6-12 TROUBLESHOOTING CHART
SYMPTOM
INSPECTION AREA
PROBABLE DEFECTS
Undesirably Closes
•
Control Circuit
• Close Circuit
(CS/C Getting Shorted)
•
Mechanism
• Close Release Latch
(Fails to reset)
• Close Floor Tripper
(Fails to reset)
Fails To Trip
• No Trip Sound
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact not making, poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Mechanism
• Trip Clapper
(Jammed)
• Trip Sound
But No Trip
• Trip Mechanism
• Trip Bar, Trip Latch
(Jammed)
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Vacuum Interrupter
(One or more welded)
Undesirably Trips
• Control Circuit
• Control Power
(CS/T Switch, remains made)
• Mechanism
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
• Trip Bar Reset Spring
(Loss of torque)
Summary of Contents for 380 VCP-W 16
Page 2: ......
Page 13: ...I B 3A74792H08 Page 7 Effective 09 2014...
Page 22: ...Page 16 I B 3A74792H08 Effective 09 2014 Figure 3 7 Typical VCP W 38kV Escutcheon...
Page 23: ...I B 3A74792H08 Page 17 Effective 09 2014 Figure 3 8 Typical VCP W 38kV Escutcheon...
Page 33: ...I B 3A74792H08 Page 27 Effective 09 2014 compartment Figure 5 5 Charging Schematic...
Page 38: ...Page 32 I B 3A74792H08 Effective 09 2014 Figure 5 10 Undervoltage Trip Device Configuration...
Page 60: ...Page 54 I B 3A74792H08 Effective 09 2014...
Page 62: ...Page 56 I B 3A74792H08 Effective 09 2014 Style 3A74792H08 Printed in USA...