Instruction Book
Page 49
IB131009EN
SYMPTOM
INSPECTION AREA
CONTROL DEFECTS
Fails to Trip
• No Trip Sound
• Control Circuit
• Control Power
(Fuse blown or switch off)
• Secondary Disconnect
• Auxiliary Switch
(a contact no making,
poor or burned)
• Trip Coil
(Burned or open)
• Terminals and Connections
(Poor or burned or open)
• Trip Mechanism
• Trip Clapper
(Jammed)
• Trip Bar, Trip Latch
(Jammed)
• Trip Sound
• Trip Mechanism
• Pole Shaft
(Jammed)
• Operating Rod Assembly
(Broken or pins out)
• Vacuum Interrupter
(One or more Welded)
Undesirably Trips
• Control Circuit
• Control Power
(SD/T Switch, remains made)
• Mechanism
• Trip Coil Clapper
(Not resetting)
• Trip Bar or Trip Latch
(Poor engagement of mating
or worn surfaces)
• Trip Bar Reset Spring
(Loss of torque)