TXV–CLP-KIT (07/15)
Page 24
Step 3:
The
Thermal Bulb must be positioned and
clamped to the suction tube as shown in the
example illustrated in Figure 13. The
Thermal Bulb and suction tube must be horizontal
regardless of the cased coil application (vertical or horizontal).
The Thermal Bulb must be positioned at the 3:00, 4:00, 8:00 or 9:00 positions on the suction tube,
as illustrated in Figure 13.
Figure 13. Thermal Bulb Positioning
Step 4:
Clamp the thermal bulb firmly against the
clean suction tube
extension and parallel to it,
as shown in Figure 14.
Isolate the Thermal Bulb from with a cold wet cloth while Nitrogen brazing the joints on the suction
line. After the suction line has cooled, apply the supplied cork tape insulation around the Thermal
Bulb to completely isolate it from the surrounding air, as shown in Figure 15.