Installation Plan and Unpacking
3-2
Eaton
®
Power Xpert 9395 Integrated Battery Cabinet (Model 1085 and 1085HR) Installation Manual
164201687—Rev 06
www.eaton.com/powerquality
The battery equipment operating environment must meet the weight requirements shown in Table 3-1 and the
size requirements shown in Figure 3-1 through Figure 3-4. The weight shown in Table 3-1 is the maximum
weight of a fully configured cabinet. The weight of your cabinet may be less due to its configuration.
The battery cabinet uses convection air cooling to regulate internal component temperature. Air inlets are in
the front of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper
air circulation. The clearances required around the battery cabinet are shown in Table 3-2. Dimensions are in
millimeters (inches).
The basic environmental requirements of both Models IBC-S and IBC-L for operation of the battery system are:
l
Operational Temperature Range: 22-28°C (72-82°F)
l
Maximum Relative Humidity: 95%, non-condensing
Table 3-1. Maximum Battery Cabinet Weight
Model
Weight
kg (lb)
Shipping
Installed
Point Loading
Power Xpert 9395 1085 or 1085HR
with 40 batteries (480 Vdc)
2368 (5221)
2327 (5130)
8 at 291 (642)
Table 3-2. UPS Cabinet Clearances
From Top of Cabinet
Minimum clearance over the UPS cabinet is 457.2 mm (18”) minimum for ventilation
From Front of Cabinet
1067 mm (42”) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
NOTE
It is recommended for optimal battery life and discharge performance to keep the
ambient air temperature the battery is used in at 25°C (77°F). Operating
temperatures above the recommended range will result in decreased battery life
and performance, and will reduce or void the battery warranty. Refer to Eaton's
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery
Replacement Price Book for more information. These documents can be found at
www.eaton.com/powerquality or contact your service representative for
information on how to obtain copies.