background image

F a u l t s a n d s o l u t i o n s

EC590

 

F a u l t s a n d s o l u t i o n s

EC590

 

Err06

Err07

Err08

Overvoltage 

during 

deceleration

Overvoltage 
at constant 

speed

Control 

power supply 

fault

1: The input voltage is too high. 
2: An external force drives the 
motor during deceleration. 
3: The deceleration time is too 
short. 
4: The braking unit and braking 
resistor are not installed.
5: Subject to external inter-
ference.

1: The input voltage is too high. 
2: An external force drives the 
motor during running.
3: Subject to external inter-
ference.

1: The input voltage is not 
within the allowable range.

1: Adjust the voltage to normal range.
2: Remove the external force or install a 
braking resistor.
3: Increase the deceleration time.
4: Install the braking unit and braking 
resistor.
5: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.
1: Adjust the voltage to the normal range. 
2: Remove the external force or install 
the braking resistor.
3: According to the historical fault 
records, if the current value at the time
of fault is far from reaching the over-
current point value, it is necessary to 
find the interference suorce.

1: Adjust the input voltage to the 
allowable range.

Err09

Undervoltage

1: Instantaneous power failure 
occurs on the input power supply. 
2: The AC drive's input voltage 
is not within the allowable range.
3: The DC-Bus voltage is abnormal.
4: The rectifier bridge and 
buffer resistor are faulty.
5: The drive board is faulty. 
6: The main control board is 
faulty. 

1: Reset the fault.
2: Adjust the voltage to the normal range.
3: Contact technical support.
4: Contact technical support.
5: Contact technical support.
6: Contact technical support. 

Err10

Err11

AC drive 
overload

Motor 

overload

1: The load is too heavy or 
locked rotor occurs on the motor. 
2: The AC drive model is of too 
small power class.

1: F9-01 is set improperly. 
2: The load is too heavy or 
locked rotor occurs on the motor. 
3: The AC drive model is of too 
small power class.

1: Reduce the load and check the motor 
and mechanical condition. 
2: Select an AC drive of higher power 
class.

1: Set it correctly. 
2: Reduce the load and check the motor and 
the mechanical condition. 
3: Select an AC drive of higher power 
class.

Err12

Power input 

phase loss

1: The three-phase power input is 
abnormal. 
2: The drive board is faulty. 
3: The lightening board is faulty. 
4: The main control board is 
faulty.

1: Eliminate external faults. 
2: Seek technical support.
3: Seek technical support.
4: Seek technical support.

Err13

Power output 

phase loss

1: The cable connecting the AC 
drive and the motor is faulty. 
2: The AC drive's three-phase 
outputs are unbalanced when the 
motor is running. 
3: The drive board is faulty. 
4: The module is faulty.

1: Eliminate external faults. 
2: Check whether the motor three-phase 
winding is normal. 
3: Seek technical support.
4: Seek technical support. 

1 3

 -

14

 -

Err14

Module 

overheat

1: The ambient temperature is too 
high. 
2: The air filter is blocked. 
3: The fan is damaged.
4: The thermally sensitive 
resistor of the module is damaged. 
5: The inverter module is damaged. 

1: Lower the ambient temperature. 
2: Clean the air filter. 
3: Replace the damaged fan.
4: Replace the damaged thermally 
sensitive resistor. 
5: Replace the inverter module. 

Err15

Err16

 

External 

equipment 

fault

Communi-

cation fault

1: External fault signal is input 
via S.
2: Input the signal of external 
fault through virtual IO function.

1: The host computer is in 
abnormal state. 
2: The communication cable is 
faulty. 
3: Incorrect setting of communi-
cation expansion card F0-28.
4: The communication parameters 
in group PB are set improperly.

1:Reset the operation.
2:Reset the operation.

1: Check the cabling of host computer. 
2: Check the communication cabling.
3: Set the communication expansion 
cardtypes.
4: Set the communication parameters 
properly.

Err17

Err18

Contactor 

faul

Current 

detection 

fault

1: The drive board and power 
supply are faulty. 
2: The contactor is faulty. 

1: The HALL device is faulty. 
2: The drive board is faulty

.

1: Replace the faulty drive board or 
power supply board. 
2: Replace the faulty contactor.

1: Replace the faulty HALL device. 
2: Replace the faulty drive board.

Err19

Motor auto-

tuning fault

1: The motor parameters are not 
set according to the nameplate. 
2: The motor auto-tuning times 
out.

1: Set the motor parameters according 
to the nameplate properly. 
2: Check the cable connecting the AC 
drive and the motor.

Err20

Encoder fault

1: The encoder type is incorrect. 
2: The cable connection of the 
encoder is incorrect.
3: The encoder is damaged. 
4: The PG card is faulty. 

1: Set the encoder type correctly 
based on the actual situation. 
2: Eliminate external faults.
3: Replace the damaged encoder. 
4: Replace the faulty PG card. 

Err21

Err22

EEPROM 

readwrite fault

AC drive 

hardware fault

1: The EEPROM chip is damaged.

1: Overvoltage exists. 
2: Overcurrent exists.

1: Replace the main control panel.

1: Handle based on over

-

voltage. 

2: Handle based on over

-

current.

Err23

Short circuit 

to ground

1: The motor is short circuited 
to the ground.

1: Replace the cable or motor.

Err26

Running 

time reached

1: Accumulative running time 
reaches setting.

1: Clear the record through the 
parameter initialization function.

Err27

Err28

User-defined 

fault 1

User-defined 

fault 2

1: Input the signal of user-
defined fault 1 through multi-
function terminal S.
2: Input the signal of user-
defined fault 1 through the 
virtual I0 function.

1: Reset the operation.
2: Reset the operation.

1: Input the signal of user-
defined fault 2 through multi-
function terminal S.
2: Input the signal of user-
defined fault 2 through the 
virtual I0 function.

1: Reset the operation.
2: Reset the operation.

Summary of Contents for EC590 Series

Page 1: ...0 in 2022 Copyright subject to change without notice Professional AC Drive Manufacturer ZHEJIANG EACN ELECTRONIC TECHNOLOGY CO LTD Address No 1 Jinhe Road Qinshan Street Haiyan County Jiaxing City Zh...

Page 2: ...s 9 5 F4 Input Terminals 9 6 F5 Output Terminals 9 7 F6 Start stop control 9 8 F7 Operating panel and display 9 9 F8 Auxiliary Functions 9 10 F9 Fault and Protection 9 11 FA PID Function 9 12 FB Fixed...

Page 3: ...e read carefully If you have any questions please contact with the agents of our company and our technicians are ready to serve you The instructions are subject to change without notice You can contac...

Page 4: ...range of 0 0 6500 0s DC braking JOG control DC braking frequency 0 00 Hz to maximum frequency Braking time 0 0 100 0s Braking action current value 0 0 150 0 Simple PIC Multiple preset speeds JOG frequ...

Page 5: ...It helps to avoid frequent overcurrent faults of the AC drive Timing control Time range 0 0 6500 0 minutes Individua lized functions Multiple communication protocols It supports Modbus Item Specifica...

Page 6: ...171 160 130 127 4 5 1 5Kw 2 2Kw 4 0Kw 7 5Kw 18 5Kw 15Kw 126 146 170 115 131 151 320 186 256 175 243 305 158 174 198 155 171 195 4 5 6 6 30Kw 5 5Kw 11Kw 22Kw A Structure 45Kw 75Kw 180 250 120 170 489 6...

Page 7: ...C 0V 10V 2 Impedance 22k 1 Input range DC 0V 10V 4mA 20mA decided by selection of F4 40 2 Impedance 22k voltage input 500 current input 10V GND 24V COM PLC AI1 GND AI2 GND Name External 10V power supp...

Page 8: ...sudden load is added during operation 5 The AC drive model is of too small power class 6 Subject to external inter ference 1 Eliminate external faults 2 Perform the motor autotuning 3 Adjust the volta...

Page 9: ...oard is faulty 4 The module is faulty 1 Eliminate external faults 2 Check whether the motor three phase winding is normal 3 Seek technical support 4 Seek technical support 13 14 Err14 Module overheat...

Page 10: ...ameter protection password is set In the function parameter mode and user change parameter mode the parameter menu can only be entered after correctly entering the password Set FP 00 to 0 to cancel th...

Page 11: ...anel keypad display 0 No function 1 Digital setting 2 AI1 3 AI2 4 Keyboard potentiometer 5 Pulse reference S5 6 Multi reference 7 Simple PLC 8 PID reference 9 Serial communication Tens terminal contro...

Page 12: ...V F complete separation 11 V F half separation Default 0 Parameter Name F3 02 Cut off frequency of torque boost 0 00 Hz to the maximum frequency 50 00Hz F3 03 F3 04 F3 05 F3 06 F3 07 F3 08 Multi poin...

Page 13: ...control switchover 47 Emergency stop 48 External STOP terminal 2 49 Deceleration DC injection braking 50 Clear the current running time 51 Two wire Three wire mode switchover 52 Reverse frequency forb...

Page 14: ...specified count value reached 10 Length arrives 11 PLC cycle completed 0 2 F5 06 F5 07 0 Operationg frequency 1 Set frequency 2 Output current 3 Output torque torque absolute value 4 Output power 5 O...

Page 15: ...l Change Function Code Setting Range Default Parameter Name 0 Speed tracking method 0 Start with stop frequency 1 Start from zero speed 2 Start from maximum frequency 0 F6 02 Speed tracking speed 1 10...

Page 16: ...eference Hz BIT0 1 Bus voltage BIT0 2 S state BIT0 3 YO state BIT0 4 AI1 voltage V BIT0 5 AI2 voltage V BITO 6 Keyboard potentiometer voltage BIT0 7 Count value BITO 8 Length value BIT0 9 PLC stage BI...

Page 17: ...d 0 00Hz F8 25 Switch over frequency of acceleration time 1 and acceleration time 2 0 00Hz to the maximum frequency F8 26 Switch over frequency of deceleration time 1 and deceleration time 2 0 00Hz to...

Page 18: ...upon 3rd latest fault Current upon 3rd latest fault 3rd latest fault type F9 19 F9 20 Bus voltage upon 3rd latest fault S state upon 3rd latest fault Y state upon 3rd latest fault F9 21 Power on time...

Page 19: ...reached Err29 0 Coast to stop 1 Stop according to the stop mode 2 Continue to run BIT3 Load lost Err30 0 Coast to stop 1 Deceleration to stop 2 Continue to run at 7 of rated motor frequency and restor...

Page 20: ...d 0 00 to 60 00s 0 AI1 1 AI2 2 Keyboard potentiometer 3 AI1 AI2 4 Pulse reference S5 5 Communication reference 6 AI1 AI2 7 Max AI1 AI2 8 Min AI1 AI2 0 0 FA 03 PID operation direction 0 Forward 1 Rever...

Page 21: ...ence 4 FC 29 FC 28 Running time of simple PLC reference 5 0 0s h to 6553 5s h Acceleration Deceleration time of simple PLC reference 4 0 to 3 Running time of simple PLC reference 6 FC 30 0 0s h to 655...

Page 22: ...mmunication detection time FE 00 User defined parameter 0 U3 17 FE 01 User defined parameter 1 F0 00 F0 00 FC 47 Acceleration Deceleration time of simple PLC reference 14 0 to 3 Running time of simple...

Page 23: ...ter 27 F0 00 FE 28 User defined parameter 28 F0 00 FE 29 User defined parameter 29 F0 00 F0 00 to FP xx A0 00 to Ax xx U0 00 to U0 xx U3 00 to U3 xx FP Parameter Management Change Function Code Settin...

Page 24: ...2 10 A2 27 A2 28 Rotor resistance Leakage inductive reactance Mutual inductive reactance No load current Encoder pulses per revolution Encoder type 0 001 to 65 535 AC drive power 55 kW 0 0001 to 6 553...

Page 25: ...0 DPWM switchover frequency upper limit 5 00 Hz to the maximum frequency 0 Asynchronous modulation 1 Synchronous modulation A5 02 Dead zone compensation mode selection 0 Disabled 1 Enabled compensatio...

Page 26: ...ump range A7 User Programmable Card Change Function Code Setting Range Default Parameter Name 0 Disabled 1 Enabled A7 01 Control board output terminal control mode selection 0 0 AC drive control 1 Use...

Page 27: ...tory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected Factory corrected U Minimum Unit UO Monitoring Parameters Function Code Param...

Page 28: ...de parameters some function codes cannot be changed only for manufacturers to use or monitor function code parameter address marking rules The rules are represented by the function code group number a...

Page 29: ...BIT1 Y2 output control BIT2 RELAY1 output control BIT3 RELAY2 output control BIT4 Y4R output control BIT5 VY1 BIT6 VY2 BIT7 VY3 BIT8 VY4 BIT9 VY5 2001 Digital output terminal control write only Comman...

Page 30: ...4 port is constrained by the functional parameter F5 00 and can be used as a high speed pulse output channel with a maximum output frequency of 50KHz when used as an open collector output Same specifi...

Reviews: