background image

-

1

-

Double channel digital weekly time switch

ESRD-TPW2

Description

ESRD-TPW2 digital time switch are used for realization of time functions in

the control systems and automation. It operates according to the set time
schedule planned by the user.

There is an internal battery which can protect real time clock and all the

settings when the electric power supply is off.

Features

Operating instruction

Screen display and keys

Digital time switch with weekly program

10 year power reserve(lithium battery).

100 programs

Sealable cover of the front panel, easy setting by 4 keys.
Automatic summer/winter time switchover
Back-lighted LCD display
Holiday mode.
Double channels (each channel can be assigned an individual program)

Manual control by keys combination.

Menu

Ok

C1

C

2

Symbol legend

Automatic transfer of weekdays

1 2 3 4 5 6 7

Days of the week Monday, Tuesday, ...Sunday

24-264V AC/DC input supply.

Double-module, mounted on TH-35 rail.

Technical data

C1

Channel 1

C

2

Channel 2

Relay status

Automatic mode
Manual mode

Prog

Holiday mode
Winter time
Summer time
Program setting

Backlight display

After the external power supply is applied and then press any of four

keys, the backlight display will be illuminated. Otherwise, only symbols
are displayed on the screen.

Keys

Menu

Enter main menu

Back to main menu

Ok

Confirm selection

Select menu

Increase a numerical

value

C1

C1 manual operation

Select menu

Decrease a numerical

value

ok

C

2

C2 manual operation

Date display

DD- MM- YY,

20th.January.2014

Output - channel 2

Supply terminal A1

28 25 26

C2

A1

1

LCD display

C1

C

2

Maximum pilotable power

Output - channel 1

Menu

ok

C1

18 15 16 A2

Control keys

Supply terminal A2

Supply terminals

A1-A2

Rated voltage

AC/DC 24-264V

Rated frequency

50/60Hz

Power consumption

2W

Supply volltage tolerance

±10%

Number of channels

Double channels

Number of programs

100

Program

weekly program, daily program

Mode of work

manual, automatic, holiday

Summer/winter time

off, automatic changes

Time tolerance

1s/day at 25°C

Power reserve

10 year

Data readout

LCD display with backlight

Number of contacts

2 C/O

Current of contacts

16A/250V AC1

Switching capacity

4000VA/AC1

,

384W/DC

Mechanical life

10

6

Electrical life

10

5

Rated insulation voltage

250V

Protection degree

IP20

Pollution degree

3

Altitude

2000m

Ambient temperature

-20°C~55°C

Permissable relative humidity

50%(40°C,without condensation)

Storage temperature

-30°C~70°C

Wire size

1mm

2

~ 4mm

2

Tightening torque

0.5Nm

Mounting

TH-35 Rail(EN60715)

Dimensions

90*36*64mm

Standard

IEC60947-1/IEC60947-2-7

2300W

2300W

1000W

500W

500W

Summary of Contents for ESRD-TPW2

Page 1: ...ght display will be illuminated Otherwise only symbols are displayed on the screen Keys Menu Enter main menu Back to main menu Ok Confirm selection Select menu Increase a numerical value C1 C1 manual operation Select menu Decrease a numerical value ok C2 C2 manual operation Date display DD MM YY 20th January 2014 Output channel 2 Supply terminal A1 28 25 26 C2 A1 1 LCD display C1 C2 Maximum pilota...

Page 2: ... 3 4 Prog Prog Prog Prog OK OK OK OK Select DATE and press Ok key Choose adequate year with keys and press Ok key adjusting range is 2000 2095 Choose adequate month with keys and press Ok key Choose adequate day with keys and press Ok key Exit from the setting by pressing Menu key 5 Long press Long press Prog Menu 0 5s increase the numerical value quickly 0 5s decrease the numerical value quickly ...

Page 3: ... memory is full new program will not be created symbol appears on the screen 4 Select CHANNEL 1 or CHANNEL 2with and press Ok key 5 Display the output state of channel 1 Choose ON or OFF with keys and then press Ok key 6 Display the output state of channel 2 Choose ON or OFF with keys and then press Ok key 7 Set the hour with keys and then press Ok key 8 Set the minute with keys and then press Ok ...

Page 4: ... increase the numerical value quickly Long press 0 5s decrease the numerical value quickly If is selected program operation is enabled for flashing day If is selected program is not used for flashing day 10 Exit from the setting by pressing Menu key Delete a program 2 3 4 1 2 3 Prog Prog Prog C1 OK OK OK 8 7 Prog OK 10 Prog 1 Select PROGRAM and press Ok key 2 Select DELETE and press Ok key 3 Selec...

Page 5: ...key 3 Set the start year of holiday with keys and press Ok key 11 Return to HOLIDAY menu Exit from the setting by pressing Menu key 4 Set the start month of holiday with keys and press Ok key 5 Set the start day of holiday with keys and press Ok key 6 Set the end year of holiday with keys and press Ok key 7 Set the end month of holiday with keys and press Ok key 8 Set the end day of holiday with k...

Page 6: ...matically A1 15 A2 18 16 25 28 26 Menu ok WARNING Please disconnect the power supply before installation Connect the supply voltage as stated on the product 1 The device should be installed operated and maintained by qualified personnel 2 Don t dismantle or repair the device whether it operates normally otherwise no responsibility is assumed by manufacturer or seller 3 Please refer to wiring diagr...

Reviews: