84
Eaton 9155 UPS (8–15 kVA) User’s Guide 164201553—Rev H0
Table 14. Dimensions and Weights (Continued)
Dimensions (H x W x D)
Weight
2-High EBM
32.2" x 12" x 30.3" (81 x 30 x 77 cm)
480 lb (218 kg)
3-High EBM
47.8" x 12" x 30.3" (121.5 x 30 x 77 cm)
710 lb (322 kg)
PDM (rear UPS mount)
16.5” x 12” x 7” (42 x 30 x 17.8 cm)
25 lb (11 kg)
MBM (rear UPS mount)
16.5” x 12” x 7” (42 x 30 x 17.8 cm)
18 lb (8 kg)
Table 15. Environmental and Safety Specifications
Operating Temperature
50°F to 104°F (10°C to 40°C)
Optimal battery performance: 77°F (25°C)
Transit Temperature
-13°F to 131°F (-25°C to 55°C)
Storage Temperature
32°F to 77°F (0°C to 25°C)
Recommended battery storage: 59°F to 77°F (15°C to 25°C)
Ventilation
Front air intake, forced air, two fans, positive pressurization, temperature UPS-monitored
Altitude
9,843 ft (3,000m) operating without derating 32,810 ft (10,000m) during transportation
Relative Humidity
5 95% noncondensing
Heat Dissipation
5582 BTU/hr maximum online
5294 BTU/hr maximum on battery
Audible Noise
<56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
Surge Suppression
ANSI C62.41 Category B3
Safety Conformance
NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3
Agency Markings
cULus, NOM-NYCE
EMC (Class A)
IEC 62040-2, FCC Part 15, ICES-003, VCCI
Table 16. Technical Specifications
Technology
Online, double-conversion, split-phase topology with static bypass switch and
optional 3-position maintenance bypass switch.
Frequency independent operation.
Input Voltage Range
75–144 Vac per phase
Isolation Transformer Input
Voltage Range
208V or 240V ±20%
Input Power Factor
>0.99 at full load nominal line conditions
Input Rated Voltage
100/200, 110/220, or 120/240 Vac with 180° phase displacement
120/208 or 127/220 Vac with 120° phase displacement
Input Frequency Range
45–65 Hz
Summary of Contents for 9155 UPS
Page 1: ...p n 164201553 Revision H0 8 15 kVA User s Guide Eaton 9155 UPS ...
Page 8: ...viii Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 List of Tables ...
Page 14: ...6 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Introduction ...
Page 18: ...10 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 Safety Warnings ...
Page 60: ...52 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS System Installation ...
Page 66: ...58 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Wiring Diagrams and Schematics ...
Page 86: ...78 Eaton 9155 UPS 8 15 kVA User s Guide 164201553 Rev H0 UPS Operating Instructions ...
Page 98: ...164201553H0 164201553 H0 ...