17
41
Lithium battery
“
SOC
”
discharge stop
Default:6%
1.When the battery capacity of the
lithium battery is lower than the set
point, the inverter stops
discharging and output will be
turned off.
setting range :1% to 60%
setting increase or decrease of
1%.
2.when the communication
connection between the lithium
battery and the inverter is normal,
“USER” will be displayed next to
the battery icon on ten display
screen.
42
Lithium battery
“
SOC
”
charge stop
Default:96%
1.When the battery capacity of the
lithium battery is higher than the
set point, the inverter stops
charging
setting range :61% to 100%
setting increase or decrease of
1%.
2.when the communication
connection between the lithium
battery and the inverter is normal,
“USER” will be displayed next to
the battery icon on ten display
screen
44
Reconnection
delay time
When the utility is connected, the
waiting time can be set. After
reaching the waiting time, the utility
will start working.
Range:0-999S
50
Battery activation
Activation activation (default)
Activation activation
:
When the AC is connected to the
inverter and turned it on. And if the
battery cannot be detected, the
battery will be activated. (If it fails,
disconnect AC and restart)
ON
Manual activation :
In this mode, select "On", connect
the AC or PV to the inverter, and
turn it on. If the battery is not
detected, an activation of the
battery is performed. "Off" will be
returned if activation is successful
or fail
OFF