EAS Electric ETH-KH160 Installation And Owner'S Manual Download Page 2

1

CONTENIDOS

PÁGINA

1. 

PRECAUCIONES

.............................................................................1

2. 

ACCESORIOS Y REFRIGERANTE

..................................................2

3. 

ANTES DE LA INSTALACION

........................................................2

4. 

INFORMACIÓN IMPORTANTE SOBRE EL REFRIGERANTE 

UTILIZADO.........................................................................................3

5. 

SELECCIONANDO EL SITIO DE INSTALACION

.......................3

6. 

INSTALACION DE UNIDAD EXTERIOR

 ...................................4

7. 

INSTALAR EL TUBO DE CONEXIÓN

...........................................6

8. 

CABLEADO ELÉCTRICO

...............................................................8

9. 

 FUNCIONAMIENTO DE PRUEBA

..............................................

10

10. 

PRECAUCIONES SOBRE FUGAS REFRIGERANTES

...............

10

11. 

Entrega del manual al cliente

.............................................

.

..............

11

12. 

OPERACIÓN Y RENDIMIENTO

.................................................

12

13. 

CÓDIGO DE MAL FUNCIONAMIENTO DE UNIDAD 

EXTERIOR

...................

.............................................

....................

13

14. 

SINTOMAS QUE NO SON PROBLEMAS

 ........

.

........................

15

15. 

SOLUCIÓN DE PROBLEMAS

....................................................

15

16. 

ESPECIFICACIONES TECNICAS

...................

.

...........................

17

 

17. 

INFORMACIÓN IMPORTANTE PARA EL REFRIGERANTE 

USADO

 .......

...............................................................................

...

18

 

PRECAUCIÓN

Nueva instalación de bomba de calor refrigerante

PRECAUCIONES

 

1) Asegúrese de que todas las regulaciones locales, nacionales e

internacionales estén satisfechas.
2) Lea detenidamente estas "PRECAUCIONES DE

SEGURIDAD" antes de la instalación.
3) Las precauciones descritas a continuación incluyen los

elementos importantes relacionados con la seguridad.

Obsérvalos sin falta.
4) Después del trabajo de instalación, realice una operación de

prueba para verificar si hay algún problema.

5) Siga el Manual del propietario para explicar cómo usar y

mantener la unidad al cliente.
6) Apague el interruptor de la fuente de alimentación principal (o

disyuntor) antes del mantenimiento de la unidad.
7) Pídale al cliente que guarde el Manual de instalación junto con

el Manual del propietario.

ESTA BOMBA DE CALOR ADOPTA AL NUEVO 

REFRIGERANTE HFC (R410A) QUE NO DESTRUYE LA 

CAPA DE OZONO.

● Las características del refrigerante R410A son: Fácil de

absorber agua, membrana oxidante o aceite, y su presión

es aproximadamente 1.6 veces más alta que la del

refrigerante R22. Acompañado con el nuevo refrigerante,

también se ha cambiado el aceite refrigerante. Por lo tanto,

durante el trabajo de instalación, asegúrese de que el

agua, el polvo, El refrigerante anterior, o el aceite de

refrigeración no entra en el ciclo de refrigeración.

● Para evitar la carga de un refrigerante y aceite de

refrigeración incorrectos, los tamaños de las secciones de 

conexión del puerto de carga de la unidad principal y las 

herramientas de instalación se cargan a partir del 

refrigerante convencional.

● En consecuencia, se requieren herramientas exclusivas

para el nuevo refrigerante (R410A):

Para conectar tuberías, use tuberías nuevas y limpias

diseñadas para R410A, y tenga cuidado de que no entre

agua o polvo. Además, no use la tubería existente porque

hay problemas con la fuerza de resistencia a la presión y

la impureza en ella.

PRECAUCIÓN

Para desconectar el aparato de la fuente de alimentación principal.

ADVERTENCIA

● Este dispositivo puede ser utilizado por niños de 8 años

en adelante y personas con capacidades físicas,

sensoriales o mentales reducidas o por falta de

experiencia y conocimiento si se les ha dado supervisión

o instrucciones sobre el uso del dispositivo de manera

segura y entienden el peligros involucrados Los niños no

deben jugar con el aparato. La limpieza y el mantenimiento

del usuario no deben ser realizados por niños sin

supervisión.

● Los niños deben ser supervisados   para asegurarse de

que no jueguen con el aparato.

● Solicite a un distribuidor autorizado o profesional de la

instalación calificado que instale / mantenga la bomba de

calor. Una instalación inadecuada puede provocar fugas

de agua, descargas eléctricas o incendios.

● Apague el interruptor principal de la fuente de

alimentación o el disyuntor antes de intentar realizar

cualquier trabajo eléctrico. Asegúrese de que todos los

interruptores de alimentación estén apagados. Si no lo

hace, puede provocar una descarga eléctrica.

● Conecte el cable de conexión correctamente. Si el cable

de conexión se conecta de manera incorrecta, las piezas

eléctricas podrían dañarse.

● Cuando mueva la bomba de calor para la instalación a

otro lugar, tenga mucho cuidado de no ingresar ninguna

sustancia gaseosa que no sea el refrigerante especificado

en el ciclo de refrigeración. Si el aire o cualquier otro se

mezcla con el refrigerante, la presión del gas en el ciclo de

refrigeración se vuelve anormalmente alta y puede como

resultado causa rotura de tubería y lesiones en personas.

Este  aparato  debe  conectarse  a  la  fuente  de  alimentación 

principal  mediante  un  interruptor  con  una  separación  de 

contacto  de  al  menos  3  mm.  El  fusible  de  instalación  debe 

utilizarse  para  la  línea  de  alimentación  de  esta  bomba  de 

calefacción.

V.2

Summary of Contents for ETH-KH160

Page 1: ...EAS THERMAL BIBLOCK MANUAL DE INSTALACIÓN Y MANUAL DE USUARIO MODELOS ETH 10VB ETH 12VB ETH 16VB V 2 ...

Page 2: ... unidad principal y las herramientas de instalación se cargan a partir del refrigerante convencional En consecuencia se requieren herramientas exclusivas para el nuevo refrigerante R410A Para conectar tuberías use tuberías nuevas y limpias diseñadas para R410A y tenga cuidado de que no entre agua o polvo Además no use la tubería existente porque hay problemas con la fuerza de resistencia a la pres...

Page 3: ...s terminales de forma segura Para evitar que las fuerzas externas aplicadas a los terminales afecten a los terminales Asegúrese de proporcionar conexión a tierra No conecte cables de tierra a tuberías de gas tuberías de agua pararrayos o cables de tierra para cables telefónicos Cumpla con las regulaciones de la compañía eléctrica local cuando realice el cableado de la fuente de alimentación Una co...

Page 4: ...d de polvo la unidad debe cubrirse No coloque ningún objeto o equipo encima de la unidad placa superior No suba se siente ni se pare encima de la unidad Asegúrese de tomar suficientes precauciones de acuerdo con las leyes y regulaciones locales pertinentes en caso de fugas de refrigerante 2 Cuando instale la unidad en un lugar expuesto a fuertes vientos ponga especial atención a los siguientes cas...

Page 5: ... mal funcionamiento de la máquina 1 Hay fugas de gas combustible 2 Hay mucho aceite incluido el aceite del motor ingrediente 3 Hay aire salado que rodea cerca de la costa 4 Hay gas cáustico el sulfuro por ejemplo que existe en el aire cerca de una fuente termal 5 Un lugar donde el aire caliente expulsado de la unidad exterior puede alcanzar la ventana de su vecino 6 Un lugar donde el agua del desa...

Page 6: ...ta unidad con tornillos para evitar que se derrumbe en caso de terremoto o viento fuerte Consulte la Fig 6 8 PRECAUCIÓN Al instalar la unidad exterior preste atención al lugar de instalación y al patrón de drenaje Para unidades de 4 8kW solo hay una salida de agua en la bandeja inferior Si se instala en una zona de temperatura ambiente baja por ejemplo la temperatura ambiente es inferior a 7 duran...

Page 7: ... Limpie la manta de goma del soporte de la tubería al lado de la tapa de la tubería de salida interior de la máquina mientras la parte trasera sale de las tuberías El cuerpo de la unidad Lado de la tubería del sitio Cortar desde arriba 7 3 Aislamiento térmico Realice el aislamiento térmico a las tuberías del lado del gas y del lado del líquido por separado La temperatura de las tuberías del lado d...

Page 8: ...vacío 1 Usar la bomba de vacío para hacer el vacío nunca usar refrigerante para expulsar el aire 2 La aspiración se debe realizar desde el lado del líquido y desde el lado del gas simultáneamente 3 Seleccione la fuente de alimentación para la unidad interior y la unidad exterior respectivamente 4 La fuente de alimentación tiene un circuito derivado específico con protector de fugas y un interrupto...

Page 9: ...onductores activos debe incorporarse en el cableado fijo de acuerdo con el Reglamento de cableado nacional La función reservada se indica en la tabla de líneas discontinuas los usuarios pueden seleccionarla cuando sea necesario Para evitar interferencias con la comunicación aumente un anillo magnético dentro y fuera de la línea de comunicación alrededor de 1 vuelta PRECAUCIÓN Cortocircuito A 32 10...

Page 10: ... Fuente de alimentación de W Phase para compresor W 4 Fuente de alimentación de la fase V para compresor V 5 Fuente de alimentación de U para compresor U 6 Puerto de salida N del módulo Pfc N_1 7 Puerto de salida P del módulo Pfc P_1 8 Puerto de entrada para inductancia Pfc L_1 L_1 9 Puerto de entrada para inductancia Pfc L_2 L_2 10 11 13 9 8 7 6 5 4 3 2 1 10 Puerto de entrada N para el módulo Pfc...

Page 11: ... un ventilador mecánico para reducir el espesor del refrigerante en un nivel crítico ventilar regularmente 4 Instale la instalación de alarma de fugas relacionada con el ventilador mecánico si no puede ventilar regularmente 9 10 3 4 5 6 7 8 1 phase 10 16kW PCB B 1 Puerto para interruptor de presión CN12 2 Puertos para sensor de temperatura de succión CN24 3 Puertos para sensor de presión CN28 4 Pu...

Page 12: ...es seguro y normalmente no tiene fugas Solicite a su distribuidor la instalación de la bomba de calor La instalación incompleta realizada por usted mismo puede provocar una fuga de agua una descarga eléctrica y un incendio Pregunte a su distribuidor por mejoras reparaciones y mantenimiento La mejora reparación y mantenimiento incompletos pueden provocar fugas de agua descargas eléctricas e incendi...

Page 13: ...tasquen Esta forma de ventana es la salida de disipación de calor de los componentes si se atasca causará que los componentes acorten su vida útil debido al sobrecalentamiento durante mucho tiempo La temperatura del circuito de refrigerante será alta mantenga el cable de interconexión alejado del tubo de cobre Si el refrigerante gotea en la habitación el contacto con el fuego de un quemador un cal...

Page 14: ... de la bomba de calor ha configurado el modo de funcionamiento entonces la bomba de calor no puede funcionar en modos distintos a los predefinidos El modo de espera o Sin prioridad se mostrarán en el Panel de control 12 4 Característica de protección del compresor 12 5 Funcionamiento de refrigeración y calefacción El motor en la unidad interior continuará funcionando durante 20 30 segundos para el...

Page 15: ...r local P6 Módulo transductor de protección Póngase en contacto con su distribuidor local P9 Protección del motor del ventilador de CC Póngase en contacto con su distribuidor local PC Otra protección que no se puede mostrar en la interfaz de usuario Póngase en contacto con su distribuidor local Pd La temperatura del intercambiador de la unidad exterior T3 es demasiado alta Póngase en contacto con ...

Page 16: ...a unidad se utiliza por primera vez en mucho tiempo Esto es porque el polvo ha entrado en la unidad La unidad puede absorber el olor de las habitaciones muebles cigarrillos etc y luego emitirlo nuevamente Síntoma 7 el ventilador de la unidad exterior no gira Durante la operación La velocidad del ventilador se controla para optimizar la operación del producto La lámpara de operación parpadea rápida...

Page 17: ... el intercambiador de calor de la unidad interior están sucios El filtro de agua está sucio La entrada salida de las unidades interiores exteriores está bloqueada La luz del sol brilla directamente Demasiado recurso de calor Temp Al aire libre es muy alta Fuga de refrigerante o falta de refrigerante Espera el regreso del poder Encienda el poder Replicación Reemplace las baterías o revise el contro...

Page 18: ...Tuberia de gas Tuberia de liquido Conexión de drenaje Max longitud de tubería 50m Max diferencia de altura cuando la unidad exterior está al revés 30m Max diferencia de altura cuando la unidad exterior está a la baja 25m Modo calor Modo frio Modo de agua caliente sanitaria φ9 52 DN15 Rango de temperatura ambiente de operación 20 35 5 46 20 43 Fin coil Refrigerante R410A Peso Conexiones φ15 9 220 2...

Page 19: ...quivalente o más pero de menos de 500 toneladas de equipos de CO2 al menos cada seis meses o donde se instala un sistema de detección de fugas al menos cada 12 meses 4 Para equipos que contienen gases fluorados de efecto invernadero en cantidades de 500 toneladas de CO2 equivalente o más al menos cada tres meses o donde se instala un sistema de detección de fugas al menos cada seis meses 5 El equi...

Page 20: ...rrosión aniónicos catiónicos mezcla de ambos o productos filmógenos que bloquean las micropilas existentes evitando reacciones de corrosión y el desprendimiento de oxígeno Cuando se utilicen inhibidores u otros productos químicos limpiadores lea las instrucciones del fabricante y su compatibilidad con los materiales que componen la instalación Anticongelante En caso de que la instalación vaya a fu...

Page 21: ...CONTROL POR CABLE CON PROGRAMACIÓN SEMANAL MANUAL DE INSTALACIÓN Y MANUAL DE USUARIO MODELO ECRTH V 2 V 2 ...

Page 22: ...n los residuos domésticos no clasificados NO intente desmontar el sistema sin ayuda profesional El desmontaje del sistema el uso del refrigerante del aceite y de los componentes se debe realizar por personal cualificado Los trabajos de instalación y mantenimiento deben cumplir con la legislación vigente Las unidades se deben tratar en un centro de tratamiento especializado para ser recicladas y re...

Page 23: ...epósito Va al próximo paso tras programar la selección del menú confirma una selección introduce un submenú dentro de sus opciones 2 2 Iconos de estado Función desinfección activada Función Holiday away home Vacaciones fuera en casa Modo Silent activado Silencio Resistencia de apoyo activada Compresor funcionando Detenido Modo Calefacción Modo Refrigeración Modo Auto Indica el modo que se esta eje...

Page 24: ...e el usuario Página de inicio 2 Climatización controlada por el panel de control ACS WATER FLOW TEMP en NON ROOM TEMP en YES El panel de control muestra la siguiente página principal NOTA En este caso el panel de control controlará la temperatura de la habitación por lo que se debe tener en cuenta dónde se instala En ajustes iniciales ir a FOR SERVICEMAN TEMP TYPE SETTING ver AJUSTE TIPO CONTROL T...

Page 25: ...emperatura de agua panel de control ACS WATER FLOW TEMP en YES ROOM TEMP en YES El panel de control muestra la siguiente página principal y adicional En ajustes iniciales ir a FOR SERVICEMAN TEMP TYPE SETTING ver AJUSTE TIPO CONTROL TEMP en el manual de la unidad interior o monobloc y ajustar TEMP TYPE SETTING de la siguiente forma En ajustes iniciales ir a FOR SERVICEMAN TEMP TYPE SETTING ver AJU...

Page 26: ... botón UNLOCK El icono desaparecerá el control se puede operar El control estará bloqueado si no se pulsa ningún botón durante un tiempo unos 60 segundos para ajustar ese tiempo consulte la sección 6 7 INFORMACIÓN DE MANTENIMIENTO Si el control está desbloqueado mantenga pulsado el botón unlock el control quedará bloqueado 5 2 Encendido Apagado ON OFF Use el panel de control para encender o apagar...

Page 27: ...RMOSTATO AMBIENTE en el manual de la unidad interior o monobloc la unidad solo se podrá encender y apagar mediante el termostato ambiente externo el panel de control indicará Si DUAL ROOM THERMOSTAT termostato ambiente doble está en YES ver TERMOSTATO AMBIENTE en el manual de la unidad interior o monobloc Si el termostato de refrigeración está apagado el de calefacción está encendido y la unidad e...

Page 28: ...a OK y sale de la página pulsando el botón BACK el modo también es efectivo si el cursor se ha movido al modo de funcionamiento Si solo se permite el modo calefacción se visualizará El modo de funcionamiento no se puede cambiar ver AJUSTE MODO REFRIGERACIÓN en el manual de la unidad interior o monobloc Si selecciona El modo de funcionamiento es Siempre modo calefacción Siempre modo refrigeración C...

Page 29: ...una vez más y el punto sin color cambia a No se ha seleccionado el temporizador 1 Use para moverse y use para ajustar el tiempo y la temperatura Se pueden ajustar seis períodos y seis temperaturas Por ejemplo Ahora son las 8 00 y hay una temp de 30 C Programamos PRESET TEMP como se muesta en la tabla siguiente INFORMACIÓN Cuando cambia el modo de funcionamiento el PRESET TEMP se apaga automáticame...

Page 30: ...S1 no se puede ajustar cuando la curva de temperatura está ajustada en ON o monobloc Si desea usar el modo calefacción seleccione HEAT MODE LOW TEMP Si desea usar el modo refrigeración seleccione COOL MODE LOW TEMP Puede seleccionar el ajuste de alta o baja temperatura para calefacción o refrigeración ver Tabla 1 8 Si selecciona ON se visualizará la página siguiente Use para moverse Pulse OK para ...

Page 31: ...ónar ON o OFF y use para moverse INFORMACIÓN Si CURRENT STATE está en OFF el COMFORT MODE no es válido Cuando se mueve el cursor a START END como la página siguiente Pulse OK o la tecla para ajustar la hora Aparecerá la página Use para moverse y use para ajustar la hora INFORMACIÓN Si CURRENT STATE está en ON y ECO TIMER está en OFF COMFORT MODE sale hasta que se activa el ECO MODE Si la hora de e...

Page 32: ...os al ajustar OPERATE DAY y START Si OPERATE DAY se ajusta en FRI Viernes y el START encendido se ajusta a las 23 00 la función de desinfección se activará el viernes a las 23 00 Si CURRENT STATE está en OFF DISINFECT no es válido Si la función de desinfección está activada se visualizará la página siguiente 6 3 2 FAST DHW ACS Rápida La función FAST DHW se usa para forzar el sistema a funcionar en...

Page 33: ...UMP Pulse OK Aparecerá la siguiente página Moverse a pulsar OK para seleccionar o eliminar se ha seleccionado el temporizador se ha cancelado el temporizador Use las teclas para moverse y use para ajustar los parámetros Por ejemplo ha ajustado el parámetro de DHW PUMP Ver el manual de la ud interior o monobloc para más información AJUSTES INICIALES AJUSTES TIPO CONTROL TEMP El tiempo de funcionami...

Page 34: ...ura está fuera del rango del modo Aparecerá la siguiente página Ejemplo Ajuste de los seis temporizadores La unidad funcionará como sigue El funcionamiento del panel de control es con los siguientes horarios Si la hora de encendido es la misma que la de apagado en un temporizador el ajuste no será válido INFORMACIÓN 6 4 2 WEEKLY SCHEDULE Programación semanal Si la función TIMER temp diario está ac...

Page 35: ...oridad y PRESET TEMP o WEATHER TEMP SET tienen la prioridad más baja PRESET TEMP o WEATHER TEMP Los valores ajustados dejan de ser válidos cuando validamos los valores de ECO o COMFORT Debemos volver a ajustar PRESET TEMP o WEATHER TEMP Los valores ajustados serán válidos si ajustamos ECO MODE o COMFORT MODE no válidos No se afectan ni TIMER ni WEEKLY SCHEDULE cuando son válidos los valores de ECO...

Page 36: ...cripción Si el CURRENT STATE está en OFF SILENT MODE no es Cuando selecciona SILENT LEVEL y pulsa OK o Aparecerá la siguiente página válido Puede usar para seleccionar el nivel 1 ó 2 Pulse OK Si se selecciona TIMER pulse OK para acceder aparecerá la siguiente página Hay dos temporizadores para ajustar Moverse a pulsar OK para seleccionar o borrar Si se borran los dos horarios el SILENT MODE funcio...

Page 37: ...arla Período Después Se usarán sus programaciones normales Se usarán los ajustes de vacaciones Para activar o desactivar el modo HOLIDAY HOME Vaya a MENU OPTIONS HOLIDAY HOME Pulse OK Aparecerá la página siguiente Use ON OFF para seleccionar OFF o ON y use para moverse y ajustar Si el CURRENT STATE está en OFF el HOLIDAY HOME está en OFF Si el CURRENT STATE está en ON en HOLIDAY HOME está en ON Us...

Page 38: ...ISPLAY para ajustar la pantalla del control 6 7 2 Como acceder al menú información de mantenimiento Ir a MENU SERVICE INFORMATION Pulse OK Aparecerá la siguiente página En la función SERVICE CALL se pueden ver los teléfonos de contacto El instalador puede introducir su número Véase FOR SERVICEMAN ERROR CODE se usa para mostrar el error cuando ocurre y se muestra el significado del código de error ...

Page 39: ...CEMAN Ajuste de la composición del sistema Ajuste de los parámetros 6 9 2 Cómo acceder a los Ajustes Iniciales Vaya a MENU FOR SERVICEMAN Pulse OK FOR SERVICEMAN se usar para realizar la configuración inicial del sistema Los usuarios finales NO deben cambiar los ajustes de este menú FOR SERVICEMAN se usar para realizar la configuración inicial del sistema Los usuarios finales NO deben cambiar los ...

Page 40: ... STATE FROM UNTIL SCHEDULE DISPLAY LANGUAGE BACKLIGHT BUZZER SCREEN LOCK TIME TIME CURRENT TIME CURRENT DAY DOMESTIC HOT WATER DHW DISINFECT FAST DHW TANK HEATER DHW PUMP OPTIONS SILENT MODE HOLIDAY AWAY HOLIDAY HOME BACKUP HEATER CHILD LOCK COOL HEAT TEMP ADJUST COOL HEAT MODE DHW TEMP ADJUST DHW MODE SERVICE INFORMATION SERVICE CALL ERROR CODE PARAMETER DISPLAY FOR SERVICEMAN DHW MODE SETTING CO...

Page 41: ...T1_AHS_OFF t_AHS_DELAY 13 2 PREHEATING FOR FLOOR FLOW SET TEMPERATURE RETURN TEMPERATURE PREHEATING TIME OPERATE PREHEATING FOR FLOOR 13 3 FLOOR DRYING UP DRYING UP TIME HIGE TEMP TIME DRYING DOWN TIME PEAK TEMPERATURE START TIME START DATE OPERATE FLOOR DRYING UP 2 COOL MODE SETTING COOL MODE T1S RANGE T4CMAX T4CMIN dT1SC dTSC t_INTERVAL_C HEAT MODE T1S RANGE T4HMAX T4HMIN dT1SH dTSH t_INTERVAL_H...

Page 42: ...22 Tabla 1 Curva de temperatura ambiente en el ajuste de baja temperatura para calefacción Tabla 2 Curva de temperatura ambiente en el ajuste de alta temperatura para calefacción V 2 ...

Page 43: ...23 Tabla 3 Curva de temperatura ambiente en el ajuste de baja temperatura para refrigeración Tabla 4 Curva de temperatura ambiente en el ajuste de alta temperatura para refrigeración V 2 ...

Page 44: ...pulación puede provocar lesiones o daños materiales No instale el equipo en un lugar peligroso con posibles fugas de gases inflamables Si hay fugas de gases inflamables y no se reparan se puede incendiar el entorno del control Los cables deben ser compatibles a la corriente del control remoto cableado De lo contrario pueden provocarse descargas eléctricas o calentamientos y ocasionarse un incendio...

Page 45: ...60mm B C A 25 V 2 ...

Page 46: ...onamiento anormal por favor en primer lugar desconecte la fuente de alimentación y póngase en contacto con nuestro servicio la postventa SAT Para consular su servicio técnico más cercano acceda a la página web www easelectric es V 2 ...

Page 47: ...EAS THERMAL BIBLOCK INSTALLATION S AND OWNER S MANUAL MODELS ETH 10VB ETH 12VB ETH 16VB V 2 ...

Page 48: ...harging port of the main unit and installation tools are charged from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please be care so that water or dust does not enter Moreover do not use the existing piping because there are problems with pressure resistance for...

Page 49: ... terminals from affecting the terminals Be sure to provide grounding Do not connect ground wires to gas pipes water pipes lightning rods or ground wires for telephone cables Conform to the regulations of the local electric company when wiring the power supply Inappropriate grounding may cause electric shock Do not install the heat pump in a location subject to a risk of exposure to a combustible g...

Page 50: ... damage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as workplace In case of construction works e g grinding works where a lot of dust is created the unit must be covered Do not place any objects or equipment on top of the unit top plate Do not climb sit or stand on top of the unit Be sure ...

Page 51: ... leakage 2 There is much oil including engine oil ingredient 3 There is salty air surrounding near the coast 4 There is caustic gas the sulfide for example existing in the air near a hotspring 5 A place the heat air expelled out from the outdoor unit can reach your neighbor s window 7 A place where the drain water does not make any problem 6 A place that the noise interferes your neighbors every d...

Page 52: ...t from collapsing in case of earthquake or strong wind Refer to Fig 6 8 CAUTION While installing the outdoor unit pay attention to the installation place and the drainage pattern For 4 8kW model units there is only one water outlet on the bottom pan If it s installed at low ambient temperature zone such as the ambient temperature is lower than 7 for a long period some heating devices should be ins...

Page 53: ...o avoid the pest processing into and destroy the components Please wipe off the piping support rubber blanket beside the inner outlet pipe cover of the machine while back side getting out pipes The unit body Affiliated heat pump belt Site pipe side Cut from upward 7 3 Heat Insulation Do the heat insulation to the pipes of gas side and liquid side separately The temperature of the pipes of gas side...

Page 54: ...ous gas 7 7 Air Purge with Vacuum Pump 1 Using vacuum pump to do the vacuum never using refrigerant to expel the air 2 Vacuuming should be done from both liquid side and gas side simultaneously 3 Please select power source for indoor unit and outdoor unit respectively 4 The power supply has specified branch circuit with leakage protector and manual switch 5 Outdoor unit and indoor unit conncet wit...

Page 55: ...n the fixed wiring according to the National Wiring Regulation The reserved function is indicated in broken line table users can select it when necessary To prevent interference with communication increase a magnetic ring inside and outside communication line around 1 lap CAUTION Circuit Breaker A 32 4 16 Indoor Unit Power Phase Voltage and Frequency 1 Phase or 3 Phase 220 240V 50Hz 380 415V 50Hz ...

Page 56: ...ase 4 6 8kW 9 1 4 5 6 7 3 8 9 10 11 2 1 To main board CN101 CN105 2 Compressor connection port U V W U V W 3 Input port N for IPM module N 4 Input port P for IPM module P 5 Input port for PFC inductance P1 P1 6 Input port for bridge Rectifiers P5 7 Input port for Bridge Rectifiers P6 8 Output port P of PFC P2 9 Input port for PFC inductance 3 P3 10 Output port N of PFC P4 11 18V P9 PCB A 1 phase 4...

Page 57: ...TE T4 temperature sensor port 8 TP temperature sensor port 9 YELLOW High pressure switch RED Low pressure switch 10 Th temperature sensor port 11 Pressure sensor port 12 Wire controller port 13 P N 18V port 14 To IPDU PFC 15 DC fan port 16 Compression electromechanical heating belt 17 4 way valve port 18 Transformer input port PCB A 2 4 5 6 7 8 9 10 11 12 13 15 14 16 17 18 3 1 PCB B 1 phase 4 8kW ...

Page 58: ...ed CN30 8 Port For Electrical Expansion Value CN22 9 Input Port For Live Wire CN1 10 Input Port For Neutral Wire CN2 11 Output Port For Neutral Wire CN3 12 Ourput Port For Live Wire CN4 13 Reserved CN7 14 Port For 4 way Value CN13 15 Port For Eletric Heating Tape CN14 16 Input Port For Transformer CN26 10 20 19 18 25 17 16 23 22 21 11 13 9 8 7 6 1 9 10 2 3 4 5 10 Input Port N For Pfc Module VIN N ...

Page 59: ... 6 7 8 4 5 6 7 11 10 9 8 1 Power supply L3 L3 2 Power supply L2 L2 3 Power supply L1 L1 4 Power supply N N 5 Ground wire GND_1 6 Power supply for load CN18 7 Power supply for main control board CN19 8 Power filtering L1 L1 9 Power filtering L2 L2 10 Power filtering L3 L3 11 Ground wire GND_2 1 2 3 8 3 2 Switch box main components 1 phase 10 12 14 16kW PCB A 3 phase 12 16kW PCB B 3 phase 12 16kW V ...

Page 60: ...mum cubage Calculate the refrigerant thickness Counter measure against over high thickness 3 Install mechanical ventilator to reduce the refrigerant thickness under critical level ventilate regularly 4 Install leak alarm facility related to mechanical ventilator if you can not regularly ventilate 10 11 1 Power supply for the main PCB CN250 2 Port for pressure sensor CN36 3 Port for sunction temper...

Page 61: ... work Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary Do not dispose of electrical appliances as unsorted municipal waste use separate collection facilities Contact you local government for information regarding the connection systems available If electrical appliances are disposed of in landfills or dumps hazardous sub...

Page 62: ...t install the heat pump at any place where flammable gas may leak out If the gas leaks out and stays around the heat pump a fire may break out The appliance is not intended for use by young children or infirm persons without supervision Young children should be supervised to ensure that they do not play with the appliance The outdoor unit window shades should be periodic cleaning in case of being ...

Page 63: ...t To increase efficiency the unit will start defrosting automatically about 1 10 minutes and then water will be drained out from outdoor unit During defrosting the fan motors in the outdoor unit will stop running If the Heat Pump Administrator has set running mode then the heat pump can not run on modes other than the presetted Standby or No Priority will be displayed in the Control Panel 12 4 Com...

Page 64: ...ng range Clean the outdoor coil If the coil is clean contact your local dealer P6 Transducer module protect Contact your local dealer P9 DC fan motor protect Contact your local dealer PC Other protection Which can not be display on the user interface Contact your local dealer Pd Outdoor unit exchanger temperature T3 too high protect Contact your local dealer L0 Inverter module error Contact your l...

Page 65: ... off odours When the unit is used for the first time in a long time This is because dust has gotten into the unit The unit can absorb the smell of rooms furniture cigarettes etc and then emit it again Symptom 7 The outdoor unit fan does not spin During operation The speed of the fan is controlled in order to optimize product operation The operation lamp is flashing rapidly twice every second This ...

Page 66: ...or too low System circuit is blocked Outdoor unit and indoor unit heat exchanger is dirty The water filter is dirty Inlet outlet of indoor outdoor units is blocked Sunlight directly shine Too much heat resource Outdoor temp is too high Leakage of refrigerant or lack of refrigerant Wait for the comeback of power Switch on the power ReplLocation Replace the batterises or check the controller Set the...

Page 67: ...60kg 76kg 99kg Gross weight 72kg 88kg 112kg Gas side Liquid side Drain connection Max piping length 20m 30m 50m Max differance in height when outdoor unit is upside 10m 20m 30m Max differance in height when outdoor unit is downside 8m 15m 25m Heating mode Cooling mode Domestic hot water mode φ9 52 DN15 Operation ambient temperature range 20 35 5 46 20 43 Fin coil Refrigerant R410A Weight Connectio...

Page 68: ...nnes of CO2 equipment at least every six months or where a leakage detection system is installed at least every 12 months 3 For equipment that contains fluorinated greenhouse gases in quantities of 500 tonnes of CO2 equivalent or more at least every three months or where a leakage detection system is installed at least every six months 4 Non hermetically sealed equipment charged with fluorinated g...

Page 69: ...itors a mixture of both or film forming products that block the existing micropiles must be added avoiding corrosion reactions and the release of oxygen When using inhibitors or other cleaning chemicals read the manufacturer s instructions and their compatibility with the materials that make up the installation Antifreeze In the case that the installation is going to work in refrigeration antifree...

Page 70: ...upervision or instruction concerning use of the appliance by a person responsible for their safety 2 Turn off the main power supply switch or breaker before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock 3 Perform installation work properly according to the Installation Manual 4 Install the heat pump securely in a location where the ba...

Page 71: ...ariable Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Decla...

Page 72: ...ble Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declared ...

Page 73: ...e Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declared ca...

Page 74: ...ariable Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Decla...

Page 75: ...iable Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declare...

Page 76: ...e Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declared ca...

Page 77: ...ariable Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Decla...

Page 78: ...iable Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declare...

Page 79: ... Capacity control For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heater Psup is equal to the supplementary capacity for heating sup Tj If Cdh is not determined by measurement then the default degradation coefficient is Cdh 0 9 Air to water heat pump Declared cap...

Page 80: ...V 2 WIRE CONTROL WITH WEEKLY PROGRAMMING OWNER S MANUAL MODEL ECRTH ...

Page 81: ... equipment or property damage 1 2 For the user If you are not sure how to operate the unit contact your installer The appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety C...

Page 82: ...iler is activated A malfunction occured Silent mode is activated The disinfect function is activated Holiday away home is activated Backup heater is activated The compressor is activated Desired temp DHW mode the desired temp will not change the desired temp will decrease the desired temp will increase TANK 55 C C 27 SET SET 08 30 C ON ON DHW MAIN 21 55 08 08 2015 SAT Tank temp Heat mode Cool mode...

Page 83: ... The system has the function including floor heating and domestic hot water The page will appear FHL1FHL2 FHLn TANK 55 C 27 SET C ON ON DHW ROOM 21 55 08 08 2015 SAT home page1 If the WATER FLOW TEMP is set YES and ROOM TEMP is set NON See FOR SERVICEMAN TEMPERATURE TYPE SETTING on installa tion ower s manual There will be only main page The system has the function including floor heating and dome...

Page 84: ...appear home page3 home page4 Main page FHL1FHL2 FHLn FCU1FCU2 FCUn ADDITION PAGE 21 55 08 08 2015 SAT ON ROOM 21 55 08 08 2015 SAT ON MAIN MAIN PAGE ADDITION PAGE TANK C 12 SET C ON ON DHW MAIN 21 55 08 08 2015 SAT 55 SET C 24 21 55 08 08 2015 SAT ON ROOM FHL1 FHL2 FHLn FCU1 FCU2 FCUn 4 MENU 4 1 About the menu structure 4 2 To go to the menu strcture From a home page press MENU Result The menu str...

Page 85: ... will disappear the interface can be controlled 5 2 Turning ON OFF controls The ON OFF of the unit can be controlled by the interface if the ROOM TEHERMOSTAT is NON see ROOM THERMOSTAT SETTING on INSTALLATION OWNER S MANUAL ON TANK 55 C SET C OFF DHW MAIN 21 55 08 08 2015 SAT 18 long press UNLOCK 1 When the cursor is on space operation mode side Including heat mode cool mode and auto mode press ON...

Page 86: ... by the room thermostat CONFIRM OK 2 When the cursor is on DHW operation mode Press ON OFF key to turn on off the DHW mode TANK C 12 SET C ON ON DHW MAIN 21 55 08 08 2015 SAT A 55 TANK C 12 SET C OFF ON DHW MAIN 21 55 08 08 2015 SAT A 55 5 3 Adjusting the temerature Press on home page the black cursor will appear TANK 55 C SET C ON ON DHW MAIN 21 55 08 08 2015 SAT A SCROLL ADJUST ON OFF ON OFF 18 ...

Page 87: ...Then the space operation mode is Always heat mode heat Always cool mode cool auto A Automatically changed by the software based on the outdoor temperature and depending on installer settings also the indoor temperature and takes monthly restrictions into account Note Automatic changeover is only possible under certain conditions See the FOR SERVICEMAN AUTO MODE SETTING on installation ower s menua...

Page 88: ...0 35 C 00 00 25 C 00 00 25 C 2 3 1 when the space operation mode is changed the PRESET TEMP is off automatically The PRESET TEMP function can be used in the heat mode or cool mode But if the operation mode is changed the PRESET TEMP function need reset again The running preset temperature is invalid when the unit is OFF It will run according to the next preset temperature when the unit turn on aga...

Page 89: ...l appear Press ON OFF The following page will appear PRESET TEMPERATURE PRESET TEMP OFF WEATHER TEMP SET ECO MODE HEAT MODE LOW TEMP ON OFF ON OFF 6 3 Domestic Hot WATER DHW 6 3 1 Disinfect DHW mode typically consists of the following 1 DISINFECT 2 FAST DHW 3 TANK HEATER 4 DHW PUMP The DISINFECT function is used to kill the legionella In disinfect function the tank temperature will be reached 65 7...

Page 90: ...s required and the heat pump system is operating for cooling or heating however there still is a demand from the hot water TANK HEATER function can be used to heat the water in tank Also even if the heat pump system fails TANK HEATER can be used to heat water in tank Use ON OFF key to select ON or OFF DOMESTIC HOT WATER DHW DIS INFECT OFF FAST DHW TANK HEATER OPERATE DAY DHW PUMP START FRI 23 00 C...

Page 91: ...O START 06 00 00 00 00 00 2 3 00 00 4 1 NO START 00 00 00 00 00 00 6 7 00 00 8 5 DIS INFECT FAST DHW TANK HEATER DHW PUMP DOMESTIC HOT WATER DHW SCROLL 2 2 NO START 06 00 00 00 00 00 10 11 00 00 12 9 NO START 00 00 00 00 00 00 14 15 00 00 16 13 DIS INFECT FAST DHW TANK HEATER DHW PUMP DOMESTIC HOT WATER DHW 1 2 NO START 00 00 00 00 2 3 00 00 4 1 NO START 00 00 00 00 00 00 6 7 00 00 8 5 DIS INFECT ...

Page 92: ...on is on the timer is off the later setting is effective If the Timer is activated is displayed on home page Move to press OK to select or unselect the timer is selected the timer is unselected six timers can be set If you want to cancel the TIMER you move the cursor to press OK the become the timer is invalid If you set the start time later than the end time or the temperature out of range of the...

Page 93: ...st reset the PRESET TEMP or WEATHER TEMP SET when we set the ECO or COMFORT invalid TIMER or WEEKLY SCHEDULE is not affected when ECO or COMFORT is valid TIMER or WEEKLY SCHEDULE is activated when the ECO or COMFORT is not running TIMER and WEEKLY SCHEDULE are at the same priority The after setting function is valid The PRESET TEMP becomes invalid when TIMER or WEEKLY SCHEDULE is valid The WEATHER...

Page 94: ...ATER OPTIONS CURRENT STATE SILENT LEVEL TIMER ON ENTER SILENT MODE SCROLL ADJUST If the silent TIMER is selected Press OK to enter the following page will appear HOLIDAY AWAY HOLIDAY HOME BACKUP HEATER OPTIONS SILENT MODE NO START 22 00 1 2 END 12 00 07 00 15 00 SCROLL If the two time are both unselected the silent mode will operate in all time Otherwise it will operate according as the time The h...

Page 95: ...ly ROOM heat mode enabled Use ON OFF to select OFF or ON and use to scroll and adjust If the CURRENT STATE is OFF the HOLIDAY HOME is OFF If the CURRENT STATE is ON the HOLIDAY HOME is ON Use to adjust the date HOLIDAY AWAY HOLIDAY HOME BACKUP HEATER OPTIONS ON 15 08 2015 17 08 2015 ENTER SILENT MODE SCROLL CURRENT STATE FROM UNTIL TIMER HOLIDAY AWAY HOLIDAY HOME BACKUP HEATER OPTIONS SILENT MODE ...

Page 96: ...R OK PARAMETER SERVICE INFORMATION SERVICE CALL LANGUAGE BACKLIGHT BUZZER SCREEN LOCK TIME EN ON ON 120SEC ERROR CODE SCROLL ENTER OK PARAMETER DISPLAY Use OK to enter and use to scroll Press OK the page will appear press OK to show the mean of the error code 12 30 08 08 2015 SAT E2 comunication fault between controller and indoor unit Please contact your dealer CONFIRM OK SERVICE INFORMATION DISP...

Page 97: ...N PARAMETER P2 COMP PRESSURE2 kPa POWER CONSUMPTION OKWH SCROLL 5 5 OPERATION PARAMETER T1B LEAVING WATER TEMP 2 25 C 30 C T2 PLATE F OUT TEMP 45 C T2B PLATE F IN TEMP 7 C T3 OUTDOOR EXCHANGE TEMP 7 C T4 OUTDOOR AIR TEMP 7 C T5 WATER TANK TEMP SCROLL 3 5 OPERATION PARAMETER COMP RUN TIME4 1000HOUR EXPANSION VALUE 240P 600 R MIN FAN SPEED 0 A BACKUP HEATER1 CURRENT 0 A BACKUP HEATER2 CURRENT T1 LEA...

Page 98: ...FROM UNTIL SCHEDULE DISPLAY LANGUAGE BACKLIGHT BUZZER SCREEN LOCK TIME TIME CURRENT TIME CURRENT DAY DOMESTIC HOT WATER DHW DISINFECT FAST DHW TANK HEATER DHW PUMP OPTIONS SILENT MODE HOLIDAY AWAY HOLIDAY HOME BACKUP HEATER CHILD LOCK COOL HEAT TEMP ADJUST COOL HEAT MODE DHW TEMP ADJUST DHW MODE SERVICE INFORMATION SERVICE CALL ERROR CODE PARAMETER DISPLAY INSTALLATION MENU DHW MODE SETTING COOL M...

Page 99: ...TE OPERATE FLOOR DRYING UP 2 COOL MODE SETTING COOL MODE T1S RANGE T4CMAX T4CMIN dT1SC dTSC t_INTERVAL_C 3 HWAT MODE SETTING HEAT MODE T1S RANGE T4HMAX T4HMIN dT1SH dTSH t_INTERVAL_H 11 TEST RUN AIR PURGE PUMP RUNNING COOL MODE RUNNING HEAT MODE RUNNING DHW RUNNING 12 SPECIAL FUNCTIONG 12 1 AIR PURGE 12 2 RREHEATING FOR FLOOR 12 3 FLOOR DRYING UP 13 AUTO RESTAR COOL HEAT MODE DHW MODE 9 SERVICE CA...

Page 100: ...6 36 35 35 34 34 33 33 32 32 31 31 30 30 30 7 T1S 40 40 39 39 38 37 37 36 36 35 35 34 34 33 33 32 32 31 31 30 30 8 T1S 41 41 40 40 39 38 38 37 37 36 35 35 34 34 33 32 32 31 31 30 30 20 T4 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 T1S 55 55 55 55 54 53 53 52 51 51 50 49 49 48 47 47 46 45 45 44 43 2 T1S 55 55 55 55 55 55 55 54 53 53 52 51 51 50 49 48 48 47 46 45 45 3 T1S 55 55 55 55 55 ...

Page 101: ...1S 25 21 18 14 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 1 T1S 20 18 18 18 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 2 T1S 21 19 18 18 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 3 T1S 22 20 18 18 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 4 T1S 23 21 18 18 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 5 T1S 24 22 20 18 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 6 T1S 25 23 21 19 T4 10 T4 15 15 T4 22 22 T4 30 30 T4 46 7 T1...

Page 102: ...1 31 30 30 30 30 30 30 30 30 30 30 30 8 37 36 35 35 34 34 33 33 32 31 31 31 30 30 30 30 30 30 30 30 Table6 The environment temperature curve of the high temperature setting for ECO mode T4 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 50 50 49 49 48 48 47 47 46 46 45 45 44 44 43 42 42 41 40 39 38 2 50 50 50 50 50 50 49 49 48 48 47 47 46 45 44 43 43 42 42 41 40 3 50 50 50 50 50 50 50 50 50...

Page 103: ...V 2 www easelectric es ...