IECEx Approval 

 

The IS-mA1 Sounder has also been approved to the IECEx 

scheme.  

 

The installation requirements for IS-mA1 sounders approved 

to  the  IECEx  scheme  are  the  same  as  the  installation 

requirements  for  IS-mA1  sounders  approved  to  the  ATEX 

directive. 

 

Certificate No. 

IECEx SIR 06.0045X 

 

Marking:  

Ex ia IIC T4 (Ta = -40

º

C to +60

º

C) 

 

Standards: 

IEC 60079-0:2000 

Edition 3.1

 

 

 

IEC 60079-11:1999 

Edition 4

 

 

 

CONDITIONS  OF  CERTIFICATION  (as  stated  on  the  IECEx 

Certificate of Conformity IECEx SIR 06.0045X) 

 

  The  equipment  has  an  ingress  protection  rating  of 

IP65.  However,  if  it  has  been  supplied  without  a 

cable  entry  device,  then  the  user  shall  ensure  that 

the  devices  that  are  fitted  will  provide  an  ingress 

protection  that is  appropriate  to  the  environment  in 

which it is installed i.e. IP20 on better. If only one of 

the  two  cable  entries  are  used,  then  the  unused 

entry 

knockout

  shall  be  left  intact  or  fitted  with  a 

blanking  device  that  ensues  ingress  protection 

appropriate to the environment in which it is installed 

i.e. IP20 or better.  

 

 

The total capacitance connected to ter w.r.t. 

terminals  -  (i.e.  the  capacitance  of  the  cable  plus 

any other capacitance) shall not exceed 83nF.

 

 

  The equipment shall not be directly installed in any 

process  where  its  enclosure  might  be  electro-

statically  charged  by  the  rapid  flow  of  a  non-

conductive media. 

 

  The equipment shall only be supplied via te 

w.r.t.  terminal  -  from  a  barrier  having  a  maximum 

open  circuit  voltage  Uo  that  is  <  28V  and  a 

maximum  short  circuit  current  Io  that  is  <  93mA, 

where Io is resistively limited.  

 

The  IS-mA1  sounders  are  marked  with  the  certification 

requirements for the ATEX and IECEx and approvals. 

 

e

2S

european safety systems ltd. 

London W3 7QH UK

WARNING: 

TO AVOID A POSSIBLE ELECTROSTATIC

 

CHARGE ONLY CLEAN WITH A DAMP CLOTH 

IS-mA1 Sounder

I

I 1G  EEx ia IIC T4 (-40

º

C <=Ta<= +60

°

C)

0518

SIRA 05ATEX2084X

Year / Serial No. 

  06 / 1MA000001

Ui = 28V   Ii = 93mA   Pi = 660mW   Ci = 0    Li = 0      

Te w.r.t. Terminal -

Ui = 28V   Ii = 0mA   

Terminals S2&S3 w.r.t. Terminal -

www.e2s.com

Ex ia IIC T4 (-40

º

C <=Ta<= +60

°

C)

IECEx SIR 06.0045X

 

 

 

 

FM Approval 

 

The IS-mA1 Sounder has also been FM Listed. 

 

 

Marking:           IS Class I, Zone 0, AEx ia IIC T4 

 

 

          IS Class I, Division 1, Groups A, B, C, D 

 

See  the  Control  Drawings  D  5035  Sheets  1  and  2  for 

installation details and entity parameters. 

 

 

WARNINGS:

IS-mA1 Sounder

              To prevent ignition of flammable or combustible

              atmospheres, disconnect power before servicing

 

Substitution of components may impair safety 

FM

APPROVED

IS Class l, Division 1, Groups A, B, C, D

IS Class I, Zone 0, AEx ia IIC T4 (-40

º

C <=Ta<= +60

°

C)

e

2S

european safety systems ltd.  London W3 7QH UK

Control Drawing D 5035

www.e2s.com

Year / Serial No. 06 / 1MS00001

TO AVOID A POSSIBLE ELECTROSTATIC

 CHARGE ONLY CLEAN WITH A DAMP CLOTH 

 

 

 

 

CPD Directive 89/106/EEC

 

 

The IS-mA1 Sounder is compliant with the 

requirements of the Construction Products Directive 

89/106/EEC. 

 

EN54-3  

Type B   

IP65 

 

Voltage Range 18 

 28V DC via a safety barrier  

       (see sections 6 and 7). 

 

Tone 

             Description 

800/1000Hz @ 0.25 Seconds Alternating 

500/1200Hz @ 0.3Hz 0.5 Sec Gap  Slow Whoop 

1200/500Hz @ 1Hz DIN 

15 

800Hz Continuous 

16 

660Hz 150mS ON 150ms OFF 

17 

554Hz (100mS) / 440Hz (400mS)  NF S 32-001 

 

 

The tones listed have been tested to EN54-3 and are 

compliant  with  the  Construction  Products  Directive 

89/106/EEC. 

 

EN54-3 Test data document D5073 