34
4.5 Alarm codes
Using a sophisticated self-diagnosis system, the UPS is able to check its
own status and any anomalies and/or faults which may occur during
normal operation and display them on the display panel. If there is a
problem, the UPS signals the event by showing the code and the type of
active alarm on the display.
Alarms
“Minor” problems which reduce performance or prevent certain functions
from being used.
CODE
DESCRIPTION
A007
Fans blocked
A107
Cable connection error
A10A
Unbalanced input voltages (three-phase input)
A806
E.P.O control active
A80E
Overload: load > 105%
A810
Load percentage greater than the user threshold set
A60D
Batteries missing or Battery Box missing or not connected
A802
Low battery
AC20
UPS work in Manual Bypass operation mode
Faults
Faults are normally preceded by an alarm signal and their scale leads to
the power-off of the inverter and the load being powered by the bypass
line.
CODE
DESCRIPTION
F002
UPS Fault
F004
Dissipator over temperature
F302 F303
Capacitor bank undervoltage
F300 F301
Capacitor bank overvoltage
F304
Unbalanced capacitor bank
F305
Failed capacitor bank soft start
F70D
Inverter overvoltage
F805
Short circuit
Summary of Contents for 20000i