Installation Plan and Unpacking
3-10
Eaton 93E Integrated Accessory Cabinet-Distribution (30IAC-D and 60IAC-D) Installation and Operation Manual P-164000072—Rev 2
www.eaton.com/powerquality
For external power wiring requirements, including the minimum AWG size of external wiring, see Table 3-3.
Wire sizes listed are for copper wiring only.
The power wiring terminals are pressure terminations, UL and CSA rated at 90°C. See Table 3-4 for external
input power cable terminations and Table 3-5 for external output power cable terminations.
Figure 4-11 and Figure 4-12 show the IAC-D input power terminal locations and detail.
Table 3-3. External Power Wiring Requirements for the Eaton 93E 30IAC-D and 60IAC-D
Basic Unit Rating
Units
Rating 60 Hz
kVA
30
60
Input/Output Voltage
Volts
208Y/120
208Y/120
AC Input to IAC-D
(3) Phases, (1) Neutral, (1) Ground
A
Maximum Amps
167
334
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil [CSA – mm2]
(each)
1/0 [143]
(2)
250 [297]
(2)
Minimum Conductor Size (Neutral)
Number per Phase
—
AWG or kcmil [CSA – mm2]
(each)
1/0 [143]
(4)
250 [297]
(4)
Minimum Conductor Size (Ground)
Number per Phase
—
AWG or kcmil [CSA – mm2]
(each)
#4 [63]
(1)
#2 [86]
(1)
AC Output
Maximum Amps
167
334
AC Output from Distribution Panel
Breakers to the Critical Load
B
Wire branch circuits in accordance with branch circuit breaker manufacturer's ratings
and instructions, power cable termination sizes listed in Table 3-5, and national and
local electrical codes (input is prewired to the panelboard).
Maximum output ratings are to be in accordance with the rating label on the IAC-D. The
total combined load is not to exceed the maximum output rating.
AC Output from Subfeed Breakers to the
Critical Load
(3) Phases, (1) Neutral, (1) Ground
B
Wire branch circuits in accordance with branch circuit breaker manufacturer's ratings,
power cable termination sizes listed in Table 3-5, and national and local electrical
codes.
Maximum output ratings are to be in accordance with the rating label on the IAC-D. The
total combined load is not to exceed the maximum output rating.
NOTE
Callout letters
A
and
B
map to Figure 5-1
Table 3-4. External Input Power Cable Terminations for the Eaton 93E 30IAC-D and 60IAC-D
Terminal Function
kVA
Rating
Terminal
Function
Number and Size of Pressure
Termination
(AWG or kcmi)
Tightening Torque
Nm (lb in)
Type and Size Screw
AC Input to
IAC-D
30
A
Phase A
2 – #6–250
31 (275)
5/16” Hex
B
Phase B
2 – #6–250
31 (275)
5/16” Hex
C
Phase C
2 – #6–250
31 (275)
5/16” Hex
N
Neutral
4 – #2–600
56.5 (500)
1/2” Hex
G
Ground
2 – #14–1/0
5.6 (50)
Slotted
60
A
Phase A
2 – #6–250
31 (275)
5/16” Hex
B
Phase B
2 – #6–250
31 (275)
5/16” Hex
C
Phase C
2 – #6–250
31 (275)
5/16” Hex
N
Neutral
4 – #2–600
56.5 (500)
1/2” Hex
G
Ground
2 – #14–1/0
5.6 (50)
Slotted