EA660 Modular UPS
User manual & Operation explain
13
A B C-1 C-2 C-3
1
、
A is no-source output dry contact, two pins as one pair(see the picture above)
。
no-source dry
contacts controled by relay; each pair of the dry contact connection is shown below (AC type and DC
type)
:
Input AC
:
input DC
:
Alarm correspondance see below
:
Mark
Mode
Dry contact pair connection
Two ends of the dry contact disconnected
LOADINV
Inverter output
System in inverter output mode
System in non-inverter output mode
LOADBYP
Bypass output
System in bypass output mode
System in non-bypass output mode
INVFAIL
Inverter failure
System inverter votage abnormal
System inverter votage normal
BYPFAIL
Bypass Failure
System bypass input voltage abnormal
System bypass input voltage normal
Note
:when input AC, the max voltage is 277V,max current is 7A;when
input DC, the voltage is 24V.