COMBUSTION AIR INTAKE VENTING REQUIREMENTS 

This appliance can draw combustion air from indoors, or utilize the factory installed air 
intake duct collar located on the blower assembly to duct combustion air in from outside.  

 
CAUTION: 

When the appliance is located in a building with a negative air condition, or 

in a dusty or dirty atmosphere such as a welding shop, wood working shop, poultry barn 
or foundry, it is mandatory to duct combustion air from outdoors or from an area free of 
the negative pressure conditions / contaminated air.  
 
Air intake duct must be a minimum of 4” (10 cm) in diameter, gas tight, and constructed 
of a suitable rigid material that will be able to withstand general environmental 
conditions.  
 
Any 90 degree bends in the combustion air intake venting reduces the total allowable 
combined intake/exhaust venting by 5’ (1.5 m) 

 
The air intake duct must not be directly connected to the appliance.

 It is mandatory 

that a heavy duty metal flexible duct be installed between the appliance air intake duct 
collar and the intake air ducting to allow for free expansion/contraction of the appliance. 
(See accessory AC1220 – Air Intake Flex Duct/Cap Kit) 

 

Combustion air intake may be drawn either horizontally or vertically, and must be 
protected with a suitable screened cap to prevent pest/debris infiltration of the duct. Do 
not use termination caps that utilize a damper or flapper system. (See accessory 
AC1220 – Side wall air Intake Flex Duct/Cap Kit. Roof caps are field supplied.) 
 
Air intake terminations shall not be located less than 3 ft (90 cm) above grade, and must 
be adequately protected from potential blockages due to snow/ice/debris accumulation.  
 
Ensure adequate clearance around the air intake to allow sufficient combustion air 
supply to the heater. It is recommended that any single wall pipe containing cold air be 
insulated to prevent or reduce nuisance condensation on the duct surface. 
 
Appliances may not share common air intake ducting except in cases where those 
appliances are jointly controlled.  

 

In situation where indoor air is especially humid (e.g., carwash applications, food 
processing, etc.) it is recommended that combustion air be drawn from an alternate 
source. Ensure that all venting materials used are suitable to withstand high moisture 
conditions (e.g., stainless steel, ABS, PVC, etc.). 
 

      

 

WARNING 

Never use a flexible duct as the only means of combustion air intake duct. Flexible 
ducts are meant to be used as a flexible transition from the burner assembly to a 
rigid duct only.  
Plastic flexible duct and light duty residential “dryer vent” type ducts are not suitable 
for this purpose.  

 
 

Summary of Contents for ED-40U

Page 1: ...opane Installation Code CSA B149 1 The latest edition Electrical Code PART 1 CSA C22 1 in Canada and ANSI NFPA NO 70 in the USA must also be observed It is beyond the scope of these instructions to co...

Page 2: ...t in the appliance Dimensions at certain points of the appliance may be less WARNING THIS AND EVERY GAS FIRED PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY A PROFESSIONALLY LICENSED AND QUALIFIED GAS...

Page 3: ...light this or any other appliance 6 Ne pas tenter d allumer ceci ou aucun autre appareil WARNING This appliance may have sharp edges and corners Wear protective clothing such as gloves and protective...

Page 4: ...nt should be installed in a visible location Minimum required clearances below the heater should be clearly visible so that appropriate distances to combustibles will be maintained to vehicles In loca...

Page 5: ...ate space around the burner and off the gas connection end of the burner to allow for servicing Minimum distance from the radiant surface to the floor in non agricultural installations is 7 ft 2 1 m i...

Page 6: ...ectrical Code ANSI NFPA N0 70 in the U S A and PART 1 CSA C22 1 in Canada must also be observed This appliance is approved for use in an attached garage only when required building codes have been met...

Page 7: ...ating equipment WARNING HEATER EXPANSION It is a normal condition that during heat up and cool down a tube heater will expand and contract Allowances for heater expansion must be made in the gas conne...

Page 8: ...ARS Low intensity radiant tube heaters are suitable for use in aircraft hangars when installed in accordance with the latest edition of the Standard for Aircraft Hangars ANSI NFPA No 409 in the USA or...

Page 9: ...Celsius It is the installer s responsibility to ensure that building materials with a low heat tolerance which may degrade at lower temperatures are protected to prevent degradation Refer to Clearance...

Page 10: ...the structure as required Attach hanger supporting anchors securely and directly into building structure only in no case should any support that anchors only into drywall or other interior wall ceili...

Page 11: ...event walking of the reflectors the first and second reflector can be joined together at the overlap with a sheet metal screw With the radiant tube and reflectors now installed the burner can be fitte...

Page 12: ...12...

Page 13: ...13...

Page 14: ...installing this appliance Consider that the heater will expand in length as much as inch 12 7 or more for every 10 ft 3 m of system length Typically the greater the firing rate the greater the expans...

Page 15: ...here the receptacle is switched by the thermostat controller Heating zones may be established where one 120 Volt thermostat controls more than one heater provided the total heater electrical load does...

Page 16: ...urner to gas supply with flexible gas connector 3 A drip leg must be installed in the gas line at the heater inlet connection tee followed by a pipe drop to the heater Failure to provide a drip leg co...

Page 17: ...e Hose and Hose Couplings for Conducting Propane and Natural Gas CSA 8 1 and of a length of 36 6 in 91 15 cm with an ID of a least in 12 7 mm In USA an approved Stainless Steel Flexible Gas Connector...

Page 18: ...rm to local codes Provide a 1 8 in 3 2 mm NPT plugged tapping accessible for test gauge connection immediately upstream of the gas supply connection to the heater Test for leaks All gas piping and con...

Page 19: ...allation instructions contravene this manual e g vent lengths vent clearances number of elbows transitions required terminations etc defer to the specifications outlined in the venting system s manual...

Page 20: ...with inputs over 100 000 BTUH Within 36 in 91 5 cm of a window or door that can be opened in any building any non mechanical air supply inlet to any building or of the combustion air inlet of any oth...

Page 21: ...a cold or unheated area where the ambient temperature is likely to produce condensation of the flue gases the vent pipe must be insulated with a suitable insulation material that is approved and speci...

Page 22: ...all be provided to supply and exhaust at least 4ft3 min 1000Btuh 0 38m3 min kW input of installed heaters Some local codes may require an electrical interlock to a dedicated exhaust fan Exhaust must b...

Page 23: ...orizontally or vertically and must be protected with a suitable screened cap to prevent pest debris infiltration of the duct Do not use termination caps that utilize a damper or flapper system See acc...

Page 24: ...24...

Page 25: ...25 EASY RADIANT WORKS ACCESSORIES NOTE FOR EXPANDED 4 ID END ORDER PART AC1190...

Page 26: ...26...

Page 27: ...uct AC1060 24V Thermostat AC1120 4 x 4 x 6 Exhaust Tee AC1072 x 36 Type I Gas Flex AC1210 3 5 Dia Emitter 90 Elbow AC1070 x 24 Stainless Steel Gas Flex AC1220 Combustion Air Intake Kit AC1080 Outside...

Page 28: ...s dommagnes mat riels de blessure ou la mort Le service d entretien qualifi e est responsible de l installation de crette trousse L installation n est pas ad quate no compl te tant que le bon fonction...

Page 29: ...ated valve with pictorial illustrations 4 A rating label indicating model no serial no btu hr rating orifice size and identification of the gas to which the appliance is to be converted The conversion...

Page 30: ...d pressure regulator cap screw Refer to chart below for manifold pressure and maximum and minimum gas pressures of the converted heater Gas Supply Natural Gas Propane Manifold Pressure 3 5 W C 10 0 W...

Page 31: ...ion occurs then the control itself is suspect and should be changed If the igniter operates and there is still no ignition then the gas valve is suspect Be sure that the main gas supply is on that the...

Page 32: ...l distributor or the manufacturer WARRANTY ALL Easy Radiant Works heaters are covered by a 4 year guarantee All heaters manufactured by Easy Radiant Works are warranted to the original user against de...

Page 33: ...CHNICAL SUPPORT INFORMATION This equipment has been factory fired and tested prior to shipment To ensure that site conditions are compatible with the heater s performance the following start up needs...

Page 34: ...INLET GAS SUPPLY PRESSURE WITH HEATER OPERATING WC GAS VALVE OUTLET Manifold PRESSURE WITH HEATER OPERATING WC WHAT IS THE LINE VOLTAGE READING AT THE HEATER VOLTS WHAT IS THE VOLTAGE READING AT THE I...

Page 35: ...35...

Page 36: ...erly earth grounded 5 Flame sense rod contaminated or in incorrect position 6 HSI element located in incorrect position 7 Hot surface element or flame sense rod wiring in good condition and properly c...

Page 37: ...37...

Page 38: ...38...

Page 39: ...r is energized If control system indicates Electronic Fan Timer the heat speed circulation air fan will be energized after the selected heat fan on delay Flame at main burner 6 Flashes System lockout...

Page 40: ...40 AB2017 H S I CONTROL MODULE...

Page 41: ...ller ONLY 7 wire C2 PIN 9 Black Igniter PIN 10 Orange Flame sensor IMPORTANT 10 and 12 Loop together for units with single flame sensor For EZM dual flame sense 10 and 12 lead to individual flame sens...

Page 42: ...operly earth grounded 5 Flame sense rod contaminated or in incorrect position 6 HSI element located in incorrect position 7 Hot surface element or flame sense rod wiring in good condition and properly...

Page 43: ...43...

Page 44: ...44 COMBUSTIBLE MATERIAL STORAGE WARNING SIGN...

Reviews: