CREATED ON: May 18, 2017
How to program:
Timing Example:-
RELAY :1 COMBINATION 1 :
DLY : 00.12.30
ON : 03.25.00
Above format is in HRS/MIN/SEC.
Slide RUN/PROG switch to PROG mode; Relay &
combination shows “1” and “DLY” & “MIN SEC” LED glows.
Press “RELAY” button till display shows “1”.
Press “combination” button till display shows ‘1’.
Press “DLY/ON” button to select Delay time
(DLY led glows).
Press “RANGE” button to select range as MIN SEC
(MIN SEC led glows).
Press “SELECT” MSD starts flashing.
Press “ADVANCE” till display shows 1.
Press “SELECT” again; 2
nd
digit starts flashing.
Press “ADVANCE” till display shows 2.
Press “SELECT” again; 3
rd
digit starts flashing.
Press “ADVANCE” till display shows 3.
Press “SELECT” again; 4
th
(LSD) digit starts flashing.
Press “ADVANCE” till display shows 0.
Press “SELECT” again; the SET value is saved in memory &
same SET value is copied to ON time of same
combination.
Press “DLY ON” button to select ON time (ON led glows).
Press “RANGE” button to select range as HRS MIN
(HRS MIN led glows).
Press “SELECT” MSD starts flashing.
Press “ADVANCE” till display shows 0.
Press “SELECT” again; 2
nd
digit starts flashing.
Press “ADVANCE” till display shows 3.
Press “SELECT” again; 3
rd
digit starts flashing.
Press “ADVANCE” till display shows 2.
Press “SELECT” again; 4
th
digit (LSD) starts flashing.
Press “ADVANCE” till display shows 5.
Press “SELECT” again, SET ON time is saved in memory.
Same procedure shall be followed for different ranges
and different combinations.
NOTE: ON time setting shall be always more than DLY time
in all ranges.
OPERATING
CONDITION/
MODE
STATUS
TIMING
SEQUENCE
TIMING IN
PROGRESS
(TIP)
TIMING
COMPLETION
(TC)
RELAY
LED
RELAY
LED
CHANNEL
“0”
DELAY TIME
OFF
OFF
ON
ON
ON TIME
ON
ON
OFF
OFF
CHANNEL”1
” & So on
DELAY TIME
OFF
OFF
ON
ON
ON TIME
ON
ON
OFF
OFF
Function
Combination Switching of
Outputs.
Rated supply Voltage
85V TO 270V AC/DC
Rated frequency
50 / 60Hz ± 5%
Power consumption
AC Approx. 20VA
DC Approx. 10W
Control output
8 (8 NO contacts rated for 5A @
250V AC/28VDC resistive load)
Start Signal
Potential free closure for a
minimum of 250mSec.
Reset Signal
Potential free closure
Time range
1Sec to 99Hrs 59Min 59Sec For
Delay & ON
Setting accuracy
± 0.2% ± 50mSec.
Repeat accuracy
± 0.2% ± 50mSec.
Recovery time
2Sec minimum
Variation due to voltage
change
± 1% max. ± 50mSec.
Variation due to
temperature change
± 2% max. ± 50mSec.
Variation due to
frequency change
± 1% max. ± 50mSec.
Ambient temperature
Operation:-10º C to + 55º C
Storage :-25º C to +80º
C
Humidity
MAX 85% RH @ 40ºC
Technical Specification
Disposition
Once the product life is over, you may send back the
unit to EAPL for disposition
Contact
Electronic Automation Pvt. Ltd
#20, KHB Industrial Area
Yelahanka, Bangalore -560064
Ph: +91-80-28567561/2, /42802345
Customer care :Ph:+91-80-42802323
Email:
,
www.eaplindia.com
OD RS AN 210001 REV 01/18-05-17