![Eaton 119380 Manual Download Page 19](http://html1.mh-extra.com/html/eaton/119380/119380_manual_526688019.webp)
8 Technical data
ESR5-NO-31-230VAC
12/19 MN049012EN
www.eaton.com
15
The data only applies if the safety function is demanded at least once a year.
The specifications apply assuming the following calculation basis
B
10d
300000 (at 5
A
DC-13)
d
op
365 days
h
op
24 h
t
Cycle
3600 s
Safety parameters for IEC 61508 - Low demand
SIL
3
MTTF
d
19346 years
PFD
avg
1.50 x 10
-4
Proof test interval
78 months
Duration of use
240 months
Safety characteristic data according to EN ISO 13849
Category
4
Performance Level
e
CCF
Passed
The data only applies if the safety function is demanded at least once a year.
The specifications apply assuming the following calculation basis
B
10d
300000 (at 5
A
DC-13)
d
op
365 days
h
op
24 h
t
Cycle
3600 s