European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH 

 [email protected] 

   Tel: +44 (0)208 743 8880 

    www.e-2-s.com  

 Fax: +44 (0)208 740 4200 

Document No. D156-00-501-IS 

 Issue 1 

 11-12-15 

 Sheet 3 of 3 

12-way 
Terminal block 
(Labeled 1-12) 

External Earth 
Stud 

Internal Earth 
Stud 

M20 x 1.5 
Entries 

M20 x 1.5 
Entries 

12-off 
Standard DIN rails 
(Labelled 1-12) 

4-off  
Bonded Earth  
DIN rails 
(Labelled 13-16)  

External Earth 
Stud 

Internal Earth 
Stud 

12)

Cable Connections

Terminal Block Version (GNExJ2T01) 

The cable connections are made into the terminal block in the 
flameproof enclosure. See section 7 of this manual for access 
to the flameproof enclosure.  

DIN Rail Version (GNExJ2D01) 

The  cable  connections  are  made  into  the  DIN  Rail  in  the 
flameproof enclosure. See section 7 of this manual for access 
to the flameproof enclosure.  

Wires having a cross sectional area of up to 2.5mm² can be 
connected to each terminal way. If an input and output wire is 
required the 2-off Live/Neutral or +/- terminals can be used. If 
fitting  2-off  wires  to  one  terminal  way  the  sum  of  the  2-off 
wires  must  be  a  maximum  cross  sectional  area  of  2.5mm². 
Strip  wires  to  8mm. When  connecting  wires  to  the  terminals 
great  care  should  be  taken  to  dress  the  wires  so  that  when 
the cover is inserted into the chamber the wires do not exert 
excess  pressure  on  the  terminal  blocks.  This  is  particularly 
important when using cables with large cross sectional areas 
such as 2.5mm². 

Internal earthing connections should be made to the terminal 
connections  in  terminal  block  or  bonded  Earth  terminals  of 
DIN rail (see figure 5). The earth conductor should be at least 
equal in size and rating to the incoming power conductors. 

External  earthing  connections  should  be  made  to  the  M4 
earth  stud,  using  a  ring  crimp  terminal  to  secure  the  earth 
conductor  to  the  earth  stud  between  the  two  M4  stainless 
steel  flat  washers,  then  reassemble  the  M4  spring  washer 
and tighten the M4 nut to ensure that the cable lug is secured 
against loosening and twisting. The external earth conductor 
should be at least 4mm

2

 in size. 

13)

Maintenance, Overhaul and Repair

Maintenance,  repair  and  overhaul  of  the  equipment  should 
only  be  carried  out  by  suitably  qualified  personnel  in 
accordance with the current relevant standards: 

EN60079-19/IEC60079-19 Explosive 

atmospheres 

Equipment repair, overhaul and reclamation 

EN  60079-17/IEC60079-17  Explosive  atmospheres  - 
Electrical installations inspection and maintenance 

Units must  not  be  opened  while an  explosive  atmosphere  is 
present. 

If  opening  the  unit  during  maintenance  operations  a  clean 

environment must  be maintained  and  any  dust  layer  removed 

prior 

to opening the unit. 

Electrostatic charging hazard - Clean only with a damp cloth. 

14

)

Adapter Options

The  GNEx  Junctino  Box  can  be  supplied  with  the  following 
types of adapters: 

M20 to ½” NPT 
M20 to ¾” NPT 
M20 to M25 

It  is  important  to  note  that  stopping  plugs  cannot  be  fitted 
onto adapters, only directly onto the M20 entries. 

If the installation is made using conduit, openings must have 
a sealing fitting connected as close as practical to the wall of 
the  enclosure,  but  in  no  case  more  than  the  size  of  the 
conduit or 50mm, whichever is the lesser. 

15)

Special Conditions of safe use

The  enclosure  is  non-conducting  and  may  generate  an 
ignition-capable  level  of  electrostatic  charges  under  certain 
extreme  conditions.  The  user  should  ensure  that  the 
equipment  is  not  installed  in  a  location  where  it  may  be 
subjected  to  external  conditions  that  might  cause  a  build-up 
of electrostatic charges on non-conducting surfaces. 

Figure 4 

Figure 5 

Reviews: