2) 

The  equipment  may  be  used  in  zones  0,  1  and  2 
with  flammable  gases  and  vapours  with  apparatus 
groups  IIA,  IIB  &  IIC  and  with  temperature  classes 
T1, T2, T3 and T4. 

3) 

The  equipment  is  only  certified  for  use  in  ambient 
temperatures  in  the  range  -40

o

C  to  +60

o

C  and 

should not be used outside this range. 

4) 

The  certificate  number  has  an  ‘X’  suffix,  which 
indicates  that  the  certificate  contains  one  of  more 
special  conditions  for  safe  use.  Those  installing  or 
inspecting the equipment should refer to this section 
of the certificate. 

5) 

The equipment has not been assessed as a safety-
related  device  (as  referred  to  by  Directive  94/9/EC 
Annex II, clause 1.5). 

6) 

Installation of this equipment shall be carried out by 
suitably-trained personnel in accordance with the 
applicable code of practice. 

7) 

Repair of this equipment shall only be carried out by 
the manufacturer or in accordance with the 
applicable code of practice. 

8) 

The certification of this equipment relies on the 
following materials used in its construction: 

 

 

 

Enclosure:

 

ABS Plastic

 

 

 

 

If the equipment is likely to come into contact with 
aggressive substances, then it is the responsibility of 
the user to take suitable precautions that prevent it 
from being adversely affected, thus ensuring that the 
type of protection is not compromised. 

 

“Aggressive substances” - e.g. acidic liquids or 
gases that may attack metals, or solvents that may 
affect polymeric materials. 

 

“Suitable precautions” - e.g. regular checks as part 
of routine inspections or establishing from the 
material’s data sheet that it is resistant to specific 
chemicals. 
 

SPECIAL CONDITIONS FOR SAFE USE (as stated on the 
EC Type Examination Certificate SIRA 04ATEX2301X) 

 
The  equipment  shall  only  be  supplied  via  Terminals  +  w.r.t. 
Terminals  -  from  a  barrier  having  a  maximum  open  circuit 
voltage Uo that is < 28 V and a maximum short circuit current 
Io that is < 93 mA, where Io is resistively limited. The barrier 
shall be ATEX certified by a notified body. 
 
The total capacitance connected to ter wrt – (i.e. the 
capacitance  of  the  cable  plus  any  other  capacitance)  shall 
not exceed 83nF. 
 
The  enclosure  is  non-conducting  and  may  generate  an 
ignition-capable  level  of  electrosatic  charges  under  certain 
extreme  conditions.  The  user  should  ensure  that  the 
equipment  is  not  installed  in  a  location  where  it  may  be 
subjected  to  external  conditions  that  might  cause  a  build-up 
of  electrostatic  charges  on  non-conducting  surfaces, 
additionally,  cleaning  of  the  equipment  should  be  done  only 
with a damp cloth. 
 
The  equipment  has  an  ingress  protection  rating  of  IP66; 
however, if it has been supplied without a cable entry device, 
then  the  user  shall  ensure  that  the  device  that  is  fitted  will 

provide  an  ingress  protection  that  is  appropriate  to  the 
environment in which it is installed i.e. IP20 or better. 
 

4.2  Zones, Gas Groups and Temperature Classification 

The  IS-A105N  sounder  has  been  certified  Ex  ia  IIC  T4  Ga. 

When  connected  to  an  approved  system  it  may  be  installed 

in: 

 

 

Zone 0 

explosive gas air mixture 

 

continuously present. 

 

Zone 1 

explosive  gas  air  mixture  likely  to  occur  in 

normal operation. 

 

Zone 2 

explosive  gas  air  mixture  not  likely  to  occur, 

and if it does, it will only exist for a short time. 

 

 

Be used with gases in groups: 

 

 

 

Group A 

propane 

 

Group B 

ethylene 

 

Group C 

hydrogen 

 

 

Having a temperature classification of: 

 

T1 

450ºC 

T2 

300ºC 

T3 

200ºC 

T4 

135ºC 

 

 

 

4.3  Ter and - 

Power  is  supplied  to  the  sounder  via  the  +  and  –  terminals 

which have the following input safety parameters: 

 

 

 

Ui 

28V 

 

Ii 

93mA 

 

Pi 

 

660mW 

 

 

Ci = 0  Li = 0 

 

 

The  IS-A105N  sounder  may  be  powered  from  an  ATEX 

certified Zener barrier or galvanic isolator which have output 

parameters  equal  to  or  less  than  28V,  93mA  and  660mW 

where  Io  is  resistively  limited.  The  cable  parameters  stated 

on  the  selected  Zener  barrier  or  galvanic  isolator  certificate 

must be observed. 

 

Up to three IS-A105N sounders can be connected in parallel 

and  powered from  a  common barrier or  isolator. Connecting 

two sounders in parallel will reduce the output from each by 

about  3dB.  Three  sounders  should  only  be  powered  from  a 

common  supply  when  the  maximum  supply  voltage  is 

available. 

 

 

4.4  Terminals S2 and S3  

When terminals S2 or S3 are connected to 0V (- terminal) the 

sounder  output  tone  changes  to  the  second  or  third  stage 

alarm  respectively.    The  input  safety  parameters  for  these 

terminals are: 

 

 

 

Ui 

28V 

 

 

Ii 

0mA  

 

 

Because  the  permitted  input  current  is  zero,  these  terminals 

may  only  be  connected  to  a  diode  return  barrier,  an 

Summary of Contents for IS-AL105NL

Page 1: ...be tested or used in safe areas without a Zener barrier or galvanic isolator but at supply voltages above 16V the internal current limit will function and therefore it is recommended that they are no...

Page 2: ...l capacitance connected to terminals wrt i e the capacitance of the cable plus any other capacitance shall not exceed 83nF The enclosure is non conducting and may generate an ignition capable level of...

Page 3: ...manual The power supply terminals and are duplicated so that sounders may be connected in parallel or an end of line monitoring resistor may be fitted d Select the required output tone by positioning...

Page 4: ...tinuous 2000Hz Intermittent 800Hz 0 25s ON 1s OFF Alternating 544Hz 100ms 440Hz 400ms NFS 32 001 Motor Siren Slow rise to 1200Hz Motor Siren Slow rise to 800Hz Continuous 1200Hz Motor Siren Slow rise...

Page 5: ...e IS A105N sounder second and third stages may be activated by using Galvanically Isolated Relays that have output parameters within the limits specified in section 4 4 which have been certified Ex ia...

Page 6: ...er shall ensure that the device that is fitted will provide an ingress protection that is appropriate to the environment in which it is installed i e IP20 or better 4 The enclosure is non conducting a...

Page 7: ...fe Systems for Hazardous Classified Locations and the National Electrical Code ANSI NFPA 70 5 The resistance between the intrinsically safe ground and the earth ground must be less the 1 ohm 6 The Shu...

Page 8: ...ne and Group of use 6 The IS A105N Sounder enclosure has an ingress protection rating of IP 66 If supplied without cable entry devices then metallic or plastic cable glands or conduit hubs shall be fi...

Reviews: