Four-Wire UL 924) Installation and Operation Manual P-164000569—Rev 03
43
Figure 23. Wire Tie Anchors
Wire Tie Anchors
Table 10. Building Alarm Connections and Wire Terminations
Terminal
Name
Description
Recommended
Wire Size
Size of
Pressure
Termination
Tightening
Torque
10
Building Alarm 1
Input: Programmable UPS
alarm, activated by a
remote dry contact closure
Twisted Pair
Wires #18 AWG
#14-#30 AWG
2 lb in
(0.22-0.25 Nm)
9
Building Alarm 1
Return
8
Building Alarm 2
Input: Programmable UPS
alarm, activated by a
remote dry contact closure
7
Building Alarm 2
Return
6
Building Alarm 3
Input: Programmable UPS
alarm, activated by a
remote dry contact closure
5
Building Alarm 3
Return
4
Building Alarm 4
Input: Programmable UPS
alarm, activated by a
remote dry contact closure
3
Building Alarm 4
Return
2
Building Alarm 5
Input: Programmable UPS
alarm, activated by a
remote dry contact closure
1
Building Alarm 5
Return