
OPERATION
Eaton
®
9130 UPS (700–3000 VA) User's Guide
S
164201718 Rev 3
www.eaton.com/powerquality
51
Configuring Battery Settings
Set the UPS for the number of EBMs installed, whether to run automatic
battery tests, and automatic restart configuration.
Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1.
Press any button on the front panel display to activate the menu
options, then select SETTINGS, USER SETTINGS, and NUMBER OF
BATTERY STRINGS.
2.
Use the or buttons to select the number of battery strings
according to your UPS configuration:
All UPS and EBM Cabinets
Number of Battery Strings
UPS only (internal batteries)
1 (default)
UPS + 1 EBM
3
UPS + 2 EBMs
5
UPS + 3 EBMs
7
UPS + 4 EBMs
9
NOTE
If 0 is selected, no batteries are connected and all battery-related
alarms are disabled.
NOTE
The UPS contains one battery string; each EBM contains two battery
strings.
3.
Press the
button to save the setting.
4.
Press the
ESC
button until the start screen appears.