Figure 5-1 Tracing a Ground Fault
5.3
Tracing ‘Wire Mix’ faults
Where a fault has occurred between two separate, otherwise isolated circuits, the signal
generator may be connected between the two circuits and the fault traced in a similar
way to a ground fault.
Use a multimeter as described previously to identify which parts of the circuit have the
lowest voltage between them, and connect the signal generator to these two cables.
Figure 5-2 shows the tracing sequence.