background image

3

 PLUMB INLET, OUTLET & DRAIN

 

 Remove  the  red  plastic  caps  from  the  softener  inlet,  outlet 

and  drain.  Run  the  pipe-work  from  the  bypass  to  the  water 

softener  using  WRAS  approved  flexible  hose.  Connect  Hose 

connectors, nuts and washers as diagram. 

 

 Connect the 3/8” drain tube via the air gap fitting by pushing the 

tube firmly into the connection. Run the tube to a convenient 

drain and connect to the drain via the air gap fitting. If the drain 

runs outside it must be protected from freezing. 

Important  note:  If  the  water 

pressure is 2 bar or less the length 

of the drain tube 

must  not  exceed 

3m 

and 

the 

discharge  point 

should be below 

the  top  of  the 

softener. 

The 

length  of  the 

drain  tube  may 

be 

increased 

by  1m,  and  the 

discharge  point 

above  the  top  of 

the  softener  may  increase  by 

0.5m, for each 1 bar above 2 bar.

15mm Indirect system

On a traditional indirect system 

with a roof storage tank the 

pressure limiting valve should 

be installed after the rising main 

stopcock and before the bypass set. 

It may be installed before or after 

the hard water tee to the outside 

tap and drinking tap etc.

22mm Direct system

On the more modern direct system 

there is normally a 3 bar pressure 

limiting valve. This must always be 

installed after the water softener 

bypass. If you connect the 3 bar 

pressure reducing valve before 

the water softener there will be 

insufficient flow.

22mm Direct system

Where you have a direct heating 

system with the inlet pressure 

above 6 bar then an additional 

pressure limiting valve should be 

fitted after the stopcock and before 

the bypass. Note that the 3 bar 

pressure limiting valve must always 

be installed after the bypass.

5 bar pressure 
limiting valve

4

  PLUMB OVERFLOW

 

 Connect  the  overflow  hose  to  the 

overflow  elbow  on  the 

side  of  the  cabinet. 

No  securing  clip  is 

necessary  as  it  is  not 

under  pressure.  The 

hose  should  be  run 

downhill  all  the  way 

and  terminate  at  the 

exterior of the building 

if possible.

Outlet
Washer

Washer

Inlet

Drain

Where to fit a pressure reducing valve

3 bar pressure 
limiting valve

3 bar pressure 
limiting valve

5 bar pressure 
limiting valve

1

  DRAIN RISING MAIN

 

 Before cutting the rising main, turn off the stopcock and open an 

upstairs tap that is fed from the roof storage tank. Run sufficient 

water so that the ball valve feeding the tank opens. Then turn on 

the kitchen sink cold tap and let it run until it stops. Your rising 

main is now empty.

2

  INSTALL CHECK 

VALVE & BYPASS

 

 Cut  the  rising  main  and 

fit  the  three  valves  as 

shown  to  form  a  bypass. 

Install  proprietary  valves 

with  direction  of  flow  as 

indicated. Garden taps and 

hard  water  drinking 

taps, if fitted, should 

be  teed  off  before 

the bypass. You may have 

to  run  additional  pipe-

work to alter the existing 

plumbing.  A  check  valve 

(complying  with  BS6282) 

must  be  fitted  in  the  rising 

main before the bypass. 

SEE POINT 3

Reviews: