E2S HA121 Installation Instructions Download Page 2

ISN5201-A

ATTENTION

No  liabil ity i s  acce pted f or an y consequen ce of  the  u se of  this d ocume nt. Th e technical   specificat ion o f this unit  is  su bject  to ch ange withou t noti ce due   to o ur pol icy
of  contin ual product   devel opmen t. All  dimen sions are a pproximate. This  u nit i s sold  subj ect to   our standa rd con ditio ns of  sale,  a cop y of which  is ava ilable  on

Disconnect from pow er  source to prev ent electrical shock before  installing and serv icing

Couper l’ alime ntati on pour empêcher  tout  choc é lectrique  av ant  d’effectuer des  trav aux d’i nstal lation et

d’e ntreti en.

Vor der I nstall ation  und Wartung v on  der  Spannungsquel le abnehmen,  um e lektri sche  S chläge zu v ermeiden.

Pri ma del l’ins tallazione  e  del la manutenzione s pegne re l’a limentazione ele ttric a  per  ev ita re scosse

ele ttric he.

Des conecte la  alimentación para  ev itar de scarga s elé ctrica s antes de  la  instala ción y mantenimie nto

Antes de  instal ar  ou de fa zer a  manutenção  desligue se mpre da alimentaç ão elé ctrica   para  ev ita r choques

elé ctric os.

Strømmen  skal a fbrydes  v ed insta lleri ng og  eftersyn for at  undgå  elektrisk stød.

Los koppel en v an  de e lektri sche v oeding  om e lektri sche  schok  v óór  i nstal latie  en onderhoud  te v oorkomen.

Før monte ring e ller  v edlik ehold,  må spenningen koples  fra  for å  unngå s trømstøt.

Bryt strömmen  innan  instal lation och  underhåll för att förhindra   elektriska  stöta r stötar.

Wiring configuration for 24vdc  units.

Wiring configuration for 115, 230vac units.

Fig. 1

Stage1

Alarm

Stage2

Stage3

tone

Description

(S2)

(S3)

Header

3

Tone 1

Industrial Hooter

Tone 3

Tone 5

2
1

3

Tone 2

High Frequency Mechanical Siren 

Tone 1

Tone 5

2
1

3

Tone 3 

Medium Frequency Mechanical Siren

Tone 1

Tone 5

2
1

3

Tone 4

Electro Mechanical Buzzer

Tone 1

Tone 5

2
1

3

Tone 5

Mechanical Bell

Tone 1

Tone 2

2
1

Fig. 2

Mounting and cabling instructions:

The unit can be mounted with either the external lugs or by fixing
through the back of the housing. For internal fixing the HA121 has
BESA compatible fixing positions marked.
THe HA121 is shipped with one M20 clearance cable entry hole
populated with an IP55 stopping plug. For installations requiring
the cable entry to be through the rear of the unit a M20 clearance
‘knockout’ is located in the centre of the back wall of the housing.
The terminals in the HA121 and HAL121 products will accept from
0.5mm² to 4.0mm²  stranded or single core cables.

DC units:

DC power supply connections should be made to the + and -
terminals.
To remotely switch the second and third stage sounds cable into
the terminals marked ‘S2’ and ‘S3’ respectively. To activate the
second and third stage sounds switch ‘S2’ or ‘S3’ to the negative
supply whilst  the unit is powered (see Fig.1). Stage 2 overides
stage 1 and stage 3 overides stage 2.

The Hootronic sounder has the facility to replicate the ‘tail off’
traditionally associated with these tone when generated by
electro-mechanical devices.  The switching is achieved by cabling
into the terminal marked STOP. The user can remotely activate
and de-activate the sounder by switching the  connection between
the STOP wire and the negative supply line whilst the unit is
powered. To achieve the ‘tail off’ sound at switch off the unit must
remain powered.

AC units:

AC power supply connections should be made to the L, N and E
terminals.
To remotely switch the second and third stage sounds cable into
the terminals marked ‘C/-’, ‘S2’ and ‘S3’ respectively. To activate
the second and third stage sounds switch ‘S2’ or ‘S3’ to the ‘C/-’
cable whilst  the unit is powered (see Fig.1). Stage 2 overides
stage 1 and stage 3 overides stage 2.

The Hootronic sounder has the facility to replicate the ‘tail off’
traditionally associated with these tone when generated by electro-
mechanical devices.  The switching is achieved by cabling into the
terminals marked STOP and ‘C/-’. The user  can remotely activate
and de-activate the sounder by switching the connection between
STOP and the ‘C/-’ cables  whilst the unit is powered. To achieve
the ‘tail off’ sound at switch off the unit must remain powered.

Tone Selection:

The Hootronic HA121, HAL121, HAL121L and HAL121B have 5 user selectable ‘traditional’ sounds:

Tone 1 :

Industrial Hooter

Tone 2 :

High Frequency MechanicalSiren

Tone 3 :

Medium Frequency Mechanical Siren

Tone 4 :

Electro Mechanical Buzzer

Tone 5 :

Mechanical Bell

Each of these sounds has two additional, remotely selectable, alarm stages as shown in the table below
(see Fig 2.). The first  stage tone is selected by means of the pin headers marked 1,2,3 on the PCBA.
Use the supplied jumper connectors to select the required tone by following the diagrams in the table below
See ‘Mounting and cabling instructions’ for details of how to activate the second and third stages.