Eastron SDM72DM User Manual Download Page 14

Eastron SDM72D-M User Manual V1.1

 

- 14 -

Holding Registers

 

30031 

Phase 1 power factor (1). 

Float 

None 

00 

1E 

30033 

Phase 2 power factor (1). 

Float 

None 

00 

20 

30035 

Phase 3 power factor (1). 

Float 

None 

00 

22 

30043 

Average line to neutral volts. 

Float 

00 

2A 

30047 

Average line current. 

Float 

00 

2E 

30049 

Sum of line currents. 

Float 

00 

30 

30053 

Total system power. 

Float 

00 

34 

30057 

Total system volt amps. 

Float 

VA 

00 

38 

30061 

Total system VAr. 

Float 

VAr 

00 

3C 

30063 

Total system power factor (1). 

Float 

None 

00 

3E 

30071 

Frequency of supply voltages. 

Float 

Hz 

00 

46 

30073 

Import active energy 

Float 

kWh 

00 

48 

30075 

Export active energy 

Float 

kWh 

00 

4A 

30201 

Line 1 to Line 2 volts. 

Float 

00 

C8 

30203 

Line 2 to Line 3 volts. 

Float 

00 

CA 

30205 

Line 3 to Line 1 volts. 

Float 

00 

CC 

30207

Average line to line volts.

4

Float

V

00

CE

30225

Neutral current.

4

Float

A

00

E0

30343 

Total active Energy (2) 

Float 

kWh 

01 

56 

30345 

Total reactive energy 

Float 

kVArh 

01 

58 

30385 

resettable total active energy 

Float 

kWh 

01 

80 

30389 

resettable import active energy 

Float 

kWh 

01 

84 

30391 

resettable export active energy 

Float 

kWh 

01 

86 

30397 

Net kWh (Import - Export) 

Float 

kWh 

01 

8C 

31281 

Total import active power 

Float 

05 

00 

31283 

Total export active power 

Float 

05 

02 

Instruction: 

(1)

The power factor has its sign adjusted to indicate the direction of the current. Positive refers to forward

current, negative refers to reverse current.

 

(2)

Total active energy equals to  export.

Holding register are used to store and display instrument configuration settings. All holding registers not listed 

in the table below should be considered as reserved for manufacturer use and no attempt should be made to 

modify their values. 

The holding register parameters may be viewed or changed using the Modbus Protocol. Each parameter is held 

in two consecutive 4X registers. Modbus Protocol Function Code 

03

 is used to read the parameter and Function 

B+G e-tech GmbH (EASTRON Germany) 

• 

www.eastron-germany.de 

[email protected] • Fax: 03574 467550

Summary of Contents for SDM72DM

Page 1: ...nal measurement IMP EXP Pulse Output RS485 Modbus Din rail mounting 35mm Direct connection up to 80A Better than Class 1 B accuracy SDM72DM multi function version Three Phase Four Wire Energy Meter User Manual V1 1 2021 B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 2: ...eral Specifications Voltage AC Un 3x230 400 V Voltage Range 80 120 Un Base Current Ib 10A AC Max Current Imax 100A AC Mini Current Imin 5 of Ib AC Starting current 0 4 of Ib Power consumption 2W 10VA for the voltage measuring circuit 4VA for the current measuring circuit Frequency 50 60Hz 10 AC voltage withstand 4KV for 1 minute Impulse voltage withstand 6KV 1 2uS wavform Overcurrent withstand 30 ...

Page 3: ...rt kWh RS485 Output for Modbus RTU For Modbus RTU the following RS485 communication parameters can be configured from the Set up menu Baud rate 1200 2400 4800 9600 19200 bps Parity none default odd even Stop bits 1 or 2 RS485 network address nnn 3 digit number 001 to 247 Modbus Word order Hi Lo byte order is set automatically to normal or reverse It cannot be configured from set up menu Environmen...

Page 4: ...51 indoor Material self extinguishing UL94V 0 Wiring PART 2 Operation Initialization Display When it is powered on the meter will initialize and do self checking Full Screen Software Version Pulse constant Total active energy kWh Total Import Export 5 2 6 1 Max read 999999 9 kWh B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 5: ...entry Confirmation After initialization and self checking program the meter display the measured values The default page is total kWh If the user wants to check other information please press the scroll button on the front panel Total active energy kWh Total Import Export Resettable partial kWh import energy export energy B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax ...

Page 6: ... User Manual V1 1 6 Total reactive energy Voltage L1 N Voltage L2 N Voltage L3 N L1 current L2 current L3 current L1 active power B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 7: ...1 7 L2 active power L3 active power Total active power L1 reactive power L2 reactive power L3 reactive power Total reactive power L1 Power factor B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 8: ... power factor L3 power factor Total Power factor Frequency Pulse output type Default kWh Pulse constant 1000imp Pulse constant Modbus Address Baud Rate B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 9: ...r 3 seconds Setting interface Setting statu Option Password Default 1000 Modbus address Rane 001 247 default 001 Buad rate Option 1200 2400 4800 9600 19200 bps default 9600 bps Parity Option NONE EVEN ODD default NONE Stop bit Option 1 2 default 1 B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 10: ...f pulse constant is 1000imp kWh pulse width will be fixed at 35ms Automatic Scroll display set Range 0 60 unit second default 0 means do not scroll Backlit time setting Option on 5 10 20 30 60 120 off unit minute default 60 minute System Option 3P4W 1P2W default 3P4W Password default 1000 Resettable partial energy Keep pressing button to exit the set up mold B G e tech GmbH EASTRON Germany www eas...

Page 11: ...Eastron SDM72D M User Manual V1 1 11 Wiring diagram NOTE Maximum Wire Size for Mainload 25mm Dimensions B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 12: ...Eastron SDM72D M User Manual V1 1 12 Installation B G e tech GmbH EASTRON Germany www eastron germany de info bg etech de Fax 03574 467550 ...

Page 13: ...ding the 30 parameter limit will cause a Modbus Protocol exception code to be returned Address Registe r Input Register Parameter Modbus Protocol Start Address Hex Description Length bytes Data Format Units Hi Byte Lo Byte 30001 Phase 1 line to neutral volts 4 Float V 00 00 30003 Phase 2 line to neutral volts 4 Float V 00 02 30005 Phase 3 line to neutral volts 4 Float V 00 04 30007 Phase 1 current...

Page 14: ...kWh 01 56 30345 Total reactive energy 4 Float kVArh 01 58 30385 resettable total active energy 4 Float kWh 01 80 30389 resettable import active energy 4 Float kWh 01 84 30391 resettable export active energy 4 Float kWh 01 86 30397 Net kWh Import Export 4 Float kWh 01 8C 31281 Total import active power 4 Float W 05 00 31283 Total export active power 4 Float W 05 02 Instruction 1 The power factor ha...

Page 15: ...ey parameters Length 4 byte Data Format Float r w 40019 Parity and stop bit 00 12 Write the network port parity stop bits for MODBUS Protocol where 0 One stop bit and no parity default 1 One stop bit and even parity 2 One stop bit and odd parity 3 Two stop bits and no parity Length 4 byte Data Format Float r w 40021 Modbus address 00 14 Write the network port node Address 1 to 247 for MODBUS Proto...

Page 16: ...ns backlit always on 121 means backlit always off Length 4byte Data Format Float r w 40087 Pulse 1 Energy Type 00 56 Pulse 1 Energy Type 1 import active energy 2 total active energy 4 export active energy default Length 4 byte Data Format Float r w 461457 Reset historical data F0 10 00 03 reset energy info Length 2 byte Data Format Hex wo 464513 Serial number FC 00 Serial number Length 4 byte Data...

Reviews: