34003906EN/AE - 5
The
Network Management Card & Modbus/Jbus
(66103) can be hot-plugged on all UPSs from
EATON equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart
the UPS.
●
Remove the plastic cover of the Minislot.
●
Note the MAC address of the card before inserting it.
●
Insert and secure the card with the screws.
●
Connect the ETHERNET cable.
●
Check the ETHERNET port indications.
●
Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.
Note.
Connection detection continues until the card has been connected to the network. Once
connection is made, card start-up continues.
Once the card has started, proceed as indicated below.
●
Connect the serial cable to card’s service port and PC’s COM port
●
Use a terminal emulator such as HyperTerminal
TM
with these settings
"Echo typed characters locally" option: disabled
●
Type EATON (or eaton).
The main configuration menu is displayed:
IP SETTINGS
Bits per second
Data bits
Stop bits
Parity
Flow control
9600
8
1
none
none
EATON
NETWORK MANAGEMENT CARD
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
5 : Jbus configuration
6 : Sensor configuration
0 : Exit
ETHERNET
ASI
Settings/Sen
sor
66103
UPS data
RS232
100M
10M