HCM-410CP-IM (12/15)
Page 5
Installation
– Hybrid Cooling Module Placement
The Hybrid Cooling Module unit is placed as shown in Figure 2 relative to other components in the
EarthLinked
®
system.
The Hybrid Cooling Module is located outdoors and will be
connected
to the refrigerant line set (vapor tube) outside the building.
Figure 2. Hybrid Cooling Module Placement in EarthLinked
®
System
Location Requirements for the Hybrid Cooling Module:
1. Within 20 Feet of the earth loop line set. Minimize refrigerant line lengths.
2. No more than 20 feet higher than the earth loop manifolds.
3. With proper clearances around the unit:
24 inches minimum on the two sides and back (coil side)
36 inches minimum on the front (fan side)
4. Away from windows, patios, decks, etc., where unit operation sounds may disturb the
occupants.