EASTRON SDM630MCT User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 16
3
Set CT 1 value
Press
to enter the CT Ratio
setting screen. The range is from 0001 to
9999.
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
1
From the Set-up menu, use
and
buttons to select the PT option.
The screen will show the voltage PT
secondary voltage value. The default
value is 400V
2
Secondary PT setting
Press
to enter the PT
secondary voltage selection routine. The
range is from 100 to 500V
3
Set PT 1 value
Press
to enter the PT ratio
screen.
The range is from 0001 to 9999
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the pulse output 1—Units: Total kWh, Total kVArh