2. Presentation
2.4 LCD description
After 5 minutes of inactivity, the LCD displays the screen saver.
The LCD backlight automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Operation status
Load/equipment status
Normal mode
100%
17min
1EBM
100%
2.7kW
3kVA
Efficiency: 98%
Battery status
Efficiency and load group information
The following table describes the status information provided by the UPS
Note:
If other indicator appears, see troubleshooting on page 21 for additional information.
Operation status
Possible cause
Action
Standby mode
The UPS is OFF, waiting for start-up
command from user
Equipment is not powered until
button is pressed.
Normal mode
The UPS is operating normally.
The UPS is powering and protecting
the equipment.
In AVR mode
Load protected LED is ON
No beep
The UPS is operating normally but
the utility voltage is outside normal
mode thresholds.
The UPS is powering the
equipment through a Automatic
Voltage Regulation device.
The equipment is still normally
protected.
On Battery
Battery LED is on
1 beep every 10 seconds
A utility failure has occured and
the UPS is in Battery mode.
The UPS is powering the equipment
with the battery power.
Prepare your equipment for
shutdown.
End of backup time
Battery LED is blinking
1 beep every 3 seconds
The UPS is in battery mode and
the battery is running low.
This warning is approximate, and
the actual time to shutdown may
vary siginificantly.
Depending on the UPS Load
and number of Extended Battery
modules (EBMs), the "Battery Low"
warning may occur before the
battery reaches 25 % capacity.