EASTRON SDM630-Modbus V2 User Manual
VoIPDistri.com - Voice over IP Distribution, Im Hagen 3, 33790 Halle Westfalen, Germany
Fon: +49 5201-73-00-30 | Fax: +49 5201-7829 | Mobil: +49 176 -204-2222-1
- 13 -
1
From the Set-up menu, use
and
buttons to select the Pulse
Rate option.
2
Press
to enter the selection
routine. The current setting will flash.
Note: When it
’
s dFt,
it means 2.5Wh/VArh
Use
and
buttons to choose pulse rate. On completion of the entry
procedure, press
to confirm the setting and press
to return to the main set
up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as
200, 100(default) or 60ms.
(It shows pulse width of 200ms)
1-1
From the Set-up menu, use
and
buttons to select the
Pulse width option.