Page 18
5SC 1 - 3 KVA US_EN
5. Maintenance
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions are
required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
A
B
A
- Remove the center panel.
B
- Remove the left-hand side of the front
panel.
C
C
-
Disconnect the battery module by
separating the two connectors.
D
D
- Remove the metal protection cover in
front of the battery (one screw).
E
E
- Remove the battery module and replace
it.
Mounting the new battery module
Carry out the above instructions in reverse order.
•
To ensure safety and high performance, use only batteries supplied by EATON.
•
Take care to firmly press together the two parts of the connector during remounting.
Summary of Contents for 5SC 1000i Rack2U
Page 2: ...Page 2 5SC 1 3 KVA US_EN ...