Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
41
8.
Connect the factory-installed wiring from the maintenance bypass switch to the UPS terminal block (see
).
Connect the maintenance bypass (red and black) wires to TB1-2 (the A/B maintenance bypass auxiliary
contacts) on the UPS terminal block.
Figure 26. Wiring from Maintenance Bypass Switch to UPS
1 2
3
4
5
6
7
8
9
A/B Maintenance
Bypass Auxiliary
Contacts
TB1
Input
Output
A
8
A
2
9.
Replace the wiring access cover on the UPS and the optional isolation transformer, if applicable.
10. Replace the MBM/PDM wiring access cover and conduit landing plate.
11. Continue to paragraph
to complete the installation.