Installation
1
2
A
Y
N
Sample Order: 250 A, Copper, IP 55, 5 Conductors Fire Barrier
KOC 0255- II -STD-150-40
Fire Barriers
Fire barriers are used to prevent the transition of flame and smoke
from one zone to another in case of fire. The fire barriers prevent the
chimney effect of air insulated busbar.
Block Joint
Floor
Internal
Fire
Barrier
Fire Barriers
Dimensioning of Fire Barrier
When placing an order for fire barriers to be installed in the
KO-II
busbar, the following information is required :
1. Thickness of floor or wall in cm. (A mm)
2.
Centreline dimension of the fire barrier should be measured
from the side without the block joint. (Y mm)
3.
There will be no plug-in points at the fire barrier location.
4.
EAE Supplies a 300 mm thick fire barrier as standard when
wall or floor thickness is not stated.
5.
The minimum length for these special elements with fire
barrier is 600 mm.
Fire Barriers