AUTOSCALING
X = KVAh
Initially starts with .000 KVAh
If X is greater than 000.999 KVAh then next value will be 001.000 KVAh.
If X is greater than 009.999 KVAh then next value will be 010.000 KVAh.
If X is greater than 099.999 KVAh then next value will be 100.000KVAh.
If X is greater than 999.999 KVAh then next value will be 1000.00KVAh.
If X is greater than 9999.99 KVAh then next value will be 10.0000 MVAh.
If X is greater than 99.9999MVAh then next value will be 100.000 MVAh.
If X is greater than 999.999 MVAh then next value will be 1000.00MVAh.
If X is greater than 9999.99 MVAh then next value will be 10.0000GVAh.
If X is greater than 99.9999 GVAh then next value will be 100.000 GVAh.
If X is greater than 999.999 GVAh then next value will be .000 KVAh
. &
All Energies get transferred to respective Old Energies.
PROGRAMMING
•
PRESS SELECT button to enter programming mode
Example: If user wants to program CT ratio 250/5, PT- 415/415, Device
ID- 123 Baud- 9600 pulse output A(Active Energy) and set a new
password 1112. Password is 1111
PRESS
TOP
DISPLAY
SHOWS
BOTTOM
DISPLAY
SHOWS
COMMENTS/
RANGE/ DEFAULT
VALUE
“SELECT”
‘1’ 0 0 0
PASSWd
# Enter 4 digits PASS
WORD.
# DEFAULT VALUE:
1000.
# Press “ADVANCE”
to set 1
st
digit (Rolls
from 0 to 9)
“SELECT”
1 ‘0’ 0 0
PASSWd
# Press “ADVANCE”
to set 2
nd
digit (Rolls
from 0 to 9)
“SELECT”
1 1 ‘1’ 0
PASSWd
# Press “ADVANCE”
to set 3
rd
digit (Rolls
from 0 to 9)
“SELECT”
1 1 1 ‘1’
PASSWd
# Press “ADVANCE”
to set 4
th
digit (Rolls
from 0 to 9)
“NEXT”
‘0’ 0 0 5
CT-PRI
# Enter 5 digit CT-
PRIMARY VALUE
# RANGE : 0001 - 5000
# DEFAULT VALUE :
0005
# Press “ADVANCE”
to set 1
st
digit (Rolls
from 0 to 5)
“SELECT”
0 ‘2’ 0 5
CT-PRI
# Press “ADVANCE”
to set 2
nd
digit (Rolls
from 0 to 9)
“SELECT”
0 2 ‘5’ 5
CT-PRI
# Press “ADVANCE”
to set 3
rd
digit (Rolls
from 0 to 9)
“SELECT”
0 2 5 ‘0’
CT-PRI
# Press “ADVANCE”
to set 4
th
digit (Rolls
from 0 to 9)
PRESS
TOP
DISPLAY
SHOWS
BOTTOM
DISPLAY
SHOWS
COMMENTS/
RANGE/ DEFAULT
VALUE
“NEXT”
‘5’
CT-SEC
# Enter CT-
SECONDARY VALUE
# RANGE : 1 - 5
# DEFAULT VALUE : 5
# Press “ADVANCE” to
set the digit (Rolls from
1 to 5)
“NEXT”
‘0’ 0 0 4 1 5
PT-PRI
# Enter 6 digit PT-
PRIMARY VALUE
# RANGE : 00110-
999000
# DEFAULT VALUE :
000415
# Press “ADVANCE” to
set 1
st
digit (Rolls from 0
to 9)
“SELECT”
0 ‘0’ 0 4 1 5
PT-PRI
# Press “ADVANCE” to
set 2
nd
digit (Rolls from
0 to 9)
“SELECT”
0 0 ‘0’ 4 1 5
PT-PRI
# Press “ADVANCE” to
set 3
rd
digit (Rolls from 0
to 9)
“SELECT”
0 0 0 ‘4’ 1 5
PT-PRI
# Press “ADVANCE” to
set 4
th
digit (Rolls from
0 to 9)
“SELECT”
0 0 0 4 ‘1’ 5
PT-PRI
# Press “ADVANCE” to
set 5
th
digit (Rolls from
0 to 9)
“SELECT”
0 0 0 4 1 ‘5’
PT-PRI
# Press “ADVANCE” to
set 5
th
digit (Rolls from
0 to 9)
“NEXT”
‘4’ 1 5
PT-SEC
# Enter 6 digit PT-
SECONDARY VALUE
# RANGE : 110 - 500
# DEFAULT VALUE :
415
# Press “ADVANCE” to
set 1
st
digit (Rolls from1
to 5)
“SELECT”
4 ‘1’ 5
PT-SEC
# Press “ADVANCE” to
set 2
nd
digit (Rolls from
0 to 9)
“SELECT”
4 1 ‘5’
PT-SEC
# Press “ADVANCE” to
set 3
rd
digit (Rolls from 0
to 9)
“NEXT”
‘y’
CLR-EN
# DEFAULT VALUE : n
# Press “ADVANCE” to
toggle to ‘Y’ (YES) and
‘n’ (NO).
# If ‘y’ selected, clears
Energy registers and
load On hours.
Simultaneously, old
energy and old load on
hour registers are
updated with current
energy readings.
NOTE:
•
Press NEXT or PREVIOUS button to come out of the
program mode & enter into RUN mode.
•
All programming parameters will be saved only after
coming out of program mode and has gone to run mode.
PRESS
TOP
DISPLAY
SHOWS
BOTTOM
DISPLAY
SHOWS
COMMENTS/
RANGE/ DEFAULT
VALUE
“NEXT”
‘1’ 0 5
dEV-Id
1. Enter Device ID
2. RANGE : 001-247
#DEFAULT VALUE:
001
3.Press “ADVANCE” to
set 1
st
digit (Rolls from 0
to
2)
“SELECT”
1 ‘2’ 5
dEV-Id
Press “ADVANCE” to
set 2
nd
digit (Rolls from
0 to 9)
“SELECT”
1 2 ‘3’
dEV-Id
Press “ADVANCE” to
set 3
rd
digit (Rolls from
0 to 9)
“NEXT”
‘9600’
bAUd
# DEFAULT VALUE
:9600
Press “ADVANCE” to
set required Baud rate.
(2400,4800,9600,19200)
“NEXT”
‘A’
PLSOUT
# DEFAULT VALUE:A
# Press “ADVANCE” to
toggle to ‘r’(Reactive
Energy) and ‘A’(Active
Energy)
“NEXT”
‘n’
ChPASS
# DEFAULT VALUE :n
Press NEXT button to
come out of the PROG
MODE
If the user wants to
change the password.
Press “ADVANCE” to
set ‘y’.
“ADVANCE”
‘y’
ChPASS
Press “NEXT” to set
new password.
“NEXT”
0 0 0 ‘1’
1.Enter 4 digit
PASSWORD-
2. RANGE: 0001-9999
# DEFAULT VALUE :
0001
3.Press “ADVANCE” to
set 1
st
digit (Rolls from 0
to 9)
“SELECT”
1 ‘1’ 0 1
ChPASS
Press “ADVANCE” to
set 2
nd
digit (Rolls from
0 to 9)
“SELECT”
1 1 ‘1’ 1
ChPASS
Press “ADVANCE” to
set 3
rd
digit (Rolls from
0 to 9)
“SELECT”
1 1 1 ‘2’
ChPASS
Press “ADVANCE” to
set 4
th
digit (Rolls from
0 to 9)
DOC NO:
OD RE YN 45001 0 Rev NO: 01 Dtd: 16/10/2013
Page 2 of 3