Eagle Signal B856-501 Technical Manual Download Page 3

3

For 3 Seconds

P

Operating Function:

 Determines how outputs will operate in relation to the set value.  Choices are:

• On-Delay (OndL)
• Off Delay (OFdL)
• Interval 1 (int1)
• Interval 2 (int2)
• Delay/Interval (dint)
• Repeat Cycle (CYCL)

See Appendix A for timing charts

P

F u n c

1

S

t

First Operation:  

Determines whether the Repeat Cycle will start with an On or an Off Operation

Note:  This parameter will only appear if Repeat Cycle is chosen as the Operating
Function

O n

O n d L

i n t

1 . 0

S

Interval Time: 

Sets the amount of time the output will be active after the On-Delay function has timed

out.  Use the 1 through 4 keys to set the value in a range from 0.1 to 999.9 seconds.

Note:  This parameter will only appear if Delay/Interval is chosen as the Operating
Function

Time Range: 

 Sets the unit of measure for the time values that will be shown on the display in Operation

Mode.  Choices are:

• Seconds
• Minutes
• Hours
• Minutes:Seconds
• Hours:Minutes

t r n G

S

P

P

P

d E c P

Decimal Position:  

Sets the decimal position for the time display.  Choices are: no decimal point (0),

 1/10ths position (0.0), or Hundredths position (0.00).  The time range selected in the previous
parameter will remain illuminated for reference.

0

S

Note:  This parameter will not appear if Minutes:Seconds or Hours:Minutes is
selected as the time range

• Enter the Program Mode by holding down the "P" key for 3 seconds
• Press the "P" key to move the top display from one parameter to the next
• Press the "E" key to scroll the bottom display through the available choices for that parameter
• While in Program Mode the unit will stop timing and the output will retain its last state. The new

settings will only become effective after returning to Operation Mode by holding down the "P" key
for 3 seconds

P R O G R A M M I N G

PROGRAM MODE

Summary of Contents for B856-501

Page 1: ...nciatorsindicate information such as the time range and the status of the input and outputs Reliability is a key feature of the B856 IEC Level4noiseimmunityensuresflawless operationinharshelectricalen...

Page 2: ...ime up mode and decrements if set in timedownmode Numeric Keys Set Value Settablevalueusedtotriggerthetimed output Time Indicators Theword Timing Flasheswhenatiming functionistakingplace Theapplicable...

Page 3: ...sure for the time values that will be shown on the display in Operation Mode Choices are Seconds Minutes Hours Minutes Seconds Hours Minutes t r n G S P P P d E c P Decimal Position Sets the decimal p...

Page 4: ...ntinue from the point of power interruption Off F r S t Front Panel Reset Enable When active On the timing operation can be reset in Operation Mode by simultaneously pressing the E and P keys If inact...

Page 5: ...sactivatedandtimingbegins Theoutputwillremainactiveuntilthepresettime T haselapsedorpoweris interrupted Removal of the start signal will also cause the output to be deactivated and the time value to b...

Page 6: ...ties within the United States and throughout the world For information about the distributor or sales office nearest you contact our customer service department Customer Service Internet Presence call...

Page 7: ...ties within the United States and throughout the world For information about the distributor or sales office nearest you contact our customer service department Customer Service Internet Presence call...

Page 8: ...shipment and products which are defective in workmanship or material will be repaired or replaced at the option of the Company at no charge to the Buyer Final determination as to whether a product is...

Reviews: