EAPL EMS-10 V4.0 Instruction Manual Download Page 2

 

AUTOSCALING

 

X = KVAh 
Initially starts with  .000 KVAh 
If X is greater than 000.999 KVAh then next value will be 001.000 KVAh. 
If X is greater than 009.999 KVAh then next value will be 010.000 KVAh. 
If X is greater than 099.999 KVAh then next value will be 100.000KVAh.  
If X is greater than 999.999 KVAh then next value will be 1000.00KVAh. 
If X is greater than 9999.99 KVAh then next value will be 10.0000 MVAh. 
If X is greater than 99.9999MVAh then next value will be 100.000 MVAh. 
If X is greater than 999.999 MVAh then next value will be 1000.00MVAh. 
If X is greater than 9999.99 MVAh then next value will be 10.0000GVAh. 
If X is greater than 99.9999 GVAh then next value will be 100.000 GVAh. 
If X is greater than 999.999 GVAh then next value will be .000 KVAh

. & 

All Energies get transferred to respective Old Energies. 

 

PROGRAMMING 

 

PRESS SELECT button to enter programming mode

 

Example: If user wants to program CT ratio 250/5, PT- 415/415, Device 
ID- 123 Baud- 9600 pulse output A(Active Energy) and set a new 
password 1112. Password is 1111 

PRESS 

TOP 

DISPLAY 

SHOWS 

BOTTOM 

DISPLAY 

SHOWS 

COMMENTS/ 

RANGE/ DEFAULT 

VALUE 

“SELECT” 

‘1’ 0 0 0 

PASSWd 

# Enter 4 digits PASS 

WORD. 
# DEFAULT VALUE: 
1000. 
# Press “ADVANCE” 
to set 1

st

 digit (Rolls 

from 0 to 9) 

“SELECT” 

1 ‘0’ 0 0 

PASSWd 

# Press “ADVANCE” 
to set 2

nd

 digit (Rolls 

from 0 to 9) 

“SELECT” 

1 1 ‘1’ 0 

PASSWd 

# Press “ADVANCE” 
to set 3

rd

 digit (Rolls 

from 0 to 9) 

“SELECT” 

1 1 1 ‘1’ 

PASSWd 

# Press “ADVANCE” 
to set 4

th

 digit (Rolls 

from 0 to 9) 

“NEXT” 

‘0’ 0  0 5 

CT-PRI 

# Enter 5 digit  CT-
PRIMARY VALUE 
# RANGE : 0001 - 5000 
# DEFAULT VALUE : 
0005 
# Press “ADVANCE” 
to set 1

st

 digit (Rolls 

from 0 to 5) 

“SELECT” 

0 ‘2’  0 5 

CT-PRI 

# Press “ADVANCE” 
to set 2

nd

 digit (Rolls 

from 0 to 9) 

“SELECT” 

 0 2 ‘5’ 5 

CT-PRI 

# Press “ADVANCE” 
to set 3

rd

 digit (Rolls 

from 0 to 9) 

“SELECT” 

 0 2 5 ‘0’ 

CT-PRI 

# Press “ADVANCE” 
to set 4

th

  digit (Rolls 

from 0 to 9) 

 
 

 

 

 

 

PRESS 

TOP 

DISPLAY 

SHOWS 

BOTTOM 

DISPLAY 

SHOWS 

COMMENTS/ 

RANGE/ DEFAULT 

VALUE 

“NEXT” 

 

‘5’ 

CT-SEC 

# Enter CT-
SECONDARY VALUE 
# RANGE : 1 - 5 
# DEFAULT VALUE : 5 
# Press “ADVANCE” to 
set the digit (Rolls from 
1 to 5) 

“NEXT” 

‘0’ 0 0 4 1 5 

PT-PRI 

# Enter 6 digit  PT-
PRIMARY VALUE 
# RANGE : 00110-
999000 
# DEFAULT VALUE : 
000415 
# Press “ADVANCE” to 
set 1

st

 digit (Rolls from 0 

to 9) 

“SELECT” 

0 ‘0’ 0 4 1 5 

PT-PRI 

# Press “ADVANCE” to 
set 2

nd

  digit  (Rolls from 

0 to 9) 

“SELECT” 

0 0 ‘0’ 4 1 5 

PT-PRI 

# Press “ADVANCE” to 
set 3

rd

 digit (Rolls from 0 

to 9) 

“SELECT” 

0 0 0 ‘4’ 1 5    

PT-PRI 

# Press “ADVANCE” to 
set 4

th

  digit (Rolls from 

0 to 9) 

“SELECT” 

0 0 0 4 ‘1’ 5     

PT-PRI 

# Press “ADVANCE” to 
set 5

th

  digit (Rolls from 

0 to 9) 

“SELECT” 

0 0 0 4 1 ‘5’     

PT-PRI 

# Press “ADVANCE” to 
set 5

th

  digit (Rolls from 

0 to 9) 

“NEXT” 

‘4’ 1 5 

     PT-SEC 

# Enter 6 digit  PT-
SECONDARY VALUE 
# RANGE : 110 - 500 
# DEFAULT VALUE : 
415 
# Press “ADVANCE” to 
set 1

st

 digit (Rolls from1 

to 5) 

“SELECT” 

4 ‘1’ 5     

PT-SEC 

# Press “ADVANCE” to 
set 2

nd

  digit (Rolls from 

0 to 9) 

“SELECT” 

4 1 ‘5’      

PT-SEC 

# Press “ADVANCE” to 
set 3

rd

 digit (Rolls from 0 

to 9) 

 “NEXT” 

‘y’ 

CLR-EN 

# DEFAULT VALUE : n 
# Press “ADVANCE” to 
toggle to ‘Y’ (YES) and 
‘n’ (NO). 
# If ‘y’ selected, clears 
Energy registers and 
load On hours.  
Simultaneously, old 
energy and old load on 
hour registers are 
updated with current 
energy readings. 

 
NOTE:

 

 

Press NEXT or PREVIOUS button to come out of the 
program mode & enter into RUN mode. 

 

All programming parameters will be saved only after 
coming out of program mode and has gone to run mode. 

 

PRESS 

TOP 

DISPLAY 

SHOWS 

BOTTOM 

DISPLAY 

SHOWS 

COMMENTS/ 

RANGE/ DEFAULT 

VALUE 

“NEXT” 

‘1’ 0 5 

dEV-Id 

1. Enter Device ID 
2. RANGE : 001-247 
#DEFAULT VALUE: 
001 
3.Press “ADVANCE” to 
set 1

st

 digit (Rolls from 0 

to

 2)

 

“SELECT” 

1 ‘2’ 5 

dEV-Id 

Press  “ADVANCE”  to 
set  2

nd

  digit  (Rolls  from 

0 to 9) 

“SELECT” 

1 2 ‘3’ 

dEV-Id 

Press  “ADVANCE”  to 
set  3

rd

  digit  (Rolls  from 

0 to 9) 

“NEXT” 

‘9600’ 

bAUd 

# DEFAULT VALUE 
:9600

 

Press “ADVANCE” to 
set required Baud rate. 
(2400,4800,9600,19200) 

“NEXT” 

‘A’ 

PLSOUT 

# DEFAULT VALUE:A  
# Press “ADVANCE” to 
toggle to ‘r’(Reactive 
Energy) and ‘A’(Active 
Energy) 

“NEXT” 

‘n’ 

ChPASS 

# DEFAULT VALUE :n 
Press NEXT button to 
come out of the PROG 
MODE 
If the user wants to 
change the password. 
Press “ADVANCE” to 
set ‘y’. 

“ADVANCE”

 

‘y’

 

ChPASS

 

Press  “NEXT”  to  set 
new password. 

“NEXT” 

 0 0 0 ‘1’ 

 

1.Enter 4 digit  
PASSWORD- 
2.  RANGE: 0001-9999 
# DEFAULT VALUE : 
0001 
3.Press “ADVANCE” to 
set 1

st

 digit (Rolls from 0 

to 9) 

“SELECT”

 

1 ‘1’ 0 1

 

ChPASS

 

Press  “ADVANCE”  to 
set  2

nd

  digit  (Rolls  from 

0 to 9) 

“SELECT”

 

1  1 ‘1’ 1

 

ChPASS

 

Press  “ADVANCE”  to 
set  3

rd

  digit  (Rolls  from 

0 to 9) 

“SELECT” 

1  1  1 ‘2’

 

ChPASS

 

Press  “ADVANCE”  to 
set  4

th

  digit  (Rolls  from 

0 to 9) 

DOC NO:

  

OD RE YN 45001 0 Rev NO: 01  Dtd: 16/10/2013

 

Page 2 of 3 