How to program: 

 

Timing Example:- 

                                      
                                      RELAY :1   COMBINATION 1 : 
                                                        DLY   : 00.12.30 
                                                        ON     : 03.25.00 
               Above format is in HRS/MIN/SEC. 
 
 

 

Slide RUN/PROG switch to PROG mode; Relay & 
combination shows “1” and “DLY” & “MIN SEC” LED glows. 

 

Press “RELAY” button till display shows “1”. 

 

Press “combination” button till display shows ‘1’. 

 

Press “DLY/ON” button to select Delay time 
 (DLY led glows). 

 

Press “RANGE” button to select range as MIN SEC  
(MIN SEC led glows). 

 

Press “SELECT” MSD starts flashing. 

 

Press “ADVANCE” till display shows 1. 

 

Press “SELECT” again; 2

nd

 digit starts flashing. 

 

Press “ADVANCE” till display shows 2. 

 

Press “SELECT” again; 3

rd

 digit starts flashing. 

 

Press “ADVANCE” till display shows 3. 

 

Press “SELECT” again; 4

th

 (LSD) digit starts flashing. 

 

Press “ADVANCE” till display shows 0. 

 

Press “SELECT” again; the SET value is saved in memory & 
same SET value is copied to ON time of same 
combination. 

 

Press “DLY ON” button to select ON time (ON led glows). 

 

Press “RANGE” button to select range as HRS MIN  
(HRS MIN led glows). 

 

Press “SELECT” MSD starts flashing. 

 

Press “ADVANCE” till display shows 0. 

 

Press “SELECT” again; 2

nd

 digit starts flashing. 

 

Press “ADVANCE” till display shows 3. 

 

Press “SELECT” again; 3

rd

 digit starts flashing. 

 

Press “ADVANCE” till display shows 2. 

 

Press “SELECT” again; 4

th

 digit (LSD) starts flashing. 

 

Press “ADVANCE” till display shows 5. 

 

Press “SELECT” again, SET ON time is saved in memory. 

 

Same procedure shall be followed for different ranges 
and different combinations. 
 

                 NOTE: ON time setting shall be always more than DLY time  
                             in all ranges. 
 

 

  

OPERATING 

CONDITION/

MODE 

STATUS 

TIMING 

SEQUENCE

 

TIMING IN 

PROGRESS 

(TIP) 

TIMING 

COMPLETION

(TC) 

RELAY 

LED 

RELAY 

LED 

CHANNEL 

“0” 

DELAY TIME 

OFF 

OFF 

ON 

ON  

ON TIME 

ON 

ON 

OFF 

OFF 

CHANNEL”1

” & So on 

DELAY TIME 

OFF 

OFF 

ON 

ON  

ON TIME 

ON 

ON 

OFF 

OFF 

 

Function

 

Combination Switching of 
Outputs. 

Rated supply Voltage

 

85V TO 270V AC/DC 

Rated frequency

 

50 / 60Hz ± 5%

 

Power consumption

 

AC Approx. 20VA 
DC Approx. 10W 

Control output 

8 (8 NO contacts rated for 5A @ 
250V AC/28VDC resistive load) 

Start Signal

 

Potential free closure for a 
minimum of 250mSec. 

Reset Signal

 

Potential free closure 

Time range 

1Sec to 99Hrs 59Min 59Sec For 
Delay & ON 

Setting accuracy

 

± 0.2% ± 50mSec. 

Repeat accuracy

 

± 0.2% ± 50mSec. 

Recovery time 

2Sec minimum 

Variation due to voltage 
change 

± 1% max. ± 50mSec.  

Variation due to 
temperature change 

± 2% max. ± 50mSec.  

Variation due to 
frequency change            

± 1% max. ± 50mSec. 

Ambient temperature 

Operation:-10º C to + 55º C 
Storage :-25º C to +80º

 

Humidity 

MAX 85% RH @ 40ºC 

  Technical Specification     

 
 
 

 

       
        

   Disposition

 

    

                       

                                                                                          

    Once the product life is over, you may send back the 

 

    unit to   EAPL for disposition              

 