7) 

Electrical  System  Design  For  Installation  In 
Hazardous Areas Using Galvanic Isolators

 

 

Galvanic  isolators  although  more  expensive  than  Zener 
barriers, do not require a high integrity earth connection. For 
small  systems  where  a  high  integrity  earth  is  not  already 
available,  the  use  of  galvanic  isolators  often  reduces  the 
overall installation cost and simplifies design. 

 

7.1  Single stage alarm 

The  IS-A105N  sounder  may  be  powered  by  any  galvanic 
isolator having output parameters within the limits specified in 
section 4.3, which has been certified Ex ia by an EC Notified 
Body.  The sounder may be controlled by turning the galvanic 
isolator on and off, or by a mechanically activated switch on 
the hazardous area side of the isolator. 

+

IS-A105N
Sounder

+

-

Hazardous Area

Safe Area

-

Power

Galvanic 
Isolator

 

 

Fig 6  Single stage alarm using galvanic isolator. 

 

7.2  Multi stage alarm 

The  IS-A105N  sounder  second  and  third  stages  may  be 
activated  by  using  Galvanically  Isolated  Relays  that  have 
output  parameters  within  the  limits  specified  in  section  4.4. 
which have been certified Ex ia by an EC Notified Body. 

 

Safe Area

Hazardous Area

-

S2

IS-A105N
Sounder

+

-

Galvanic Isolated Relay

-

Galvanic Isolator

+

Power

Power

 

Fig 7  Multi stage alarm using galvanic isolated relays 

 
 

8) 

Cable Parameters 

 
The  maximum  permitted  cable  parameters  are  as  specified 
on the certificate of the Zener barrier or galvanic isolator that 
has been selected for the installation. Normally the limits are 
not  restrictive,  but  care  should  be  taken  not  to  exceed  a 
capacitive limit of 83nF for installations when very long cables 
are used. 
 
 
 

9) 

 Volume Control

 

 

The  output  level  of  the  IS-A105N  sounder  can  be  set  by 
adjusting the volume control potentiometer (see Fig 2). 

 
 

10) 

Servicing

 

 

No  attempt  should  be  made  to  repair  a  faulty  IS-A105N 
sounder. Suspect sounders should be returned to European 
Safety Systems Ltd. for repair. 
 

11) 

 Guarantee

 

 
Sounders  that  fail  within  the  guarantee  period  should  be 
returned  to  European  safety  Systems Ltd.    It  is  helpful  if  a 
brief description of the fault symptoms is provided. 
 