10
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
•
The newer, more energy efficient data center cooling methods (such as air side economization) can create
much wider ranges of temperature and Relative Humidity (RH) in the UPS room and/or data center. There
are two aspects of this increased operating environment that can, if ignored, create issues.
–
One is the creation of microclimates, which are persistent variations of temperature and/or RH within
a single room. For example one side of the room is always cooler than the other side, no matter the
actual temperature.
–
The other aspect is the rate of change of temperature and/or RH, which can occur during transitions
within the cooling system. Examples: changing the mixture ratio of inside versus outside air, or
external changes in the outside air when going from night to day, and back to night.
–
When ignored, either one of these aspects can create an undesirable microclimate at the UPS
location. If the environment created by this microclimate exceeds the UPS operating specification, the
UPS reliability, over time, will be reduced. These same environmental extremes will also create
reliability concerns for any servers that are exposed to them.
The basic environmental requirements for operation of the UPS are:
•
Ambient Temperature Range: 5–40°C (41–104°F)
•
Recommended Operating Range: 5–40°C (41–104°F)
•
Maximum Relative Humidity: 5–95%, noncondensing
CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's environmental
requirements should be followed if they are more stringent than the UPS requirements. Operating
temperatures above the recommended range will result in decreased battery life and performance, and may
reduce or void the battery warranty.
The UPS ventilation requirements are shown in
. To allow for future power upgrades, Eaton
recommends using air conditioning or ventilation sized for the fully rated UPS kW frame size installed instead of
the derated kW ordered. Sizing the site cooling infrastructure to be capable of cooling the maximum kW frame
size will allow a full power rating upgrade without having to modify the infrastructure.
Table 1. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
UPS Rating
Minimum Required Cooling Air Flow
Eaton 9355 UPS
8–15 kVA
104 liter/sec (220 cfm)
The UPS equipment operating environment must meet the weight requirements shown in
and the size
requirements shown in
.
Table 2. UPS Cabinet Weights
Standard Model Floor Loadings (2-High/3-High Cabinets)
Eaton 9355 UPS
Maximum Weight
Point Loading
lb/in
2
(kg/cm
2
)
2-High UPS
381 lb (173 kg)
95 (6.7)
3-High UPS-32
587 lb (266 kg)
147 (10.3)
3-High UPS-64
619 lb (281 kg)
155 (10.9)
Summary of Contents for 9355 Series
Page 1: ...p n 164201601 Revision E0 10 15 kVA User s Guide Eaton 9355 Parallel UPS ...
Page 4: ......
Page 10: ...x Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 List of Tables ...
Page 18: ...8 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Safety Warnings ...
Page 54: ...44 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 UPS System Installation ...
Page 68: ...58 Eaton 9355 Parallel UPS 10 15 kVA User s Guide 164201601 Rev E0 Operation ...
Page 72: ...164201601E0 164201601 E0 ...