background image

UPS OPERATING INSTRUCTIONS

Eaton

®

9390 UPS (20–80 kVA) and 9390IT (20-40 kVA) Installation and Operation Manual  

S

  164201603 Rev 4

 www.eaton.com/powerquality

9-9

9.1.16

Transfer from Normal to Bypass Mode and Shut Down UPS

To transfer the critical load to Bypass mode and shut down the UPS:

1.

Transfer the critical load to bypass by performing the procedure in
paragraph 9.1.4.

2.

Press the 

CONTROLS

 pushbutton on the main menu bar. The System Control

screen appears.

3.

Press the   pushbutton to display System Controls Screen 2.

4.

Press the 

PM OFF

 pushbutton on the System Controls menu bar.

The power module (PM) status indicates SHUTDOWN

The input and output

contactors open, the battery breaker or disconnect is tripped, and the power
module is turned off. The bypass source supplies the critical load.

W

 

A

 

R

 

N

 

I

 

N

 

G

Power is present inside the UPS cabinets.

9.1.17

UPS and Critical Load Shutdown

To perform maintenance or service on the critical load, shut down power to the load
by performing the following procedure:

1.

Turn off all equipment that is being powered by the UPS.

2.

Perform the LOAD OFF procedure in paragraph 9.1.19.

The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off.

W

 

A

 

R

 

N

 

I

 

N

 

G

Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.

3.

Open the UPS input and bypass (if dual feed) feeder circuit breakers.

9.1.18

Charger Control

To turn the battery charger on or off:

1.

Press the 

CONTROLS

 pushbutton on the main menu bar. The System Control

screen appears.

2.

Press the   pushbutton to display System Controls Screen 2.

3.

Press the 

CHGR ON

 or 

CHGR OFF

 pushbutton on the System Controls menu bar to

toggle the charger on or off.

Summary of Contents for 9390IT

Page 1: ...Powerware Series Eaton 9390 9390IT UPS 20 80 kVA Installation and Operation Manual For 9390IT 20 40 kVA and 9390 20 80 kVA UPS models...

Page 2: ......

Page 3: ...Powerware Series Eaton 9390 9390IT UPS 20 80 kVA Installation and Operation Manual For 9390IT 20 40 kVA and 9390 20 80 kVA UPS models...

Page 4: ...es uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipmen...

Page 5: ...is symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact...

Page 6: ...This page intentionally left blank...

Page 7: ...I 1 5 1 2 8 Relay Interface Module II 1 5 1 2 9 Supervisory Contact Module II 1 5 1 2 10 Energy Saver and High Alert Modes 1 5 1 3 Basic System Configurations 1 6 1 4 Conventions Used in This Manual 1...

Page 8: ...rvisory Contact Module II 6 6 Section II Operation 7 Understanding UPS Operation 7 1 7 1 Single Module Reverse Transfer RT 7 2 7 1 1 Single Module RT Modes 7 2 7 1 2 Normal Mode RT 7 3 7 1 3 Bypass Mo...

Page 9: ...9 8 9 1 15 Transfer from High Alert to Energy Saver Mode 9 8 9 1 16 Transfer from Normal to Bypass Mode and Shut Down UPS 9 9 9 1 17 UPS and Critical Load Shutdown 9 9 9 1 18 Charger Control 9 9 9 1...

Page 10: ...2 Monthly Maintenance 13 2 13 2 3 Annual Maintenance 13 2 13 2 4 Battery Maintenance 13 3 13 3 Recycling the Used Battery or UPS 13 3 13 4 Maintenance Training 13 3 14 Product Specifications 14 1 14...

Page 11: ...7 7 Path of Current through the UPMs in Bypass Mode Parallel 7 11 Figure 7 8 Path of Current through the UPMs in Battery Mode Parallel 7 13 Figure 8 1 UPS Control Panel 8 1 Figure 8 2 Parts of the LCD...

Page 12: ...1 Unit Type Screen 8 31 Figure 8 42 Enter Password Screen 8 31 Figure 8 43 System Setup Level 1 Screen 8 32 Figure 8 44 Change Password Screen 8 33 Figure 8 45 Change Password Save Screen 8 33 Figure...

Page 13: ...on equipment due to unexpected power problems The Eaton 9390 9390 UPS continually monitors incoming electrical power and removes the surges spikes sags and other irregularities that are inherent in co...

Page 14: ...390IT configuration is not available with NiCad batteries The 9390IT UPS functions the same as the 9390 UPS 20 40 kVA models It can be paralleled with another UPS for redundancy Battery Compartment Fi...

Page 15: ...monitoring through a Web browser interface e mail and a network management system NMS using SNMP See Chapter 12 Communication for additional information 1 1 6 ABM Technology ABM technology is a three...

Page 16: ...binet designed for line up and match installation but may be installed separate from the UPS cabinet 1 2 3 Integrated Accessory Cabinets IAC B IAC T and IAC D The following Integrated Accessory Cabine...

Page 17: ...uses relay contact closures to indicate the operating status and alarm condition of the UPS This option is described further in Chapter 10 Using Features and Options 1 2 9 Supervisory Contact Module...

Page 18: ...allel system with three UPS modules one to four battery cabinets for each UPS and an optional module tie cabinet Two capacity one redundant 2 1 Three capacity 3 0 S Powerware Hot Sync parallel system...

Page 19: ...nual for the following additional information S Integrated Battery Cabinet IBC installation instructions including site preparation planning for installation wiring and safety information S Detailed i...

Page 20: ...help with any of the following S Scheduling initial startup S Regional locations and telephone numbers S A question about any of the information in this manual S A question this manual does not answer...

Page 21: ...ty controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum The system is not intended fo...

Page 22: ...r disposal requirements S Never dispose of batteries in a fire Batteries may explode when exposed to flame S Keep the UPS door closed and front panels installed to ensure proper cooling airflow and to...

Page 23: ...Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 2 1 Section I Installation...

Page 24: ...Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 2 2...

Page 25: ...ng installed Use the procedures and illustrations in the following chapters to create a logical plan for installing the system 3 2 Preparing the Site For the UPS system to operate at peak efficiency t...

Page 26: ...m AWG size of external wiring see Table H through Table J starting on page A 15 The power wiring connections for this equipment are rated at 90 C If wire is run in an ambient temperature greater than...

Page 27: ...ack the cabinet 1 Carefully inspect the outer packaging for evidence of damage during transit 2 Use a forklift or pallet jack to move the packaged cabinet to the installation site or as close as possi...

Page 28: ...damage and compare each item with the Bill of Lading If damage has occurred or shortages are evident contact your Eaton service representative immediately to determine the extent of the damage and its...

Page 29: ...dels only When a line up and match UPS system is ordered together with battery cabinets the first battery cabinet is supplied with two cosmetic covers The UPS cabinet additional battery cabinets and o...

Page 30: ...e 4 1 Remove the front anti tip shipping bracket Retain the front anti tip shipping bracket and securing hardware for later use Do not discard the front anti tip shipping bracket This bracket is requi...

Page 31: ...TE Do not discard the front anti tip shipping bracket This bracket is required for installation Lower Shipping Bracket Bolts 2 Front View Vented Front Door Upper Shipping Bracket Bolts 3 Front Anti ti...

Page 32: ...90 UPS NOTE In the following step the pallet tilts and acts as a ramp once the cabinet is rolled beyond the center of the pallet Be sure to restrain the cabinet as it continues to roll down the pallet...

Page 33: ...15 Using the retained hardware reinstall the shipping brackets removed in Step 5 to the front and rear of the UPS cabinet with the angle facing outward see Figure 4 1 and Figure 4 2 16 Secure the cabi...

Page 34: ...ring the rear shipping bracket to the cabinet and two bolts securing the bracket to the pallet see Figure 4 4 on page 4 8 Remove the rear shipping bracket If installing the cabinet permanently retain...

Page 35: ...Shipping Bracket Bolts 2 Front View Vented Front Door Upper Shipping Bracket Bolts 3 Front Anti tip Shipping Bracket note wide base Pallet Long Angle Shipping Bracket Removable Skid Bolts 4 Removable...

Page 36: ...Operation Manual S 164201603 Rev 4 www eaton com powerquality 4 8 Rear Shipping Bracket Removable Skid Rear View Lower Shipping Bracket Bolts 2 Upper Shipping Bracket Bolts 3 Pallet Wooden Mounting G...

Page 37: ...tip shipping brackets must be reinstalled otherwise injury to personnel and damage to the UPS may result when removing components during service If the brackets are not reinstalled the cabinet may tip...

Page 38: ...ore operating the UPS Once the debris shield is removed do not place objects on the ventilation grill NOTE Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit holes se...

Page 39: ...s in the bottom conduit plate prior to mounting on the UPS Install the conduit plate and install all conduit runs into the plate Pull wiring through the conduit into the UPS wiring area 8 Route the in...

Page 40: ...3 22 Connect phase A B and C and Neutral if required power wiring from the output and neutral terminals to the critical load See Appendix A for wiring and termination requirements and wiring access in...

Page 41: ...locks and the top conduit landing plate see Drawing 164201603 10 starting on page A 46 Retain the hardware for later use 6 If installing interface wiring from the bottom of the cabinet proceed to Step...

Page 42: ...4201603 10 starting on page A 46 7 If battery cabinets are installed attached to the UPS cabinet proceed to Step 8 if battery cabinets are installed separated from the UPS cabinet proceed to Step 11 8...

Page 43: ...e X Slot communication bay For installation and setup of an X Slot card please contact Eaton see page 1 8 To install wiring for connections 1 If not already installed install the LAN and telephone dro...

Page 44: ...the Installation Checklist The final step in installing the UPS system is completing the following installation checklist This checklist ensures that you have completely installed all hardware cables...

Page 45: ...talled Air conditioning equipment is installed and operating correctly The area around the installed UPS system is clean and dust free Eaton recommends that the UPS be installed on a level floor suita...

Page 46: ...sized and terminated The bypass source feeding the optional bypass of the parallel tie cabinet and the UPMs is from the same source of supply and is a four wire wye configuration Neutral conductors a...

Page 47: ...________________________________ _________________________________________________________________________ _________________________________________________________________________ ___________________...

Page 48: ...INSTALLING THE UPS SYSTEM Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 4 20 This page intentionally left blank...

Page 49: ...install a REPO station 1 Verify that the UPS system is turned off and all power sources are removed See Chapter 9 UPS Operating Instructions for shutdown instructions 2 Securely mount the REPO station...

Page 50: ...iring from the second contact block in the REPO station to trip circuitry of other equipment such as upstream protective devices facility monitoring devices or alarms Using the contact block that was...

Page 51: ...a Relay Interface Module II or a Supervisory Contact Module II to the UPS Plug in Terminal Block J3 Figure 6 1 Powerware Hot Sync CAN Bridge Card NOTE Only one Powerware Hot Sync CAN Bridge Card can...

Page 52: ...emove the retaining screws located inside each door at the top and bottom hinge pivot points then lift the door off Retain the hardware for later use 4 Remove the screws securing the control panel doo...

Page 53: ...w wall secure the enclosure to a wood or metal stud within the wall Do not use hollow wall anchors 3 Securely mount the RMP II at the desired location See drawing 164201603 14 on page A 69 for mountin...

Page 54: ...s for shutdown instructions 2 Perform the procedure listed in paragraph 6 1 NOTE If mounting to a hollow wall secure the enclosure to a wood or metal stud within the wall Do not use hollow wall anchor...

Page 55: ...page A 70 You can order interface cables separately for connecting to the 15 Pin D Sub Connectors Table 6 1 J1 through J4 Interface Connectors Status J1 through J4 Description UPS AVAILABLE Pins 1 an...

Page 56: ...OTE Remove the UPS cabinet top or bottom conduit landing plate to drill or punch conduit holes see Drawing 164201603 7 on page A 36 4 Remove the X Slot conduit landing plate from the UPS cabinet to dr...

Page 57: ...6 2 for terminal assignments and Drawing 164201603 10 on page A 46 for terminal block location System Normal No Redundancy On Generator Bypass Not Available On Battery UPS Alarm On Bypass Shutdown Imm...

Page 58: ...INSTALLING OPTIONS AND ACCESSORIES Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 6 8...

Page 59: ...Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 6 9 Section II Operation...

Page 60: ...Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 6 10...

Page 61: ...gic In this manual the power required by your equipment is called the critical load The UPS supplies the critical load with conditioned power that is synchronized with your utility power Figure 7 1 sh...

Page 62: ...The standard operation modes are S Normal mode The critical load is supplied by the inverter which derives its power from rectified utility AC power In this mode the battery charger also provides cha...

Page 63: ...he system is derived from a utility input source through the rectifier input contactor K1 The front panel displays Normal indicating the incoming power is within voltage and frequency acceptance windo...

Page 64: ...ort the critical load without interruption When utility power returns the UPS returns to Normal mode If the UPS becomes overloaded or unavailable the UPS switches to Bypass mode The UPS automatically...

Page 65: ...to bypass and provides upstream protection The backfeed protection contactor is opened preventing system output voltage from bleeding across the static switch snubber components to the bypass input s...

Page 66: ...aver mode K5 Rectifier Inverter K1 K3 Battery Converter Battery Battery Breaker Main Power Flow Trickle Current Energized De Energized Closed Open Breakers Contactors K5 Rectifier Inverter K1 K3 Batte...

Page 67: ...t interruption If bypass is common with the rectifier input the backfeed protection contactor K5 also opens The opening of contactors K1 and K5 prevent system voltages from bleeding backwards through...

Page 68: ...erruptible power modules UPMs Multiple UPMs are connected with their outputs in parallel tied together to provide a load level greater than the rating of one UPM and or for redundancy The paralleled U...

Page 69: ...thout operator intervention except when manually switching to Bypass mode The sophisticated detection and switching logic inside the UPMs ensures that operating mode changes are automatic and transpar...

Page 70: ...en operating in Normal mode Main Power Flow UPM 1 UPM 2 UPM 3 UPM 4 Output to Critical Load Battery UPM Input Module Tie Cabinet UPM 1 Output Bypass Input UPM 2 Output UPM 3 Output UPM 4 Output Batter...

Page 71: ...he path of electrical power through the parallel system when operating in Bypass mode Main Power Flow UPM 1 UPM 2 UPM 3 UPM 4 Output to Critical Load Battery UPM Input Module Tie Cabinet UPM 1 Output...

Page 72: ...em locks the critical load to the bypass source and requires operator intervention to transfer Bypass mode is a normal operating mode not an alarm condition However if the parallel system is unable to...

Page 73: ...ual indicator lamp on the front panel System Normal On Battery and create an entry into the alarm event history As the battery discharges the boost converter and inverter constantly make minute adjust...

Page 74: ...frequency PWM IGBT based power conversion stage that continuously supplies the critical load with high quality AC power The IGBTs are modulated to maintain the highest efficiency 7 3 3 Battery Charge...

Page 75: ...battery discharge time of 20 seconds S Battery voltage is under the opportunity charge level of 2 1 volts cell and the cabinet has been in rest mode for longer than 240 hours S An XCP command Initiate...

Page 76: ...UNDERSTANDING UPS OPERATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 7 16 This page intentionally left blank...

Page 77: ...2 PRESS ANY KEY TO CONTINUE Figure 8 1 UPS Control Panel The control panel consists of the following S A liquid crystal display LCD 1 S A horizontal row of pushbutton switches 2 S A vertical column of...

Page 78: ...message For more information about alarms and notices see Chapter 11 Responding to System Events B The information area contains data about UPS status and operations C The menu bar lists the titles of...

Page 79: ...ew the firmware version numbers LOAD OFF De energizes the critical load and powers down the UPS Returns to Main Menu and Mimic screen from the Events Meters Controls or Setup screens Returns to the ma...

Page 80: ...ystem events that are currently active The most recent event is listed first As events clear they are removed from the Active System Events listing Figure 8 4 shows the Active Events screen To scroll...

Page 81: ...following groups S User and service status S User instruction S User alarm S Check UPS S Schedule service S UPS shutdown S Service alarm The end of the log the most recent events appears when you dis...

Page 82: ...10 show the Unit Meter screens To scroll through the meter screens press the or pushbuttons on the menu bar The current UPS readings are displayed in the information area of the screen NOTE The UNIT...

Page 83: ...oming utility source as well as the kVA kW and power factor measurements INPUT UNIT V1 V2 V3 KVA KW PF I1 I2 I3 FREQ LEAD UNIT SYSTEM Figure 8 7 Unit Input Meter Screen The Bypass screen shows the byp...

Page 84: ...rature must be set up by an authorized Eaton Customer Service Engineer When battery life decreases to less than 20 Check Battery is displayed VDC IDC TIME REMAINING V A MINUTES BATTERY UNIT UNIT SYSTE...

Page 85: ...attery discharge log collects information when the UPS is on battery The Battery Discharge Log Summary screen displays the total number of times since the last log reset that the UPS has transferred t...

Page 86: ...occurred and the end voltage of the battery for that discharge period If no events have occurred the screen will display LOG EMPTY Figure 8 12 shows the Battery Discharge Log screen To scroll through...

Page 87: ...ays the number of total times the limit has been exceeded since the last log reset the date of the last log reset the maximum kW reading and the total time over the limit It also displays the average...

Page 88: ...mber of total kWH used during the interval and the number of times over limit during the interval If no events have occurred the screen displays LOG EMPTY Figure 8 14 shows the kW Demand Log screen To...

Page 89: ...Setup screen 1 The Current kW Demand Log Setup screen 1 displays the current user defined log settings If no log settings are configured the screen will display KW LOG DISABLED Figure 8 15 shows the C...

Page 90: ...Setup screen can be used to set up or change the time interval and maximum level log settings Figure 8 16 shows the Current kW Demand Log Setup screen 2 Use the or pushbuttons to highlight the setup...

Page 91: ...change the character value Once the new value is entered press the DONE pushbutton The Time Interval Monitored Setup Save screen is displayed 0000 DONE TIME INTERVAL MONITORED SETUP Figure 8 17 Time I...

Page 92: ...pushbuttons to change the character value Once the new value is entered press the DONE pushbutton The Maximum Level kW Setup Save screen is displayed 0000 DONE MAXIMUM LEVEL KW SETUP Figure 8 19 Maxi...

Page 93: ...s a limit defined for each phase individually In the first case an event is logged if the average across the phases exceeds the defined limit within a given time period and in the second case an event...

Page 94: ...een will display LOG EMPTY Figure 8 22 and Figure 8 23 show the Maximum Current Log screens To scroll through the individual events press the or pushbuttons on the menu bar To return to the Maximum Cu...

Page 95: ...aximum Current Log Setup screen 1 displays the current user defined log settings If no log settings are configured the screen will display MAXIMUM CURRENT LOG DISABLED Figure 8 24 shows the Maximum Cu...

Page 96: ...time interval the maximum percent of load and the calculation method three phase average or individual phases log settings Figure 8 25 shows the Maximum Current Log Setup screen 2 Use the or pushbutto...

Page 97: ...change the character value Once the new value is entered press the DONE pushbutton The Time Interval Monitored Setup Save screen is displayed 0000 DONE TIME INTERVAL MONITORED SETUP Figure 8 26 Time I...

Page 98: ...ushbuttons to change the character value Once the new value is entered press the DONE pushbutton The Maximum of Full Load Setup Save screen is displayed 000 DONE MAXIMUM OF FULL LOAD SETUP Figure 8 28...

Page 99: ...e full load limit of the event being monitored to be changed Figure 8 30 shows the Calculation Method Setup screen Use the or pushbuttons to highlight the calculation method desired then press the SEL...

Page 100: ...ings from any UPS when a parallel system is installed Press the METERS pushbutton on the main menu bar to display the Unit Meter screens Press the SYSTEM pushbutton on the menu bar to display the Syst...

Page 101: ...and frequency being supplied by the UPS as well as the kVA kW and power factor measurements for the total system The displayed voltages and frequency are the highest measured value of all UPSs The di...

Page 102: ...selected UPS are displayed in the information area of the screen To return to the present Unit Meter screens press the UNIT pushbutton on the menu bar NOTE In the following figures X equals the unit...

Page 103: ...ell as the kVA kW and power factor measurements for the selected UPS INPUT UNIT X V1 V2 V3 KVA KW PF I1 I2 I3 FREQ LEAD UNIT SYSTEM Figure 8 34 Input Unit X Meter Screen The Bypass screen shows the by...

Page 104: ...set up by an authorized Eaton Customer Service Engineer When battery life decreases to less than 20 Check Battery is displayed VDC IDC TIME REMAINING V A MINUTES BATTERY UNIT X UNIT SYSTEM TEMPERATUR...

Page 105: ...ter a password to access Level 1 functions see paragraph 8 2 9 No password is necessary to access Level 0 functions S Set the screen contrast S Show the firmware versions installed S Identify the UPS...

Page 106: ...s saved the System Setup screen displays To return to the System Setup screen without saving the setting press the pushbutton CONTRAST ADJUST 70 SAVE Figure 8 39 Contrast Adjust Screen Select VERSIONS...

Page 107: ...RIAL 0000000000000000 0000000000000000 UNIT TYPE Figure 8 41 Unit Type Screen 8 2 9 System Setup Level 1 Screens A password is required to access the Level 1 functions To enter the password select ENT...

Page 108: ...the Level 0 functions are available Figure 8 43 shows the System Setup Level 1 screen Use the or pushbuttons to highlight the setup function screen desired then press the SELECT pushbutton to display...

Page 109: ...or pushbuttons to change the password character Once the new password is entered press the DONE pushbutton The Change Password Save screen is displayed NEW OLD L1 L1 CHANGE PASSWORD DONE Figure 8 44 C...

Page 110: ...etup screen allows the selection of either month day year or day month year formats for display on the screen and for logging events in the Event and History Logs Figure 8 46 shows the Time Format scr...

Page 111: ...and for logging events in the Event and History Logs Figure 8 47 shows the Set Date and Time MM DD YYYY screen Use the or pushbuttons to highlight the setting to be changed Use the or pushbuttons to m...

Page 112: ...and for logging events in the Event and History Logs Figure 8 48 shows the Set Date and Time DD MM YYYY screen Use the or pushbuttons to highlight the setting to be changed Use the or pushbuttons mak...

Page 113: ...Setup Level 1 menu to display the COM Port Setup screen This screen allows selection of the serial COM port to set up Figure 8 49 shows the COM Port Setup screen Use the or pushbuttons to highlight th...

Page 114: ...Port Setup screen displays If the changes are not wanted use the ABORT pushbutton to return to the COM Port Setup screen Figure 8 50 shows the COM Setup screen Use the or pushbuttons to highlight the...

Page 115: ...e UPS is in Maintenance Bypass or Bypass and the state of the power module PM and battery charger Figure 8 51 and Figure 8 52 show the System Controls screens Use the or pushbutton on the menu bar to...

Page 116: ...he amber BYPASS LED will be off and green NORMAL LED will be on solid SYSTEM CONTROLS LOAD OFF HI ALRT ENGY SVR MAINTENANCE BYPASS BYPASS POWER MODULE PM OFF OFF ENERGY SAVER CHARGER OFF Figure 8 54 S...

Page 117: ...stem Controls see Chapter 9 UPS Operating Instructions 8 4 Load Off Screen The Load Off screen appears when the LOAD OFF pushbutton is selected from the main menu bar or System Controls menu bar This...

Page 118: ...ndicators are illuminated The indicator continues to flash until acknowledged by pressing any control panel pushbutton once Battery This yellow indicator is illuminated when the UPS is operating in Ba...

Page 119: ...the UPS in Normal Mode NOTE When starting a 9390IT UPS with internal batteries remove the battery compartment access panel by loosening the wing nut at the bottom of the panel and lifting the panel of...

Page 120: ...r interruptions and abnormalities 1 Close the UPS input feeder circuit breaker 2 If the UPS is dual feed close the UPS Bypass input feeder circuit breaker 3 Observe the UPS control panel becoming acti...

Page 121: ...rs 2 Press the BYPASS pushbutton on the System Controls menu bar The UPS transfers to Bypass mode and the critical load is immediately supplied by the bypass source If the bypass source is not availab...

Page 122: ...ilable the power module remains on and an alarm sounds The NORMAL status indicator is illuminated The UPS status indicates ENERGY SAVER The Bypass status indicates ON The UPM status indicates ONLINE I...

Page 123: ...rs to Energy Saver mode and the critical load is immediately supplied by the bypass source If the bypass source is not available the power module remains on and an alarm sounds The NORMAL status indic...

Page 124: ...supplied by the bypass source The NORMAL status indicator is illuminated The UPS status indicates ENERGY SAVER The Bypass status indicates ON The UPM status indicates ONLINE If the battery is not cha...

Page 125: ...ource is not available the power module remains on and an alarm sounds The NORMAL status indicator is illuminated The UPS status indicates HIGH ALERT The UPM status indicates ONLINE The power module i...

Page 126: ...the power module remains on and an alarm sounds The NORMAL status indicator is illuminated The UPS status indicates HIGH ALERT The UPM status indicates ONLINE The power module is on 9 1 15 Transfer fr...

Page 127: ...lies the critical load WARNING Power is present inside the UPS cabinets 9 1 17 UPS and Critical Load Shutdown To perform maintenance or service on the critical load shut down power to the load by perf...

Page 128: ...OAD OFF from the Load Off menu bar and hold for three seconds To abort the shutdown press CANCEL When LOAD OFF is selected and held for three seconds the input output and bypass backfeed contactors op...

Page 129: ...er or disconnect is tripped and the power module is turned off immediately without asking for verification CAUTION DO NOT attempt to restart the system after Load Off until the cause of the shutdown h...

Page 130: ...pushbutton on the System Controls menu bar of any UPM If Auto Bypass is enabled the critical load is immediately supplied by the bypass source in Bypass mode until the inverters turn on and the UPMs t...

Page 131: ...ystem Controls menu bar of any UPM The critical load is immediately supplied by the bypass source in Bypass mode 7 The UPMs are now operating in Bypass mode and the BYPASS status indicator on each UPM...

Page 132: ...NOTE The UPM can be shut down only if remaining UPMs can support the critical load without being overloaded 1 Press the CONTROLS pushbutton on the main menu bar on the UPM to be shut down The System...

Page 133: ...te SHUTDOWN 7 Press the NORMAL pushbutton on the System Controls menu bar of the UPM 8 Observe the following messages appear sequentially on the power module PM status line of the UPM DC STARTING INVE...

Page 134: ...and then follow the procedure in paragraph 9 2 1 or 9 2 2 9 2 8 Using the UPS LOAD OFF Pushbutton NOTE The UPM LOAD OFF pushbutton controls only the UPM on which Load Off was activated and only inter...

Page 135: ...power to the critical load is lost when the REPO switch is activated in the following step You should use this feature only when you want to de energize the critical load NOTE The following instructio...

Page 136: ...To restart the UPS after using the REPO pushbutton follow the procedure in paragraph 9 1 1 or 9 1 2 NOTE Follow Lockout Tagout LOTO procedures for your location The key should not be stored in the swi...

Page 137: ...as smoke detectors or overtemperature alarms The customer interface terminals for external connections are located inside the UPS You should use twisted pair wires for each alarm input and common The...

Page 138: ...option a Remote Monitor Panel II RMP II can be installed to monitor the operation of the UPS system from virtually any location within the facility up to 152 4m 500 ft from the UPS The RMP II contains...

Page 139: ...utility power ON BYPASS The bypass source is supplying the critical load Usually this means that the UPS is not energized The load is not protected in Bypass mode and a horn sounds after 30 seconds U...

Page 140: ...s labeled J1 through J4 Figure 10 2 Relay Interface Module II The RIM II can provide the status and alarm signals shown in Table 10 2 Table 10 2 Customer Interface Connectors Status J1 through J4 Desc...

Page 141: ...m equipment The SCM II can be flush mounted or surface mounted on a desktop or secured to a wall Figure 10 3 shows the SCM II Figure 10 3 Supervisory Contact Module II The SCM II provides signals for...

Page 142: ...USING FEATURES AND OPTIONS Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 10 6 This page intentionally left blank...

Page 143: ...an operator that an event needing attention is taking place Horn 1 cycles at a one second rate 11 3 System Event Indicators The status indicators on the UPS control panel work in conjunction with the...

Page 144: ...ice Required Check Input Switchgear OK Off No 1 HA Condition Cleared Check Inv Temperature Sensor 1 No 1 HA Service Required Check Inv Temperature Sensor OK Off No 1 HA Condition Cleared Check Inverte...

Page 145: ...e Required Inverter Overtemperature OK Off No 1 HA Condition Cleared Inverter Overtemperature Trip 1 No 1 HA Service Required Inverter Overtemperature Trip OK Off No 1 HA Condition Cleared L1 Overload...

Page 146: ...verload 1 No 1 HA User Action Required Parallel System Overload OK Off No 1 HA Condition Cleared Rect Overtemperature Trip 1 No 1 HA Service Required Rect Overtemperature Trip OK Off No 1 HA Condition...

Page 147: ...pass Phase Rotation OK Off No No A Condition Cleared Bypass Source Out of Tolerance 1 No No HA Investigate UPS Bypass Source Out of Tolerance OK Off No No HA Condition Cleared Bypass Under or Over Fre...

Page 148: ...n Cleared Inverter Off Command 1 No No A Information Only Inverter On Command 1 No No HA Information Only Inverter Output Overcurrent 1 No No HA Information Only Inverter Phase Rotation 1 No No HA Inf...

Page 149: ...OK Off No No A Condition Cleared Log codes indicate where the UPS records the event H History log HA History and Active logs and A Active log only Table 11 3 Status Message Horn Phone Relay Log Indic...

Page 150: ...atus Rectifier Status Off No No No H User Status Rectifier Status On No No No H User Status Rectifier Switchgear Closed No No No No User Status Rectifier Switchgear Open No No No No User Status Rectif...

Page 151: ...ork drops In addition a Powerware Environmental Monitoring Probe EMP can be attached to obtain humidity temperature smoke alarm and security information S Powerware Hot Sync CAN Bridge Card provides c...

Page 152: ...y and Call Home features within the UPS please contact Eaton see page 1 8 Remote Notification provides the UPS with the capability to use a standard off the shelf PC modem as a telephone interface The...

Page 153: ...l into the UPS from a remote location and enter Terminal mode S Call Out The Call Out function allows the UPS to be configured to call either a remote computer or numeric paging service over the phone...

Page 154: ...COMMUNICATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 12 4 This page intentionally left blank...

Page 155: ...nected and the electrolytic capacitors are discharged After disconnecting the utility power and the DC power authorized service personnel should wait at least five minutes for capacitor bleedoff befor...

Page 156: ...e UPS is in Normal mode Normal status indicator is illuminated If an alarm lamp is illuminated or the Normal status indicators are not illuminated contact your Eaton service representative 13 2 2 Mont...

Page 157: ...es is required Refer to your local codes for disposal requirements S Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION Do no...

Page 158: ...MAINTAINING THE UPS SYSTEM Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 13 4 This page intentionally left blank...

Page 159: ...ons detail the input output environmental and battery specifications for the UPS 14 2 Single Module Specifications 14 2 1 UPS System Input Operating Input Voltage Nominal 10 15 208 Vac for operation f...

Page 160: ...load imbalance linear load Output Transients 5 for 100 load step or removal Frequency Regulation 0 01 Hz free running Synchronous to Bypass Bypass within voltage limits of 5 8 of output setting bypass...

Page 161: ...Vac to 242 Vac 380 Vac for operation from 323 Vac to 418 Vac 400 Vac for operation from 340 Vac to 440 Vac 415 Vac for operation from 353 Vac to 457 Vac 480 Vac for operation from 408 Vac to 528 Vac O...

Page 162: ...PRODUCT SPECIFICATIONS Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 14 4 This page intentionally left blank...

Page 163: ...outside of the USA performs startup and commissioning of the Product b if the Product is moved to a new location by someone other than an authorized Eaton Customer Service Engineer in the USA or Agent...

Page 164: ...WARRANTY Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 164201603 Rev 4 www eaton com powerquality 15 2...

Page 165: ...figurations S 164201603 5 UPS System Oneline Drawing S 164201603 6 Power Wiring Installation Notes S 164201603 7 Standard 9390 9390IT UPS Conduit and Wire Entry Locations S 164201603 8 9390IT UPS with...

Page 166: ...9390 9390IT UPS SYSTEM 091509 A DESCRIPTION DATE DRAWING NO SHEET REVISION STANDARD 9390 9390IT UPS INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Ma...

Page 167: ...EVISION AVAILABLE ONLY IN 208V INPUT OUTPUT AND 480V INPUT OUTPUT 40 40 KVA 40 30 KVA AND 40 20 KVA CONFIGURATIONS 9390IT UPS with INTERNAL BATTERY CONFIGURATION INSTALLATION INFORMATION Eaton 9390 UP...

Page 168: ...n millimeters inches 5 The standard 9390 cabinets can be installed in line up and match or standalone configurations The 9390IT UPS with internal battery configuration is standalone only Table A Stand...

Page 169: ...peration of the UPS system are Ambient Temperature Range 0 40 C 32 104 F Recommended Operating Range 20 25 C 68 77 F Maximum Relative Humidity 95 noncondensing The UPS ventilation requirements are sho...

Page 170: ...d with Typical Maintenance Bypass Panel 380 400 415 480 380 400 415 480 Sheet 4 9390 9390IT 40 20 9390 9390IT 40 30 9390 9390IT 40 40 9390 80 40 9390 80 50 9390 80 60 9390 80 80 208 220 208 220 Multip...

Page 171: ...OTATION NOTE 1 See Paragraph 4 7 on page 4 10 for dual feed 2 See Note 7 on page A 14 for neutral bonding instructions See Drawing 164201603 10 INPUT CONTACTOR K1 BATTERY CONVERTER BATTERY CABINET X S...

Page 172: ...7 on page 4 10 for dual feed 2 See Note 7 on page A 14 for neutral bonding instructions See Drawing 164201603 10 INPUT CONTACTOR K1 BATTERY CONVERTER BATTERY CABINET X SLOT INTERFACE Internal DUAL FEE...

Page 173: ...RITICAL LOAD DISTRIBUTION UNIT NOTE If installing as part of the UPS system a maintenance bypass without a rectifier input breaker a minimum of two separate feeds with upstream feeder breakers or one...

Page 174: ...OB 2 MIS MBP TYPICAL PARALLEL SYSTEM 1 1 AND 2 0 CONFIGURATIONS 4 of 6 C C 164201603 5 G NOTE 1 UPM and system bypass input feeds must come from the same source 2 Remove jumper for dual feed 3 See Not...

Page 175: ...ATIC SWITCH FUSE K3 FUSE BATTERY CON VERTER RECTIFIER INVERTER K1 UPM 2 E1 E2 E3 E6 E7 E8 E12 A B SEE NOTE 2 D BATTERY CABINET BATTERY BREAKER E4 E5 E9 E10 E11 E12 FUSE K5 STATIC SWITCH FUSE K3 FUSE B...

Page 176: ...12 A B SEE NOTE 2 D BATTERY CABINET BATTERY BREAKER E4 E5 E9 E10 E11 E12 FUSE K5 STATIC SWITCH FUSE K3 FUSE BATTERY CON VERTER RECTIFIER INVERTER K1 UPM 4 E1 E2 E3 E6 E7 E8 E12 A B SEE NOTE 2 D BATTER...

Page 177: ...mil each 2 1 2 1 2 1 2 1 2 1 AC Output to Critical Load Full Load Current 3 Phases 1 Neutral if required 1 Ground D Amps 56 53 31 29 28 24 Minimum Conductor Size Number per Phase AWG or kcmil each 2 1...

Page 178: ...tral Bonding Jumper Minimum Conductor Size Number See Note 7 AWG or kcmil each 4 1 6 1 6 1 6 1 6 1 NOTE Callout letters A B C and D map to Drawing 164201603 5 sheets 1 of 6 4 of 6 5 of 6 and 6 of 6 6...

Page 179: ...Conductor Size Number per Pole AWG or kcmil each 1 0 1 1 0 1 1 0 1 1 0 1 1 0 1 AC Output to Critical Load Full Load Current 3 Phases 1 Neutral if required 1 Ground D Amps 111 105 61 58 56 48 Minimum C...

Page 180: ...Conductor Size Number per Phase AWG or kcmil each 4 0 1 1 1 1 1 1 1 2 1 AC Input to UPS Bypass Full Load Current 3 Phases 1 Neutral if required 1 Ground B Amps 139 131 76 72 70 60 Minimum Conductor Si...

Page 181: ...Size Number per Phase AWG or kcmil each 250 1 1 0 1 1 0 1 1 0 1 1 1 AC Input to UPS Bypass Full Load Current 3 Phases 1 Neutral if required 1 Ground B Amps 167 158 91 87 84 72 Minimum Conductor Size...

Page 182: ...Number per Phase AWG or kcmil each 2 0 2 2 0 1 2 0 1 2 0 1 1 0 1 AC Input to UPS Bypass Full Load Current 3 Phases 1 Neutral if required 1 Ground B Amps 222 210 122 116 111 96 Minimum Conductor Size...

Page 183: ...hase C 2 6 250 kcmil 42 4 375 5 16 in Hex AC Input to UPS Rectifier Dual Input E1 Phase A 2 6 250 kcmil 42 4 375 5 16 in Hex E2 Phase B 2 6 250 kcmil 42 4 375 5 16 in Hex E3 Phase C 2 6 250 kcmil 42 4...

Page 184: ...13 5 120 3 16 in Hex E8 Phase C 1 14 2 0 13 5 120 3 16 in Hex AC Input to UPS Rectifier Dual Input E1 Phase A 1 14 2 0 13 5 120 3 16 in Hex E2 Phase B 1 14 2 0 13 5 120 3 16 in Hex E3 Phase C 1 14 2 0...

Page 185: ...1 14 2 0 13 5 120 3 16 in Hex AC Input to UPS Rectifier Dual Input E1 Phase A 1 14 2 0 13 5 120 3 16 in Hex E2 Phase B 1 14 2 0 13 5 120 3 16 in Hex E3 Phase C 1 14 2 0 13 5 120 3 16 in Hex AC Input...

Page 186: ...double size neutral 13 Conduit sizes were chosen from NEC Table C1 type letters RHH RHW RHW 2 TW THW THHW THW 2 Table O Power Cable Conduit Requirements UPS Model Voltage Terminal Number of Wires in...

Page 187: ...4 2 1 2 1 AC Input to Bypass A B C Neut Gnd 5 2 1 2 1 Output A B C Neut Gnd 5 2 1 2 1 DC Battery Positive Negative Gnd 3 1 1 Powerware 9390 9390IT 40 40 and 9390 80 40 480 AC AC Input to UPS A B C Gn...

Page 188: ...2 1 2 1 AC Input to Bypass A B C Neut Gnd 5 2 1 2 1 Output A B C Neut Gnd 5 2 1 2 1 DC Battery Positive Negative Gnd 3 1 1 2 1 Powerware 9390 80 60 380 415 480 AC AC Input to UPS A B C Gnd 4 2 1 AC I...

Page 189: ...Gnd 4 1 1 4 1 AC Input to Bypass A B C Neut Gnd 5 1 1 4 1 Output A B C Neut Gnd 5 1 1 4 1 DC Battery Positive Negative Gnd 3 1 1 4 1 Powerware 9390 40 30 380 400 415 AC AC Input to UPS A B C Gnd 4 1...

Page 190: ...ents continued UPS Model Voltage Terminal Number of Wires in Conduit Minimum Conduit Trade Size inches Number of Conduits Powerware 9390 80 60 380 400 415 AC AC Input to UPS A B C Gnd 4 2 1 2 1 AC Inp...

Page 191: ...60A 60A 100 100A 60A 60A 50A 45A Powerware 9390 9390IT 40 40 Powerware 9390 80 40 80 175A 90A 90A 80A 70A 100 150A 80A 80A 70A 60A Powerware 9390 80 50 80 225A 110A 110A 100A 100A 100 175A 90A 90A 90A...

Page 192: ...150A 100 300A 150A 150A 150A 125A 19 There is no DC disconnect device within the standard UPS 20 An external battery disconnect device is recommended and may be required by NEC or local codes when ba...

Page 193: ...ds must come from the same source 27 Parallel UPM input wiring size requirements and output wiring size requirements from the UPMs to the tie cabinet or distribution panel are the same as listed in Ta...

Page 194: ...requirements 31 Setup of the CAN Bridge card for parallel operation must be performed by an authorized Eaton Customer Service Engineer Contact service to schedule a date 32 For parallel system circui...

Page 195: ...System Neutral Bonding Jumper Minimum Conductor Size Number See Note 29 AWG or kcmil each 6 1 8 1 8 1 8 1 8 1 2 0 and 2 1 AC Input to Tie Cabinet Bypass optional Full Load Current 3 Phases 1 Neutral i...

Page 196: ...nimum Conductor Size Number See Note 29 AWG or kcmil each 6 1 6 1 6 1 6 1 8 1 2 0 and 2 1 AC Input to Tie Cabinet Bypass optional Full Load Current 3 Phases 1 Neutral if required 1 Ground F Amps 278 2...

Page 197: ...um Conductor Size Number See Note 29 AWG or kcmil each 2 1 6 1 6 1 6 1 6 1 2 0 and 2 1 AC Input to Tie Cabinet Bypass optional Full Load Current 3 Phases 1 Neutral if required 1 Ground F Amps 334 316...

Page 198: ...inimum Conductor Size Number See Note 29 AWG or kcmil each 2 1 6 1 6 1 6 1 6 1 2 0 and 2 1 AC Input to Tie Cabinet Bypass optional Full Load Current 3 Phases 1 Neutral if required 1 Ground F Amps 444...

Page 199: ...Required parallel system wiring length should be in accordance with the following rule as referenced to the diagram below to ensure approximately equal current sharing when in Static Bypass mode Tota...

Page 200: ...PANEL TO DRILL OR PUNCH CONDUIT HOLES BOTTOM ENTRY CONDUIT LANDING FOR AC INPUT AND OUTPUT DC INPUT DC CONTROL AND INTERFACE CONNECTIONS REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES CONDUIT LANDINGS F...

Page 201: ...KNOCKOUTS AS REQUIRED TO ROUTE WIRES BETWEEN CABINETS INSIDE PANELS INTER CABINET WIRING ACCESS KNOCKOUTS REMOVE KNOCKOUTS AS REQUIRED TO ROUTE WIRES BETWEEN CABINETS 164201603 7 STANDARD 9390 9390IT...

Page 202: ...BOTTOM ENTRY CONDUIT LANDING FOR AC INPUT AND OUTPUT DC INPUT DC CONTROL AND INTERFACE CONNECTIONS REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES CONDUIT LANDINGS FOR X SLOT CONNECTIONS REMOVE PANELS T...

Page 203: ...IRED TO ROUTE WIRES BETWEEN CABINETS INSIDE PANELS INTER CABINET WIRING ACCESS KNOCKOUTS REMOVE KNOCKOUTS AS REQUIRED TO ROUTE WIRES BETWEEN CABINETS 164201603 7 9390IT UPS MODELS with INTERNAL BATTER...

Page 204: ...TERMINALS AC INPUT TO UPS RECTIFIER AND BYPASS A B C N DC INPUT FROM BATTERY TO UPS AND AC OUTPUT TO CRITICAL LOAD A B C N SEE SHEET 2 FOR DETAILS WIREWAY FOR TOP ENTRY POWER WIRING MODELS 80 40 80 50...

Page 205: ...NGLE INPUT AC INPUT TO BYPASS DUAL INPUT PHASE A E1 PHASE B E2 PHASE C E3 PHASE A E9 PHASE B E10 PHASE C E11 AC OUTPUT TO CRITICAL LOAD PHASE A E6 PHASE B E7 PHASE C E8 TERMINAL DETAIL MODELS 80 40 80...

Page 206: ...C N DC INPUT FROM BATTERY TO UPS AND AC OUTPUT TO CRITICAL LOAD A B C N SEE SHEET 4 FOR DETAILS MODEL 40 40 40 30 AND 40 20 208V 220V INPUT AND 208V 220V OUTPUT AND 380V 400V 415V 480V INPUT AND 380V...

Page 207: ...RECTIFIER DUAL INPUT PHASE A E1 PHASE B E2 PHASE C E3 PHASE A E9 PHASE B E10 PHASE C E11 AC OUTPUT TO CRITICAL LOAD PHASE A E6 PHASE B E7 PHASE C E8 AC INPUT TO UPS RECTIFIER AND BYPASS SINGLE INPUT A...

Page 208: ...IREWAY FOR TOP ENTRY POWER WIRING AC INPUT TO UPS RECTIFIER AND BYPASS A B C N DC INPUT FROM BATTERY TO UPS AND AC OUTPUT TO CRITICAL LOAD A B C N SEE SHEET 6 FOR DETAILS MODELS 80 40 80 50 80 60 AND...

Page 209: ...PHASE A E6 PHASE B E7 PHASE C E8 AC INPUT TO UPS RECTIFIER AND BYPASS SINGLE INPUT AC INPUT TO BYPASS DUAL INPUT DC INPUT FROM BATTERY E4 E5 RIGHT SIDE VIEW MODELS 80 40 80 50 80 60 AND 80 80 380V 40...

Page 210: ...g 8 LAN and telephone drops for use with X Slot connectivity cards must be provided by facility planners or the customer Table X TB1 and TB2 Interface Connections Terminal TB1 Name Description 1 Remot...

Page 211: ...S NOTE Metal shields covering wiring terminals must be removed or opened to gain access to terminals 2 of 15 INTERFACE TERMINAL LOCATIONS TB1 TB2 MINI CSB MINI CSB BUILDING ALARM TERMINAL BLOCK P5 BAT...

Page 212: ...e normally closed EPO contact is not used 032406 B 164201603 10 DESCRIPTION DATE DRAWING NO SHEET REVISION INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS INTERFACE TERMINALS 1 10 1 10 TB1...

Page 213: ...lied 2 The building alarms can be programmed to display the alarm functional name 091505 A 164201603 10 DESCRIPTION DATE DRAWING NO SHEET REVISION INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCA...

Page 214: ...y Aux signal wiring from the UPS must be connected to the DC source disconnect device 10 Battery Aux and UVR wiring should be a minimum of 18 AWG Table Y Battery Disconnect Interface BATTERY AUX BATTE...

Page 215: ...ctive devices to the UPS The REPO switch must be a latching type switch with a dedicated circuit 12 A jumper wire must be connected between pins 1 and 2 on TB1 if a normally closed EPO switch is not u...

Page 216: ...ntenance bypass auxiliary contacts as applicable See Table AB Table AB Typical Maintenance Bypass Panel Auxiliary Contact Control Wiring TB1 9 10 MAINTENANCE BYPASS PANEL PROVIDED BY OTHERS UPS NOTE R...

Page 217: ...from the critical bus by facility planners or the customer See Table AC Table AC Typical Maintenance Bypass Panel Key Switch Control Wiring Neutral Key Switch Lamp 120 VAC Fused TB2 Output Contactor...

Page 218: ...the UPM cabinets for parallel interface wiring Install the interface wiring in separate conduit from the power wiring 17 Use Class 1 wiring methods as defined by the NEC for parallel interface wiring...

Page 219: ...LEL SYSTEM CAN WIRING 10 of 15 TWISTED PAIR TWISTED PAIR TWISTED PAIR UPM 1 CAN CARD J3 UPM 2 CAN CARD J3 UPM 3 CAN CARD J3 IF INSTALLED UPM 4 CAN CARD J3 IF INSTALLED INSTALLATION INFORMATION Eaton 9...

Page 220: ...n Wiring Terminations All UPMs From To TB2 1 Bldg Alarm 2 TB2 3 On Byp NO TB2 2 Bldg Alarm 2 Return TB2 4 Byp Common 032406 B 164201603 10 DESCRIPTION DATE DRAWING NO SHEET REVISION INTERFACE WIRING I...

Page 221: ...nd Operation Manual S 164201603 Rev 4 www eaton com powerquality A 57 071608 A 164201603 10 INTERFACE WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS DESCRIPTION DATE DRAWING NO SHEET REVISION PARALL...

Page 222: ...Pair CAN Card J3 2 AUX 1 COM TB2 1 AUX 2 NO Pullchain From UPM 4 To MOB 4 Function Remarks CAN Card J3 1 AUX 1 NC MOB Open Alarm Twisted Pair CAN Card J3 2 AUX 1 COM TB2 1 AUX 2 NO Pullchain From MOB...

Page 223: ...NTERFACE MODULE II TERMINAL LOCATIONS TERMINAL TB 3 120 VAC POWER SUPERVISORY CONTACT MODULE II TERMINAL LOCATIONS GROUND TERMINAL TERMINAL TB 1 SIGNAL CONNECTIONS FROM THE UPS TERMINAL TB 3 120 VAC P...

Page 224: ...omer 21 Maximum distance between the UPS cabinet and RMP II RIM II or SCM II is not to exceed 500 feet 22 Use Class 1 wiring methods as defined by the NEC for RMP II RIM II or SCM II power and signal...

Page 225: ...RIPTION DATE DRAWING NO SHEET REVISION FRONT VIEW Dimensions are in millimeters inches STANDARD 93909390IT UPS MODELS INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installatio...

Page 226: ...ION DATE DRAWING NO SHEET REVISION TOP VIEW BOTTOM VIEW LEFT SIDE LEFT SIDE RIGHT SIDE RIGHT SIDE FRONT FRONT STANDARD 9390 9390IT UPS MODELS INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390...

Page 227: ...of 6 DESCRIPTION DATE DRAWING NO SHEET REVISION FRONT VIEW RIGHT SIDE VIEW 9390IT UPS MODELS WITH INTERNAL BATTERY CONFIGURATION INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA...

Page 228: ...nches 4 of 6 DESCRIPTION DATE DRAWING NO SHEET REVISION FRONT FRONT 9390IT UPS MODELS WITH INTERNAL BATTERY CONFIGURATION INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Install...

Page 229: ...with OPTIONAL FLOOR MOUNTING BRACKETS DESCRIPTION DATE DRAWING NO SHEET REVISION LEFT SIDE RIGHT SIDE FRONT STANDARD 9390 9390IT UPS MODELS ONLY INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and...

Page 230: ...SEISMIC MOUNTING BRACKETS DESCRIPTION DATE DRAWING NO SHEET REVISION SEISMIC KIT INSTALLATION LEFT SIDE RIGHT SIDE FRONT STANDARD 9390 9390IT UPS MODELS ONLY INSTALLATION INFORMATION Eaton 9390 UPS 2...

Page 231: ...LS WITH INTERNAL BATTERY CONFIGURATION BATTERY TRAYS INSTALLED BATTERY DISCONNECT BREAKER LOCATION 2 STRING 3 STRING 80 BATTS 120 BATTS WIREWAY WINGNUT LEFT SIDE COVER PANEL AND FRONT BATTERY COMPARTM...

Page 232: ...wire size 14 AWG Minimum wire size 22 AWG Dimensions are in millimeters inches NOTE Interface wiring and conduit between the REPO switch and the UPS are to be supplied by the customer 115 8 4 56 114 3...

Page 233: ...CES FLUSH MOUNT USE 10 PAN HEAD SCREWS MOUNT WITH VENT HOLES FACING UP SURFACE MOUNT USE 10 PAN HEAD SCREWS FOR HANGING MOUNT WITH VENT HOLES FACING UP Dimensions are in millimeters inches INSTALLATIO...

Page 234: ...ACES FLUSH MOUNT USE 10 PAN HEAD SCREWS MOUNT WITH VENT HOLES FACING UP SURFACE MOUNT USE 10 PAN HEAD SCREWS FOR HANGING MOUNT WITH VENT HOLES FACING UP Dimensions are in millimeters inches INSTALLATI...

Page 235: ...05 A DESCRIPTION DATE DRAWING NO SHEET REVISION 164201603 15 2 of 2 15 PIN D SUB CONNECTORS INSTALLATION INFORMATION Eaton 9390 UPS 20 80 kVA and 9390IT 20 40 kVA Installation and Operation Manual S 1...

Page 236: ...RFACES FLUSH MOUNT USE 10 PAN HEAD SCREWS MOUNT WITH VENT HOLES FACING UP SURFACE MOUNT USE 10 PAN HEAD SCREWS FOR HANGING MOUNT WITH VENT HOLES FACING UP Dimensions are in millimeters inches INSTALLA...

Page 237: ......

Page 238: ...1642016034 164201603 4...

Reviews: