E2S Warning Signals
Impress House, Mansell Road, Acton, London W3 7QH
[email protected] e2s.com
Page 2 of 2
D242
-
00
-
001
-
IS_Issue_4
-
28/10/2022
INSTRUCTION & SERVICE MANUAL
SONF1 Range
-
Alarm Horn Sounder
DC
Tone
Settings
AC
Tone
Settings
Tone 1
Tone 2
Tone 3
Tone 4
Tone 5
Tone 6
Tone 7
Tone 8*
Tone 9*
Tone 10*
Loosen posi
-
pan screws
in two positions to
access enclosure
Tighten Screws 5Nm
800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
Simulated Bell Sound
Sweeping 800/1000 Hz @ 7 Hz Sweeping
500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation
Continuous 1000 Hz PFEER toxic gas
Continuous 554 Hz
420 Hz @ 0.625 sec Australian Alert
1
2
3
4
5
6
7
8
9
Sawtooth 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
10
8
8
8
1
1
9
10
Tone Description
Stage 1
Stage 2
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
100dB(A) @1m
97dB(A) @1m
97dB(A) @1m
SONF1 dB@ 1m
800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
800/1000 Hz @ 7 Hz Sweeping
2400/2900 Hz 50 Hz Sweeping
1
2
3
4
5
6
7
8
9
Sawtooth 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
10
Tone Description
Stage 1
Simulated Bell Sound
Continuous 1000 Hz PFEER toxic gas
420 Hz @ 0.625 sec Australian Alert
500 1200 Hz 3.75 sec / 0.25 sec Australian Evacuation
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
100dB(A) @1m
95dB(A) @1m
99dB(A) @1m
100dB(A) @1m
97dB(A) @1m
100dB(A) @1m
Mounting Positions
[S] Backbox
[M] Backbox
Access to Enclosure
Open
Close
See D242
-
05
-
001
800/1000 Hz @ 0.25 sec Alternating BS5839 Alarm Tone
500/1200 Hz @ 0.3 Hz 0.5 sec Slow Whoop NEN 2575:2000
544Hz (100mS)/440 Hz (400mS) AFNOR NF S 32 001
Continuous 1000 Hz PFEER toxic gas
Continuous 554 Hz
1
2
3
4
8
9
Sawtooth 1200/500 Hz @ 1 Hz DIN / PFEER P.T.A.P
Tone Description
Stage 1
99dB(A) @1m
100dB(A) @1m
99dB(A) @1m
97dB(A) @1m
100dB(A) @1m
97dB(A) @1m
SONF1 dB@ 1m
VdS / CPR
Tone Table
SONF1 24vdc (18
-
30vdc) unit is CPR compliant
EN54
-
3
Type B
IP55
The tones listed below have been tested to EN54
-
3
and are compliant with the Construction Products
Regulation 305/2011.
EN54
-
3 test data: Document D0665
Adhere supplied Gasket to
backbox to maintain IP Rating
115V AC and 230V AC Tone Table
24V DC Tone Table
*To set tones 8, 9 & 10 as first
stage on DC, connect terminal
‘
S2
’
to
‘
-
’
terminal