Table 7 Electrical and Water Connections, Continued
A
Service Hose - suggested length to reach the Processor and Replenisher Tanks.
B
⁄
1
2
in. NPT Check Valve
C
Kodak Thermostatic Mixing Valve ⁄
1
2
in. NPT available from Eastman Kodak Company,
Part No. 467621. Not supplied with the Processor.
IMPORTANT
A mixing valve is not required for the processor if incoming water temperature is between
4
°
and 29.4
°
C (40
°
and 85
°
F).
D
Shutoff Valves ⁄
1
2
in. NPT. Two additional required. Available from Eastman Kodak Company,
Part No. 459981. Not supplied with the Processor.
E
Cold Water Supply ⁄
1
2
in. NPT
F
30 AMP - 2 POLE, Thermo-magnetic Circuit Breaker. Locate safe distance from water service.
Not supplied with the Processor.
G
Shutoff Valves ⁄
1
2
in. NPT. Two additional required. Available from Eastman Kodak Company,
Part No. 459981.
H
Hot and Cold Water Supply ⁄
1
2
in. NPT.
I
⁄
1
2
in. NPT Union. Locate as close to the Processor as possible.
NOTE
• The processor is UL listed, CSA certified. Specifications are subject to change without notice.
• Follow local electrical and plumbing codes.
18
1C7070
Summary of Contents for Kodak RP X-Omat Processor M6B
Page 4: ...BLANK PAGE 4 1C7070 ...