UPS INSTALLATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide
S
164201642 Rev C
www.eaton.com/powerquality
25
11.
Use the conduit knockouts on the rear, sides, and bottom of the
cabinet to attach power wiring conduit.
12.
Hardwire the input, output, and ground terminations for the UPS.
See Table 3 for wiring specifications. See Table 4 to construct the
input and output terminal connectors.
For a detailed view of the terminal block, see Figure 10.
NOTE
Input neutral must be wired for proper operation. Failure to connect an input neutral
will void the warranty.
NOTE
The Eaton 9355-F47 Unirom UPS is a single-feed UPS only.
Table 3. Terminal Block Wiring
10 kVA
System
Voltage
Wire
Function
Feeder Circuit
Breaker Rating
L1, L2, L3, N
Wire Size
1
Tightening
Torque
(L and N)
Ground
Wire
Size
1
Tightening
Torque
(Ground)
Conduit Size
2, 3
(Number of
Conduits)
208
Input
40A
8 AWG
40 lb in
(4.5 Nm)
10 AWG
35 lb in
(4.0 Nm)
1.00
”
conduit (1)
208
Output
40A
8 AWG
40 lb in
(4.5 Nm)
10 AWG
35 lb in
(4.0 Nm)
1.00
”
conduit (1)
15 kVA
System
Voltage
Wire
Function
Feeder Circuit
Breaker Rating
L1, L2, L3, N
Wire Size
1
Tightening
Torque
(L and N)
Ground
Wire
Size
1
Tightening
Torque
(Ground)
Conduit Size
2, 3
(Number of
Conduits)
208
Input
60A
4 AWG
50 lb in
(5.6 Nm)
10 AWG
35 lb in
(4.0 Nm)
1.25
”
conduit (1)
208
Output
60A
4 AWG
50 lb in
(5.6 Nm)
10 AWG
35 lb in
(4.0 Nm)
1.25
”
conduit (1)
1
Use only 90
°
C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code
Table 310‐104(A). Code may require a larger AWG size than shown in this table because of temperature, number of
conductors in the conduit, or long service runs. Follow local requirements.
2
Per NEC article 300‐20(a) for Ferrous Metal Raceways, all three-phase conductors must be run in the same conduit.
Neutral and ground must be run in the same conduit as the phase conductors.
3
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.